Page 1 :
CFH, , EQUIPMENT ABBREVIATIONS, BFP, CB, DET, FCO, FD, GM, HB, LAV, MB, RP, RPZ, SH, SK, TP, TV, WC, WH, WHA, WM, , BACKFLOW PREVENTER, CATCH BASIN, DOMESTIC WATER EXPANSION TANK, FLOOR CLEAN OUT, FLOOR DRAIN, GAS METER, HOSE BIBB, LAVATORY, MOP BASIN, RECIRCULATING PUMP, REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER, SHOWER, SINK, TRAP PRIMER, TEMPERING VALVE, WATER CLOSET, WATER HEATER, WATER HAMMER ARRESTOR, WATER METER, , DRAFTING SYMBOLS, XX, , KEY NOTES, , XX, , DEMOLITION KEY NOTES, , X, PX.X, , 3. NO PLUMBING (WATER, DRAINS, VENT, OR GAS PIPING) SHALL BE INSTALLED DIRECTLY ABOVE ANY ELECTRICAL, PANELS. COORDINATE WITH OTHER DIVISIONS BEFORE PROCEEDING WITH INSTALLATION., 4. IF NON DESIGN BASE EQUIPMENT IS SELECTED, CONTRACTOR SHALL BEAR ADDITIONAL COSTS FOR MODIFICATIONS, TO THE ORIGINAL SYSTEM(S)., 5. PROVIDE WATER HAMMER ARRESTERS AT PLUMBING FIXTURES AND GROUPS OF PLUMBING FIXTURES THAT ARE, SUBJECT TO WATER HAMMER. SELECT ARRESTERS IN ACCORDANCE WITH THE PLUMBING AND DRAINAGE INSTITUTE, STANDARD., 6. CONTRACTOR SHALL FURNISH AND INSTALL ALL MATERIALS, LABOR AND EQUIPMENT PERMIT FEES, REQUIRED FOR,, OR INCIDENTAL TO THE INSTALLATION OF A COMPLETE AND OPERATIONAL PLUMBING SYSTEM AS INDICATED IN THE, CONTRACT DOCUMENTS INCLUDING SPECIFICATIONS., 7. ALL PLUMBING SERVICES GOING INTO THE BUILDING AND LEAVING THE BUILDING SHALL BE CONNECTED TO THE SITE, UTILITIES, COORDINATE WITH SITE UTILITIES DWGS. COORDINATE ALL EXTERIOR UNDERGROUND PLUMBING WORK, WITH THE SITE UTILITIES BEFORE COMMENCING WORK. COORDINATE ALL UNDERGROUND PIPING WITH FOUNDATION, DRAWINGS., 8. ALL PLUMBING WORK SHALL BE IN CONFORMANCE WITH THE OHIO PLUMBING CODE, LATEST EDITION ADOPTED BY, THE STATE OF OHIO WITH OHIO AMENDMENTS, MUNICIPAL OR CITY CODES, AND THE AUTHORITY HAVING, JURISDICTION., 9. INSTALL BALL VALVE CLOSE TO WATER MAIN ON EACH BRANCH AND RISER SERVING PLUMBING EQUIPMENT AND, FIXTURES., 10. SANITARY/VENT FITTING TYPES SHALL BE AS REQUIRED BY THE OHIO BUILDING AND PLUMBING CODE., 11. FIRST FLOOR 100'-0" IS EQUIVALENT TO 891.15 FINISHED FLOOR ELEVANTION., , PLUMBING SYMBOLS, CW, G, HW, , DOMESTIC COLD WATER, NATURAL GAS, DOMESTIC HOT WATER, , HWR, , HOT WATER RETURN, , SAN, , SANITARY, , V, , VENT, BALL VALVE, CALIBRATED BALANCING VALVE, CHECK VALVE, SINGLE LINE - PIPE DROP, SINGLE LINE - PIPE RISE, SINGLE LINE - PIPE RISE TEE, SINGLE LINE - PIPE DROP TEE, TWO LINE - PIPE DROP, TWO LINE - PIPE RISE, , PLUMBING, , GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS, , P0.1, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, LANCASTER, DRAWING NUMBER, , 11/26/2018 12:49:19 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , OHIO, , DRAWN: KB, , X, PX.X, , DETAIL REFERENCE, NUMBER, SHEET ON WHICH DETAIL IS, FOUND, DETAIL REFERENCE, NUMBER, SHEET ON WHICH DETAIL IS, FOUND, , DLZ OHIO, INC, , 559, , 1821-7001-50, , GAS, , PROJECT NUMBER, , WSFU'S, , 2. INSTALLATION OF PLUMBING PIPING SHALL BE FULLY COORDINATED WITH STRUCTURAL, ARCHITECTURAL,, ELECTRICAL, AND HVAC DRAWINGS TO AVOID CONFLICT., , December 6th, 2018, , 56.00, , 1. INSTALLATION OF PLUMBING FIXTURES AND ACCESSORIES, INCLUDING FLUSH CONTROL VALVES INTENDED FOR, PEOPLE WITH DISABILITIES, SHALL BE IN ACCORDANCE WITH ADA REQUIREMENTS., , DATE:, , COLD WATER, , HOT WATER, INVERT ELEVATION, IN JOIST SPACE, INCHES, INFRARED TUBE HEATER, IN WALL SPACE, LEAVING AIR TEMPERATURE, POUNDS OR POUND, LAB EQUIPMENT CONTRACTOR, MAXIMUM, MOP BASIN, 1000 BRITISH THERMAL UNITS PER HOUR, MECHANICAL CONTRACTOR, MECHANICAL, MANUFACTURER, MANHOLE, MINIMUM, MOUNTED, MOUNTING, MAKE-UP WATER, NOT APPLICABLE, NORMALLY CLOSED, NUMBER OR NORMALLY OPEN, NOT TO SCALE, OUTSIDE SCREW & YOKE, OIL WATER SEPARATOR, PLUMBING CONTRACTOR, PRESSURE DROP, POST INDICATING VALVE, PLUMBING, PRESSURE, REQUIRED, ROOM, REVOLUTIONS PER MINUTE, REDUCED PRESSURE ZONE, SHOCK ABSORBER, SANITARY, SILL FAUCET, SHOWER, SHEET METAL, STATIC PRESSURE, SUMP PUMP DISCHARGE, SQUARE FEET, STAINLESS STEEL, STORAGE TANK, THERMOSTAT, STANDARD, STORM, STRUCTURAL, SUCTION, SINGLE WALL, SYSTEM, TEMPERATURE CONTROL PANEL, TRENCH DRAIN, TEMPERATURE, TO FLOOR ABOVE, TO FLOOR BELOW, THERMOMETER, THREADED, THROUGH, TANK, TRAP PRIMER, TYPICAL, UNDER GROUND, URINAL, UNDERGROUND STORAGE TANK, VENT, VACUUM BREAKER, VENT THRU ROOF, WITH, WASHER BOX, WATER CLOSET, WALL CLEAN OUT, WASH FOUNTAIN, WALL HYDRANT, WATER TANK, WATER TEMPERATURE DIFFERENCE, WATER, , ESA, , WSFU'S, , HW, IE, IJS, IN, IRTH, IWS, LAT, LBS/LB, LEC, MAX, MB, MBH, MC, MECH, MFGR, MH, MIN, MTD, MTG, MUW, NA, NC, NO, NTS, OS&Y, OWS, PC, PD, PIV, PLBG, PRESS, REQ'D, RM, RPM, RPZ, SA, SAN, SF, SH, SHT MTL, SP, SPD, SQFT, SS, ST, STAT, STD, STM, STRUCT, SUCT, SW, SYST, TCP, TD, TEMP, TFA, TFB, THERM, THRD, THRU, TK, TP, TYP, UG, UR, UST, V, VB, VTR, W/, WB, WC, WCO, WF, WH, WT, WTD, WTR, , APPRV'D:, , 11.25, , ABOVE, ABOVE FINISHED FLOOR, ABOVE FINISHED ROOF, AIR HANDLING UNIT, ABOVE SUSPENDED CEILING, AVERAGE, BACKFLOW PREVENTER, BRAKE HORSE POWER, BELOW, BUILDING, BOTTOM OF DUCT, BOTTOM OF PIPE, BASEMENT, BOTTOM, COMPRESSED AIR, CAPACITY, CATCH BASIN, CENTRIFUGAL, CUBIC FEET PER MINUTE, CAST IRON, CEILING, CLOSET, CLEANOUT, CONCRETE, CONDENSING UNIT, CONNECT, CONSTANT, CONTRACTOR, CLEANOUT TO GRADE, CIRCULATING PUMP, CLOSE TO WALL, COMBINATION UNIT, COLD WATER, DOMESTIC COLD WATER, DEGREE, DRINKING FOUNTAIN, DOMESTIC HOT WATER, DOMESTIC HOT WATER RETURN, DIAMETER, DISCHARGE, DOWN, ENTERING AIR TEMPERATURE, EMERGENCY EYEWASH, EXHAUST FAN, EFFICIENCY, ELEVATION, ELECTRICAL, ELEVATOR SUMP PUMP, EXPANSION TANK, ELECTRIC WATER COOLER, ELECTRIC WATER HEATER, EXIST/EXISTING, EXHAUST, FLOOR CLEANOUT, FLOOR DRAIN, FROM FLOOR ABOVE, FROM FLOOR BELOW, FINISHED, FLEXIBLE, FLOOR, FROSTPROOF WALL HYDRANT, FILTER/REGULATOR/LUBRICATOR, FEET, FEET OF HEAD, FURNISH, NATURAL GAS, GAUGE, GALVANIZED, GENERAL CONTRACTOR, GENERAL, GALLONS PER MINUTE, GATE VALVE, HOSE BIBB, HORIZONTAL, HORSE POWER, HEATING, HEATER, HEATING, VENTILATING & AIR CONDITIONING, , DATE, , HOT WATER, , AB, AFF, AFR, AHU, ASC, AVG, BFP, BHP, BL, BLDG, BOD, BOP, BSMT, BTM, CA, CAP, CB, CENT, CFM, CI, CLG, CLO, CO, CONC, COND, CONN, CONST, CONTR, COTG, CP, CTW, CU, CW, DCW, DEG, DF, DHW, DHWR, DIA, DISCH, DN, EAT, EEW, EF, EFF, EL, ELECT, ESP, ET, EWC, EWH, EX, EXH, FCO, FD, FFA, FFB, FIN, FLEX, FLR, FPWH, FRL, FT, FTHD, FURN, G, GA, GALV, GC, GEN, GPM, GV, HB, HORIZ, HP, HTG, HTR, HVAC, , REVISION, , DFU'S, , NO., , 54, , PLUMBING GENERAL NOTES, , DESIGNED: KB, , SANITARY, , PLUMBING ABBREVIATIONS, , CHK'D: MLV, , PLUMBING BASIS OF DESIGN
Page 2 :
P1.1 CODED NOTES, , 6" EX SAN LINE TO BE, REMAIN AND REUSE., NEW SAN LINE WILL, CONN TO EX., , 6" EX SAN CO PLUG, TO REMAIN. REFER TO, C7.0 FOR EXACT, LOCATION., , A, , REMOVE 4" EX SAN PIPING, UP TO THE 90° EL FITTING., CAP PIPE OPENING., , EX G LINE. REFER TO, C7.0 FOR EXACT, LOCATION., , A, , EX SAN CO PLUG TO, REMAIN. REFER TO, C7.0 FOR EXACT, LOCATION., , A, , G PIPE UP, TO GM., , REMOVE 4" EX SAN PIPING, UP TO THE 45° T FITTING., CAP PIPE OPENING., , D, E, F, G, , H, , K, K, , I, , B, B, , B, , J, , K, , C, , K, , C, K, , B, , K, , D, , L, , ABANDON EX SAN PIPE., REMOVE EX SAN PIPING., REMOVE 2" EX G PIPING. ANY GAS PIPING REMAINS IN THE CRAWL, SPACE NEEDED TO BE PURGED BEFORE IT IS CAPPED., REMOVE 3/4" EX DCW PIPING., REMOVE 3/4" EX DHW PIPING., REMOVE EX PLUMBING FIXTURES AND CONNECTED PLUMBING PIPING., REMOVE PIPING BELOW GROUND LEVEL. CAP PIPE OPENINGS., REMOVE EX PLUMBING FIXTURES AND CONNECTED PLUMBING PIPING., REMOVE ALL PIPINGS BEHIND THE WALL AND THRU BASEMENT FLOOR., PATCH WALL AND FLOOR OPENING. CAP PIPE OPENINGS., REMOVE EX SAN PIPE FROM SECOND FLOOR AND PATCH PIPE, OPENING. SAW CUT EX SAN PIPE CLOSE TO FLOOR. REMOVE SAN PIPE, IN BULKHEAD AND CHASE. CAP PIPE OPENING., REMOVE EX DCW PIPE FROM SECOND FLOOR AND PATCH PIPE, OPENING. SAW CUT EX DCW PIPE CLOSE TO FLOOR. REMOVE DCW PIPE, IN BULKHEAD AND CHASE. CAP PIPE OPENING., REMOVE EX DHW PIPE FROM SECOND FLOOR AND PATCH PIPE, OPENING. SAW CUT EX DHW PIPE CLOSE TO FLOOR. REMOVE DHW PIPE, IN BULKHEAD AND CHASE. CAP PIPE OPENING., FIELD VERIFY FOR ALL PLUMBING PIPE INVERT ELEVATION. REMOVE, ALL EXPOSED PLUMBING PIPING ABOVE FINISHED GRADE. REMOVE ALL, PLUMBING PIPING WITH LESS THAN 12" FROM NEW GROUND LEVEL., REMOVE EX V PIPE., , DLZ OHIO, INC, , A, B, C, , K, , E, D, , REMOVE ALL PIPING IN, ACCESSIBLE AREA AND, CAP PIPE OPENINGS., TYP OF 5, , WH-EX, , E, , A, E, , C, , D, , C, , RETAIN REMOVED WM-EX., WM-EX TO BE RETURNED TO, WATER COMPANY., , D, , REMOVE 3/4" EX WATER SERVICE, INLET PIPING AND WATER, METER. SAW CUT PIPING CLOSE, TO WALL AND CAP., , REMOVE WH-EX AND, ASSOCIATED PIPES,, VALVES, AND, APPURTENANCES., , C, , 1, P1.1, , BASEMENT PLUMBING REMOVAL, SCALE: 3/16" = 1'-0", , REVISION, , DATE, , NORTH, , D, , LANCASTER, , 2, NORTH, , FIRST FLOOR PLUMBING REMOVAL, SCALE: 3/16" = 1'-0", , DRAWING NUMBER, , 11/26/2018 12:49:21 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , D, , 1821-7001-50, , P1.1, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , H, , P1.1, , PROJECT NUMBER, , December 6th, 2018, DATE:, , ESA, , J, , PLUMBING, , I, , BASEMENT & FIRST FLOOR PLUMBING REMOVAL, , REMOVE ALL ABANDONED, PIPING. PATCH WALL, OPENING., , G, , OHIO, , DRAWN: KB, , L, , APPRV'D:, , F, L, , DESIGNED: KB, , F, , CHK'D: MLV, , NO., , GM-EX TO REMAIN, AND REUSE.
Page 3 :
P1.2 CODED NOTES, A, B, , DLZ OHIO, INC, , C, D, , REMOVE EX PLUMBING FIXTURES AND CONNECTED SAN, V, DCW, AND, DHW PIPING. SEAL FLOOR PIPE OPENINGS., REMOVE EX V PIPE UP IN ATTIC. EX V PIPE OPENING THRU ROOF TO BE, USED FOR NEW V PIPE INSTALLATION., REMOVE EX V PIPE., REMOVE EX V PIPE IN ATTIC AND THRU ROOF., , C, , REVISION, , DATE, , A, , 1, , SECOND FLOOR PLUMBING REMOVAL, SCALE: 3/16" = 1'-0", , 1821-7001-50, , PROJECT NUMBER, , DATE:, , ESA, APPRV'D:, , P1.2, NORTH, , ATTIC PLUMBING PIPING REMOVAL, SCALE: 3/16" = 1'-0", , PLUMBING, , 2, , P1.2, , LANCASTER, , C, , DRAWING NUMBER, , 11/26/2018 12:49:23 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , D, , SECOND FLOOR PLUMBING REMOVAL, , B, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , OHIO, , D, , DESIGNED: KB, , DRAWN: KB, , CHK'D: MLV, , NORTH, , December 6th, 2018, , NO., , P1.2
Page 4 :
EX SAN CO PLUG TO, REMAIN. REFER TO, C7.0 FOR EXACT, LOCATION., , DLZ OHIO, INC, , 6" EX SAN SERVICE LINE., REFER TO C7.0 FOR, EXACT LOCATION AND, INVERT ELEVATION., 6" NEW SAN LINE BELOW, RAMP. REFER TO C7.0 FOR, EXACT LOCATION ANE IE., 4" NEW SAN DROP TO 6", NEW SAN SERVICE LINE, INLET TO BUILDING. REFER, TO 1/P3.2 FOR DETAIL., , 2"ø V UP, 3" SAN, , ELEV, 106, , MAP, STORAGE, X19, , 4" SAN, WC-1, , MB-1, FD-2, JAN., 105, , 4" SAN, , FD-1, , GIS, X18, , 3, P4.1, , FD-1, , MEN'S RR, 108, , WOMEN'S RR, 107, , SP-1, , FCO-1, , 1/2" TP LINE DN, FROM FIRST, FLOOR ACS, , BTM OF CB-1, AT IE ± 93.49., 1-1/2" SAN UP, FROM SP-1, , WC-1, , CB-1, 4" SAN, FCO-1, , 1 1/2" SAN, LOBBY/, SERVICE, 102, , VESTIBULE, 101, , CORRIDOR, 103, , HEARING, WAITING, X14, , CORRIDOR, X20, , CORRIDOR, X11, , ANTEROOM, 110, , CONVEYANCE, 104, , BOR OFFICE, X12, , CORRIDOR, X15, , MAP ROOM, X17, , HEARING, ROOM, X13, , 2, , REVISION, , DATE, , SERVICE, AREA, X16, , FIRST FLOOR UNDERFLOOR SAN & V PLAN, , P2.1, , SCALE: 3/16" = 1'-0", , WOMEN'S RR, 205, , 2" SAN DN FROM, ATTIC SPACE., , REF., , CLOSET, X26, , 2" SAN, FCO-1, , 1 1/4"ø V UP, , F-1, , MECH/, STORAGE, 202, , 2" SAN, , FCO-1, , CORRIDOR, 204, , CORRIDOR, X24, , IT/DATA, X21, , 1/2" TP LINE DN, FROM SECOND, FLR ACS, CORRIDOR, X25, , APPRAISAL, X29, , 1 1/4"ø V UP, , CONFERENCE, 203, , DATA, COLLECT./, CAUV, X23, , FCO-1, , 1/2" TP LINE, , FD-1, , GIS OFFICE, X22, , F-4, , 1, P2.1, NORTH, , SECOND FLOOR UNDERFLOOR SAN & V PLAN, SCALE: 3/16" = 1'-0", , DRAWING NUMBER, , LANCASTER, , MECH/ ELEC, 207, , 11/26/2018 12:49:26 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , 1/2" TP LINE, FIRST FLR ACS, , 2" SAN, , FD-1, , 2" SAN, , 2" SAN, , 2" SAN, , PLUMBING, , 1-1/4" SAN DN, FROM SK-1., , 4, P4.1, , FD-1, , PROJECT NUMBER, , December 6th, 2018, DATE:, , ESA, , FIRST & SECOND FLOOR UNDERFLOOR PLUMBING PLAN 1821-7001-50, , FD-1, , RE, CONTRACT, X27, , P2.1, , 1/2" TP LINE, DN TO, FIRST FLR., , ELEV, 106, ELEVATOR, LOBBY, 201, , WC-1, MEN'S RR, 206, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , 1 1/2" V UP, FROM, FIRST FLOOR, , WC-1, , BREAK ROOM, X28, , OHIO, , 1 1/2" V, , APPRV'D:, , 2"ø V UP, , DESIGNED: KB, , DRAWN: KB, , CHK'D: MLV, , NO., , NORTH
Page 5 :
DLZ OHIO, INC, , 1 1/4"ø V UP, , 3"ø V UP, 3" V, 1/2" TP LINE, 3"ø V UP, , 2" V, , 1 1/2" V, , 2" V, 2"ø V UP, , 3" V, , FD-1, , 1 1/4" V, , 2"ø V UP, , 1 1/4" V FROM SK-1. V, RISE TO SECOND FLOOR, ABOVE CEILING SPACE., , PROVIDE FD-1, WITH ASSE 1072, RATED TRAP SEAL., , 1/2" TP LINE, , 1/2" TP LINE, , 2" V, 2" V, , PROVIDE FD-1, WITH ASSE 1072, RATED TRAP SEAL., , FCO-1, , 2" V, , 2" SAN, , 1 1/4" V, , 1 1/4" V, , 1/2" TP LINE, , 2"ø SAN DN, , 1 1/4" V UP, BELOW THE, ATTIC ROOF., , 1 1/4"ø V UP, FD-1, , 2, , REVISION, , DATE, , 1/2" TP LINE, , ATTIC UNDERFLOOR SAN & V PLAN, , P2.2, , SCALE: 3/16" = 1'-0", , 1 1/4" V, FROM FFB, , F-3, , F-6, , F-5B, , 1, P2.2, NORTH, , ATTIC ABOVE FLOOR SAN & V PLAN, SCALE: 3/16" = 1'-0", , DRAWING NUMBER, , LANCASTER, , F-5A, , 11/26/2018 12:49:29 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , FD-1, , PROJECT NUMBER, , December 6th, 2018, DATE:, , 1821-7001-50, PLUMBING, , FCO-1, , ATTIC UNDERFLOOR & ABOVE PLUMBING PLAN, , 1 1/4" V, FROM FFB, , 1/2" TP LINE, TO FFB, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , FD-1, , P2.2, , 1 1/4" V, , 1 1/4" V, , 3" V THRU, ROOF, , ESA, , OHIO, , 1 1/4" V, , APPRV'D:, , DRAWN: KB, , 3" V THRU, ROOF. USE EX, ROOF OPENING., , 1 1/4" V, FROM FFB, , DESIGNED: KB, , CHK'D: MLV, , NO., , NORTH
Page 9 :
DLZ OHIO, INC, , 2" V, , 2" V, , 2" V, , 1 1/4, , "V, , 3" V, , 3" V, , 1 1/4" V, , 1 1/4" V, , 3" VTR, , 1 1/4, , 2" V, , 2" V, , 3" V, , 3" VTR, , FD-1, , "V, , FCO-1, , 2" SAN, , 2" V, , FCO-1, , 1 1/2" V, , FD-1, , FD-1, , 1 1/2, , FCO-1, , "V, , 1 1/4" V, , 2" V, , FD-1, , N, , 2, , N, " SA, 2" SAN, , WC-1, 2" SAN, , AN, 2" S, , FD-2, , MB-1, , December 6th, 2018, , ESA, , OHIO, , V, 2", , 1821-7001-50, , FCO-1, , PROJECT NUMBER, , 1 1/2" SAN, , DATE:, , 2" SAN, , AN, 2" S, , 4" SAN, , FWD-1, , CHK'D: MLV, , 1 1/2" V, , SK-1, , NO., , 2" SAN, , 2" V, , 2" SAN, , FD-1, , FCO-1, , REVISION, , WC-1, , 2" S, A, , 2" SAN, , FD-1, , APPRV'D:, , AN, 2" S, , DESIGNED: KB, , "V, , 4" V, , DRAWN: KB, , 1 1/4, , 1 1/, , DATE, , 1 1/4" V, , 1 1/4" V, , 1 1/2" SAN, , 4" NEW SAN LINE., IE ± 97.50 BEFORE, 45° EL FITTING TO, THE DROP, , 1 1/2" SAN, , 2" SAN, FCO-1, , 3" SAN, , WC-1, , CHECK VALVE, WCO-1, , CB-1, , FD-1, SP-1, 4" SAN, 4" SAN, 4" SAN, FROM WC-1., TYP OF 4, , NOTE:, FIRST FLOOR 100'-0" IS, EQUIVALENT TO 891.15, FINISHED FLOOR ELEVANTION., , 6" SAN SERVICE LINE. IE ±, 91.75. REFER TO C7.0 FOR, EXACT LOCATION., , LANCASTER, , SANITARY AND VENT ISOMETRIC VIEW, SCALE: N.T.S., , DRAWING NUMBER, , 1, P3.2, , 11/26/2018 12:49:38 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , AN, 2" S, , PLUMBING, , WC-1, 2" SAN, , ISOLATION VALVE, , SANITARY AND VENT ISOMETRIC VIEW, , AN, 4" S, , P3.2, , 2" V, , FD-1, , 4" SAN, , LAV-1, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , 4" SAN
Page 10 :
P3.3, , 1, , SCALE: N.T.S., , NATURAL GAS ISOMETRIC VIEW, 2" G, , 2" G, , F-2, 60 CFH, December 6th, 2018, , 1821-7001-50, , PROJECT NUMBER, , DATE:, , NO., , REVISION, , 3/4" G, , 1 1/4" G, , DATE, , 1 1/4" G, , 3/4" G, , 3/4" G, , 3/4" G, , DLZ OHIO, INC, , 1 1/4" G, , PLUMBING, , EX GM AND GAS SERVICE, INLET. REFER TO C7.0, FOR EXACT LOCATION., , NATURAL GAS ISOMETRIC VIEW, , F-1, 60 CFH, ESA, , CHK'D: MLV, , 1 1/4" G, , APPRV'D:, , 1 1/4" G, , DESIGNED: KB, , 1 1/4" G, GAS PRESSURE, REDUCING VALVE, , DRAWN: KB, , F-4, 60 CFH, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , OHIO, , 2" G, , WH-1, 199 CFH, , P3.3, , GM-EX, TOTAL 559 CFH, , 3/4" G, , 1 1/4" G, , DRAWING NUMBER, , LANCASTER, , 11/26/2018 12:49:39 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , 3/4" G, , 1" G, , F-6, 60 CFH, , F-3, 80 CFH, 60 CFH, , F-5B, , F-5A, , 60 CFH, , 3/4" G, , 1 1/4" G, , 1 1/4" G, , 1 1/4" G
Page 11 :
SECOND FLOOR, 113' - 7", 4" SAN PIPE UP, TO WCO-1., EWH-1, , 2" DCW, , WOMEN'S RR, 107, , WC-1, , RPZ-1, , 4", S, , AN, , 4", , N, SA, , EWH-1, , 1" DCW TYP OF 2, WC-1, , WOMEN'S RR, 107, , 4" SAN, , 1/2" TP LINE FROM FIRST, FLR ACS THRU WALL., TYP OF 2, , EWH-1, , MEN'S RR, 108, , WC-1, , JAN., 105, , WM, , EWH-1, , 4" SAN DN FROM, ABOVE., , HB-1, , WC-1, MEN'S RR, 108, , TP-1, , 1 1/2" DCW, , 4" SAN DN FROM WC-1., TYP OF 2, , DLZ OHIO, INC, , WCO-1, , WHA-1, , 3/4" DCW, , 1/2" TP LINE, , 1/2" TP, , FD-1, , FD-1, , RPV-1, , AN, , 1/2" TP LINE, , 3/4" DCW, 3/4" DHW, , 2", S, , S, 2", , FIRST FLOOR, 100' - 0", , 1 1/2" DCW, , AN, , 2"ø V UP, 4" SAN, , FD-2, 4" SAN, , 2" DCW, , LAV-1, , NOTE:, FIRST FLOOR 100'-0" IS, EQUIVALENT TO 891.15, FINISHED FLOOR ELEVANTION., , GROUND LEVEL, 96' - 0", , 1-1/4" SAN, FROM LAV-1., TYP OF 2, , 2" WATER SERVICE, ENTRANCE. IE ± 91.32, , 3, , 5, , LAV-1, , LAV-1, , 3/4" DHW, 3/4" DCW, 3/4" DHW, 2" DCW, , 2"ø SAN DN, 4" SAN, , 1, , FIRST FLOOR RESTROOM ENLARGED SAN PLAN, , P4.1, , BASEMENT, 91' - 0", , P4.1, , LAV-1, , SCALE: 1/2" = 1'-0", , P4.1, , NORTH, , FIRST FLOOR RESTROOM ENLARGED PLAN, SCALE: 1/2" = 1'-0", , NORTH, , WATER SERVICE ENTRANCE SECTION, SCALE: 1/4" = 1'-0", , 4" SAN DN FROM WC-1., TYP OF 2, EWH-1, , WC-1, , WC-1, , 4"ø SAN DN, MEN'S RR, 206, , TP-1, , 1/2" TP LINE DN FROM FIRST, FLOOR ACS. SERVING TWO, (2) FD-1 ON FIRST FLOOR., TYP OF 2, , MEN'S RR, 206, , WOMEN'S RR, 205, , 1" DCW, TYP OF 2, , TP-1, WHA-1, , 1/2" TP, LINE, , FD-1, 1/2" TP LINE, , 3/4" DCW, 3/4" DHW, , LAV-1, , LAV-1, , 3/4" DHW, , 3/4" DCW, , AN, , WH-1 SECTION, SCALE: 1/4" = 1'-0", , 4, P4.1, , SCALE: 1/2" = 1'-0", , P4.1, NORTH, , SECOND FLOOR RESTROOM ENLARGED PLAN, SCALE: 1/2" = 1'-0", , PLUMBING, , PLUMBING ENLARGED PLANS & SECTIONS, , P4.1, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, LANCASTER, DRAWING NUMBER, , 11/26/2018 12:49:43 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , OHIO, , NORTH, , 2, , SECOND FLOOR RESTROOM ENLARGED SAN PLAN, , 1821-7001-50, , 2", S, , PROJECT NUMBER, , 1-1/4" SAN, FROM LAV-1., TYP OF 2, , December 6th, 2018, , SECOND FLOOR, 113' - 7", , DATE:, , P4.1, , 2" DCW, , 1" DHW, , ESA, , 6, , LAV-1, , APPRV'D:, , DET-1, , LAV-1, , NO., , EXTEND 3/4", DRAIN TO FD-1., , WOMEN'S RR, 205, , 2" SAN, , ISOLATION VALVE, TYP OF 2, CHECK VALVE, , DESIGNED: KB, , AN, , 2"ø V UP, 2"ø V UP, , CHK'D: MLV, , 2", S, , FD-1, , REVISION, , 1/2" TP LINE, , CHECK VALVE, STRAINER, , DATE, , WC-1, , 1/2" TP LINE FROM SECOND, FLR ACS THRU WALL., TYP OF 2, , STRAINER, , ISOLATION VALVE, TYP OF 2, , WC-1, , DRAWN: KB, , GAS PRESSURE, REDUCING VALVE, , T & P RELIEF VALVE, , EWH-1, , 1 1/2"ø DCW DN, , 1 1/2" DCW, , WH-1, , 3/4" DHWR, 1 1/2" DCW, ISOLATION, VALVE, , 2" V UP FROM 4" SAN. MERGE, 2" V TO 3" V AFTER THE, SECOND FLOOR WC-1., , EWH-1, , AN, , 1 1/4" G, , 1 1/2" V, 1 1/2" DHW, , 2" V, , ROOF BEARING, 126' - 8", , EWH-1, , 3"ø V UP, , 2", S, , 2" V
Page 12 :
ADJUSTABLE SHANK, FLOOR TILE, CLAMPING COLLAR, , DLZ OHIO, INC, , INCOMING GAS LINE, , TILE BED, , EQUIPMENT, 1/2" Ø THREADED ROD, , LUBRICATED, PLUG VALVE, , CLEVIS PIPE HANGER, , DIRT LEG, PIPE INSULATION WITH, VAPOR BARRIER, , UNION, PIPE REDUCER FROM BRANCH PIPE SIZE, TO UNIT CONNECTION SIZE. PROVIDE AT, UNIT, , 3, P5.1, , 3'-0" x 3'-0" x 4 LB., PER S.F. LEAD PAN, , 2, , TYPICAL GAS EQUIPMENT CONNECTION DETAIL, , P5.1, , SCALE: N.T.S., , 180° SECTION OF RIGID, INSULATION MIN. 12" LONG, (TYP. FOR ALL PIPING), , 18" LONG 16 GAUGE, GALV. PIPE SHIELD, , CONNECT TO P-TRAP, , 1, , FLOOR DRAIN DETAIL, , P5.1, , SCALE: N.T.S., , PIPE SUPPORT DETAIL, SCALE: N.T.S., , 1" INTO VENT, TURN FLASHING DN., , 1' - 0", , 3 LB. LEAD FLASHING, ROOFING - SEE, ARCHITECTURAL DRAWINGS, FOR ROOF CONSTRUCTION, , 8", , WIRING TO 120 VOLT SOURCE BY, ELECTRICAL CONTRACTOR, 5° DIFFERENTIAL AQUASTAT "HONEYWELL", MODEL 4006, 120 VOLT SINGLE PHASE, HOT WATER RECIRCULATING PUMP, , AIR VENT, , WH, 1, , T & P RELIEF, VALVE, , 1/2" TRAP PRIMER LINE, , G, SLEEVE THRU, SLAB, , DATE, OHIO, , DISTRIBUTION UNIT,, FOR 4 LINES OR VARIES., , DRAWN: KB, , TRAP PRIMER VALVE, , 1821-7001-50, , DOMESTIC WATER LINE, , PROJECT NUMBER, , 1/2" TRAP PRIMER SUPPLY, , December 6th, 2018, , SCALE: N.T.S., , DATE:, , P5.1, , SCALE: N.T.S., , HOT WATER RECIRCULATING PUMP DETAIL, , ESA, , 4, , APPRV'D:, , "Y" STRAINER WITH BLOW, DOWN DRAIN VALVE &, HOSE BIBB, , UNION (TYP.), , REVISION, , FLOW DIRECTION, , CHECK VALVE, , VENT THRU ROOF DETAIL, , P5.1, , HOT WATER RETURN, PIPING SEE PLANS, FOR SIZE, , NO., , PIPING TO WATER, HEATER SEE, PLANS FOR SIZE, , REFER TO PLANS FOR, SIZE OF VENTING, , DESIGNED: KB, , NOTE:, VENT PIPE AND LEAD FLASHING, SHALL BE INSTALLED BY THE, PLUMBING CONTRACTOR PRIOR, TO ROOFING IS APPLIED., COORDINATE W/ THE GENERAL, CONTRACTOR., , HHWR OUT, , CHK'D: MLV, , STRUCTURE, , 5, , BALL VALVE (TYP.), , SECURELY FASTEN VENT, PIPING TO STRUCTURE, USING STEEL ANGLES,, BOLTED TO STRUCTURE, , FLOOR SLAB, , EXTEND 3/4", DRAIN TO FLOOR, DIRT LEG, DHWR, RP, 1, , 6, ET, , ISOLATION VALVE, , P5.1, , TRAP SEAL PRIMER DETAIL, SCALE: N.T.S., , 1, , UNION, PRESSURE REGULATING VALVE, , CW, , CHECK VALVE, , COLD WATER INLET, , 7, P5.1, , GAS WATER HEATER DETAIL, SCALE: N.T.S., , DRAWING NUMBER, , NOTE:, 1. THE AIR VENT IS TO BE INSTALLED AT THE HIGHEST LOCATION OF THE SYSTEM. THE, DIAMETER OF THE PIPE LEADING UP THE AIR VENT IS TO BE NO SMALLER THAN THE PIPING, THROUGHOUT THE SYSTEM., 2. RECIRCULATION PUMP IS TO BE CONTROLLED BY THE DUAL-SET AQUASTAT WITH TIMER., 3. THE RECIRCULATION PUMP IS TO PROVIDE NO LESS THAN 2 GPM AND NO MORE THAN 3, GPM THROUGH EACH ACTIVATED UNIT IN THE SYSTEM,, , LANCASTER, , Y-STRAINER, , 11/26/2018 12:49:44 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , DHWR, , PLUMBING, , 1/2" BYPASS, , PLUMBING DETAILS, , HW, , P5.1, , 110°F HW, , DHW TO FIXTURES, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , FLOOR DRAIN, , 1 1/4" G
Page 13 :
DLZ OHIO, INC, , PLUMBING FIXTURE SCHEDULE, TAG, FCO-1, , FIXTURE, , DESCRIPTION, , ACCEPTABLE MANUFACTURER, , LACQUERED CAST IRON BODY FLOOR CLEANOUT WITH ADJUSTABLE, HEAVY DUTY STAINLESS STEEL ROUND TOP WITH INTEGRAL PLUG. TOP TO BE ANSI HEAVY DUTY, LOAD RATED. CLEANOUTS TO BE LOCATED IN FINISHED FLOOR AREAS., LACQUERED CAST IRON HEAVY DUTY FLOOR DRAIN WITH 5"' ROUND DUCTILE IRON, ADJUSTABLE STRAINER, AND DEEP SUMP BODY COMPLETE WITH SEDIMENT BUCKET., LACQUERED CAST IRON HEAVY DUTY FLOOR DRAIN WITH 5"' ROUND DUCTILE IRON, ADJUSTABLE STRAINER, AND DEEP SUMP BODY COMPLETE WITH SEDIMENT BUCKET., STAINLESS STEEL GRINDING CHAMBER, 1/2 HP / 120V / 1PH / 5.8 AMPS., , LAV-1, , FLOOR, CLEANOUT, FLOOR DRAIN, FLOOR DRAIN, FOOD WASTE, DISPOSER, WALL, HYDRANT, LAVATORY, , MB-1, , MOB SINK, , BASIN - ONE PIECE MOLDED STONE 24"x24"x10" WITH INTEGRAL STAINLESS STEEL BODY DRAIN, STAINLESS STEEL CAPS ON ALL CURBS, AND WALL GUARDS. ■ FAUCET CHROME PLATED WITH VACUUM BREAKER, INTEGRAL STOPS, ADJUSTABLE WALL BRACE, PAIL HOOK AND 3/4" HOSE THREAD ON SPOUT. BODY INLETS 8" CENTER TO, CENTER, FOUR ARM HANDLES. ■ HOSE AND HOSE BRACKET - 30" LONG FLEXIBLE, HEAVY DUTY 5/8" RUBBER HOSE, CLOTH REINFORCED WITH 3/4" BRASS COUPLING AT ONE, END, 5" LONG BY 3" WIDE BRACKET. 18 GAUGE #302 STAINLESS STEEL WITH RUBBER GRIP. ■ MOP HANGER - 24" LONG BY 3" WIDE STAINLESS STEEL WITH (3) RUBBER TOOL, GRIPS., , SK-1, , COUNTERTOP, SINK, , WC-1, , WATER, CLOSET, , BOWL - ONE (1) 16"x21"x9.5" DEEP BOWL, COUNTERTOP, SELF RIMMING, DROP-IN SINK. TYPE 304 STAINLESS STEEL, DEEP DRAWN, FAUCET HOLES 4" CENTERS ■ FAUCET TWO HANDLE TOP-MOUNTED KITCHEN FAUCET SHALL FEATURE CAST BRASS CONSTRUCTION WITH ALL BRASS COUPLING NUTS, BRASS FIELD CONVERTIBLE RIGID/SWIVEL, SPOUT WITH 5" REACH, 1/4 TURN WASHERLESS CERAMIC DISC VALVE CARTRIDGES, ■ SUPPLIES AND STOPS-LOOSE KEY ANGLE STOP, 3/8"IPS, CHROME PLATED INLET, 3/8" O.D. FLEXIBLE RISER, WALL ESCUTCHEON., BOWL - WHITE VITREOUS CHINA, ELONGATED, FLOOR MOUNTED, FLOOR OUTLET, SIPHON JET, 1-1/2" TOP SPUD, 2-1/8" TRAPWAY, CLOSET BOLTS AND CAPS. LOW WATER, CONSUMPTION (1.28 GPF). ■ FLUSH VALVE - EXPOSED, HARDWIRED (INCLUDE TRANSFORMER), SENSOR OPERATED FLUSH VALVE. SELF-CLEANING PISTON VALVE WITH, MANUAL OVERRIDE. CAST BRASS VALVE BODY AND METAL COVER WITH CHROME FINISH, VANDAL RESISTANT STOP CAP, ANGLE STOP WITH BACK-FLOW PROTECTION AND, VACUUM BREAKER. LOWER WATER CONSUMPTION (1.28 GPM). ■ SEAT - WHITE HIGH IMPACT, EXTRA HEAVY SOLID PLASTIC, ELONGATED, CHEMICAL RESISTANT, OPEN, FRONT. (LESS COVER), MODEL-IN SURFACE CHECK AND STAINLESS STEEL HINGE POSTS. ■ CARRIER - BOLTED TYPE CLOSET FITTING, ADJUSTABLE SHORT FOOT WITH, BEARING PLATE, SIZE AND TYPE AS REQUIRED., , WCO-1, , WALL, CAST BRONZE CLEANOUT PLUG WITH 8" ROUND, SMOOTH, STAINLESS STEEL ACCESS COVER., CLEANOUT, WATER METER, , FD-1, FD-2, FWD-1, HB-1, , WM, , SAN/WASTE, , VENT, , COLD, WATER, , HOT, WATER, , MIFAB MODEL C1100-XR-3, SMITH, JOSAM, OR ZURN, MIFAB MODEL F1100-5-HG-3-5 OR EQUIVALENT, MIFAB MODEL F1100-5-EF-3-5 OR EQUIVALENT, INSINKERATOR LC50-11, , CONCEALED BOX TYPE FREEZELESS WALL HYDRANT, AUTOMATIC DRAINING, ANTI-SIPHON VACUUM BREAKER WITH 3/4" MALE HOSE THREAD, LOOSE TEE KEY, CHROME, WOODFORD MODEL NO. B65; JAY R. SMITH; WADE;, PLATED EXTERIOR FINISH, JOSAM; ZURN, BOWL - WALL HUNG, VITREOUS CHINA, CONCEALED ARM SUPPORTS. ■ FAUCET - VANDAL RESISTANT ALL BRASS BODY WITH SINGLE INLET AND IN-LINE STRAINER., BOWL - SLOAN MODEL SS-3003 ■ FAUCET - SLOAN, HARDWIRED 24VAC SOLENOID VALVE (INCLUDE TRANSFORMER) AND MICROPROCESSOR CONTROLLED PROXIMITY SENSORS. PROVIDE THERMOSTAT MIXING VALVE OPTION MODEL ETF600-B-BDT-EL-248-40 ■ SUPPLIES AND, WITH ASSE 1017 COMPLIANCE. ■ SUPPLIES AND STOPS - LOOSE KEY ANGLE STOPS: 3/8" I.P.S. CHROME PLATED INLET, 3/8" O.D., FLEXIBLE STEEL RISERS, WALL, STOPS - WOLVERINE BRASS INC. MODEL ENCORE; T&S, ESCUTCHEON. ■ TRAP - 1-1/4"x1-1/2" CAST BRASS: CHROME PLATED, ADJUSTABLE WITH CLEANOUT PLUG. TUBING TO WALL AND ESCUTCHEON. ■ DRAINS - LAVATORY DRAIN BRASS ■ TRAP - WOLVERINE BRASS INC.; T&S BRASS ■, OUTLET FITTING WITH PERFORATED GRID, CHROME PLATED FINISH AND CAST BRASS BODY., DRAINS - WOLVERINE BRASS INC. CATALOG NO. 56096;, T&S BRASS, , REMARKS, MATCH SAN PIPE SIZE, , 2", 4", 1-1/2", , PROVIDE WITH TRAP PRIMER, PROVIDE WITH TRAP PRIMER, PROVIDE WITH SK-1, , 1-1/4", 3/4", , 1-1/4", , 2", , 3/4", , 3/4", , BASIN - FIAT MODEL MSB-2424 OR MUST,, STERN-WILLIAMS, ACORN. ■ FAUCET - FIAT MODEL, 830-AA OR CHICAGO FAUCETS, KOHLER, AMERICAN, STANDARD, SPEAKMAN, T&S BRASS, CRANE. ■ MOP, HANGER - FIAT MODEL 889-CC OR CHICAGO FAUCETS,, KOHLER, AMERICAN STANDARD, CRANE, T&S, , 3", , 1-1/2", , 3/4", , 3/4", , BOWL - EAGLE MODEL FDI-14-16-9.5-1 ■ FAUCET AMERICAN STANDARD MODEL 6405.171. ■ SUPPLES, AND STOPS - WOLVERINE BRASS INC. MODEL ENCORE, , 1-1/2", , 1-1/4", , 3/4", , 3/4", , TOILET SYSTEM - SLOAN WETS-2020.1401. INCLUDE, TRANSFORMER FOR HARDWIRE. ■ SEAT - AMERICAN, STANDARD MODEL 5901.110T OR EQUIVALENT., , 4", , 2", , 1", , MIFAB MODEL C1436, , 4", , MOUNT HYDRANT 24" ABOVE, FINISHED FLOOR / GRADE, ADA COMPLIANT, , ADA COMPLIANT, , MATCH SAN PIPE SIZE, 2", , BACKFLOW PREVENTER VALVE SCHEDULE, MANUFACTURER, , PLUMBING EQUIPMENT SCHEDULE, , BELL & GOSSETT, , PTA-5, , 3/4" INLET, , BELL & GOSSETT, , ECOCIRC XL 20-35, , 1/12, , 1800, , 115, , 1, , 5 FT, , 1 GPM 3/4" DHWR INLET AND OUTLET, , SUMP PUMP: DURABLE, CAST IRON CONSTRUCTION WITH POWDER COATED EPOXY FINISH WITH ALL, STAINLESS STEEL FITTINGS., TRAP PRIMER: AUTOMATIC PRESSURE DROP ACTIVATED WITH DU-U DISTRIBUTION., TANKLESS CONDENSING HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER: INDOOR MODEL WITH, INTEGRATED TEMPERATURE CONTROLLER. 3" CONCENTRIC VENT AND FLUE TERMINATION. 199,000 BTU/H, MAXIMUM GAS CONSUMPTION INPUT. PROVIDE DISCONNECT AT THE WATER HEATER., WATER HAMMER ARRESTOR: ASSE 1010 APPROVED. 12 TO 32 CROSS FIXTURE UNIT RATING., , ZOELLER, , 940-0012, , 4/10, , 3450, , 115, , 1, , 15 FT, , PPP, AO SMITH, , P1-500, ACT-199I-N, , 120, , 1, , WATTS, , LF15M2-B, , 50 GPM PROVIDE OIL SMART SIMPLEX, CONTROL PANEL IN 105 JANITOR ROOM., 1/2" INLET, 10 GPM PROVIDE CONDENSATE DRAIN WITH, MANUFACTURER PROVIDED, NEUTRALIZER KIT., 3/4" INLET, , P6.1, , LANCASTER, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , 30 GALLON CAPACITY, , DRAWING NUMBER, , 11/26/2018 12:49:44 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , WHA-1, , 31-0444, , PLUMBING, , TP-1, WH-1, , ZOELLER, , 1821-7001-50, , SP-1, , CATCH BASIN: PROVIDE 18" DIAMETER X 30" DEEP CATCH BASIN WITH TOP DISCHARGE ASSEMBLY WITH, BASIN, SIMPLEX SP-1, FLOAT CONTROLS AND NO. 17-0135 SLOTTED COVER., DOMESTIC EXPANSION TANK: 2 GALLON TANK FOR 0.74 GALLON OF REQUIRED TANK VOLUME WITH 0.2, GALLON OF REQUIRED ACCEPTANCE VOLUME. NSF 61 CERTIFIED, RECIRCULATION PUMP: PUMP BODY SHALL BE LEAD-FREE BRONZE CONSTRUCTION, STAINLESS STEEL, FACE PLATE, POLY-PHENYLENE SULFIED IMPELLER, AISI 420 STAINLESS STEEL SHAFT, CARBON ON, SILICON CARBIDE MECHANICAL FACES, THE MOTOR SHALL BE NON-OVERLOADING AT ANY POINT ON THE, PUMP PERFORMANCE CURVE, DRIP PROOF, CARBON SLEEVE SEALED PRECISION BEARING. THE, PERMANENT SPLIT CAPACITOR MOTOR SHALL BE EQUIPPED WITH THERMAL OVERLOAD PROTECTION., PROVIDE STARTER/DISCONNECT FOR THE CIRCULATION PUMP., , EQUIPMENT & FIXTURE SCHEDULES, , RP-1, , REMARKS, , PROJECT NUMBER, , DET-1, , MODEL, , PHASE SYSTEM, RPM VOLT. CYCLE HEAD FLOW, , December 6th, 2018, , CB-1, , DESCRIPTION, , MOTOR, HP, , DATE:, , TAG, , BASIS OF, DESIGN, , ESA, , REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER - MAIN BODY AND ACCESS COVER SHALL BE EPOXY COATED DUCTILE IRON (ASTM A, 536 GRADE 4). THE SEAT RING AND CHECK VALVE SHALL BE NORYL, THE STEM SHALL BE STAINLESS STEEL (ASTM A 276) AND THE SEAT DISC, ELASTOMERS SHALL BE EPDM., , APPRV'D:, , RPZ-1, , NO., , PRESSURE REDUCING VALVE - 1 1/2" INLET WITH LEAD-FREE., , DESIGNED: KB, , PRV-1, , CONNECT 3/4" DCW TO 3/8". 1/8" DISCHARGE PIPE, FROM VENT PORT TO THE NEAREST FD IN ATTIC, SPACE., ZURN WILKENS MODEL 500XLC OR EQUIVALENT 110 PSI INLET PRESSURE TO 65 PSI OUTLET, PRESSURE @ 60 GPM, ZURN WILKENS MODEL 375 OR EQUIVALENT, 11 PSI LOSS @ 60 GPM, , REVISION, , ZURN WILKENS MODEL 740 OR EQUIVALENT, , CHK'D: MLV, , BACKFLOW PREVENTER - CONFORMING TO ASSE 1022. 3/8" INLET AND OUTLET SIZE WITH 1/8" VENT., , DRAWN: KB, , BFP-1, , COMMENTS, , DATE, , DESCRIPTION, , OHIO, , TAG
Page 14 :
AØ, , ROUND DUCT DIMENSION, , RECTANGULAR DUCT - UP, , RECTANGULAR DUCT - DOWN, , ROUND OR OVAL DUCT - UP, , ROUND OR OVAL DUCT - DOWN, , SUPPLY AIR DIFFUSER (SQUARE), RETURN AIR GRILLE (SQUARE), RETURN AIR GRILLE OR EXHAUST REGISTER (RECTANGULAR), , EXHAUST GRILLE (SQUARE), , S, , DUCT SMOKE DETECTOR, D, , BD, , BACKDRAFT DAMPER, , VOLUME DAMPER, , ROUND DIFFUSER, , SLOT DIFFUSER, , HVAC, BASIS OF DESIGN, SUMMER, OUTDOOR, , 90°F DB, 74°F WB, , INDOOR, , 75°F DB, 63°F WB, , 1°F DB, , INDOOR, , 70°F DB, , 5., , CONTRACTOR IS RESPONSIBLE FOR ALL WORK IDENTIFIED ON ALL DRAWINGS AND INFORMATION IN, THE PROJECT MANUAL, AS A COMPLETE PROJECT. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY, TO DETERMINE THE SPECIFIC SCOPE OF WORK FOR ANY SUBCONTRACTORS FOR THIS PROJECT, EXCEPT AS SPECIFICALLY NOTED., , 6., , ALL DUCTS IN FINISHED ROOMS AND SPACES SHALL BE CONCEALED IN CHASES OR ABOVE THE, CEILINGS, UNLESS OTHERWISE NOTED., , 7., , ALL LISTED DUCTWORK DIMENSIONS ARE CLEAR AIR FLOW DIMENSIONS., , 8., , COORDINATE WORK WITH OTHER TRADES., , 9., , MAXIMUM LENGTH OF FLEX DUCT SHALL BE 5'-0". FLEX DUCT SHALL NOT BE USED WHERE DUCTWORK, IS EXPOSED., , 10., , DUCT AND PIPING LAYOUTS ARE SCHEMATIC IN NATURE. FIELD VERIFY LOCATION OF BEAMS, GENERAL, STRUCTURE, LIGHTING, PIPING, ETC., BEFORE FABRICATION AND INSTALLATION OF DUCTWORK, COORDINATE ELEVATIONS, OFFSETS, AND TRANSITIONS AS REQUIRED., , 11., , CONNECTION TO EQUIPMENT SHALL CONFORM TO MANUFACTURER'S SPECIFICATION., , 12., , ALL HANGER SYSTEMS FOR PIPING AND EQUIPMENT SHALL BE SECURED TO BUILDING STRUCTURAL, SYSTEM. CONTRACTORS SHALL COORDINATE HANGERS CONNECTED TO STEEL JOISTS TO ENSURE, HANGERS ARE ATTACHED AT JOIST PANEL POINTS., , 13., , CONTRACTOR SHALL PROVIDE ACCESS DOORS IN ALL WALLS AND CEILINGS WHERE SERVICE OR, ADJUSTMENT TO MECHANICAL OR PLUMBING ITEMS MAY BE REQUIRED. ACCESS DOORS SHALL BE OF, AN APPROPRIATE SIZE REQUIRED FOR EACH APPLICATION. WHERE APPLICABLE, ACCESS DOORS, SHALL MATCH THE FIRE RATING OF THE WALL ASSEMBLY., , 14., , VOLUME DAMPERS SHALL BE INSTALLED IN ALL BRANCH DUCT., , 15., , THE ELBOWS FOR DUCTWORK SHALL HAVE TURNING VANES UNLESS NOTED OTHERWISE., , 16., , ALL HVAC CONTROL WIRING AND CONDUIT SHALL BE PROVIDED BY DIVISION 23 CONTRACTOR UNLESS, OTHERWISE NOTED. EXPOSED CONTROL WIRING SHALL BE IN CONDUIT. USE THE PLENUM RATED, CABLE FOR CABLES NOT IN CONDUIT., , 17., , REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR ALL AIR DEVICE LOCATIONS., , 18., , ALL MECHANICAL EQUIPMENT REQUIRING NATURAL GAS SHALL BE FURNISHED WITH PRESSURE, REGULATOR. THE GAS PRESSURE REGULATOR SHALL REGULATE THE GAS PRESSURE BETWEEN THE, INLET AND OPERATING PRESSURE OF THE EQUIPMENT. PROVIDE VENT TO OUTDOOR FROM EACH, REGULATOR., , 19., , ALL STRUCTURAL OPENINGS SHALL BE COORDINATED WITH THE STRUCTURAL DRAWING. COORDINATE, ANY STRUCTURAL SUPPORTS FOR OPENINGS WITH STRUCTURAL TRADES., , 20., , HVAC EQUIPMENT SHALL BE CONNECTED TO A BUILDING MANAGEMENT SYSTEM. REFER TO X, DRAWINGS FOR CONNECTION DETAILS., , 21., , ALL EXPOSED DUCTWORK AND PIPING SHALL BE PAINTED PER DIVISION 9 SPECIFICATIONS., , GENERAL MECHANICAL NOTES, A., , COORDINATE ALL WORK WITH OTHER TRADES AND EXISTING WORK TO PERMIT ACCESS AND SERVICE, CLEARANCES TO ALL SYSTEMS. COORDINATE DUCT WITH ELECTRICAL J-BOXES TO PREVENT, OBSTRUCTIONS., , B., , REFER TO DETAIL SHEETS FOR ADDITIONAL INFORMATION ON INSTALLMENT METHODS., , M0.1, , LANCASTER, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , OUTDOOR, , KEY NOTES ARE MEANT AS A GENERAL GUIDE FOR TYPICAL LOCATIONS. CONTRACTOR TO PERFORM, FULL EXTENT OF WORK REQUIRED TO ACCOMPLISH DESIGN INTENT., , DRAWING NUMBER, , 11/26/2018 12:48:55 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , WINTER, , 4., , DLZ OHIO, INC, , DRAWING WHERE SECTION WAS CUT, OR, DRAWING TO SEE FOR SECTION, , FLAT-OVAL DUCT DIMENSION, , DO NOT SCALE DRAWINGS FOR DIMENSIONS. REFER TO DIMENSIONED DRAWINGS. IF DIMENSIONS, CANNOT BE ACCURATELY DETERMINED, REQUEST THE INFORMATION FROM THE, ARCHITECT/ENGINEER., , 1821-7001-50, , X, , A/B, , 3., , GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS, , SECTION REFERENCE NUMBER, , RECTANGULAR DUCT DIMENSION, , PROJECT NUMBER, , X, , AxB, , December 6th, 2018, , EQUIPMENT TYPE (SEE ABBREVIATIONS), SCHEDULE #, , DATE:, , X, X, , ESA, , CONDENSATE, , CND, , APPRV'D:, , TEMPERATURE SENSOR, , IF NON-DESIGN BASE EQUIPMENT IS SELECTED, THIS CONTRACTOR SHALL BEAR ANY ADDITIONAL, COSTS FOR MODIFICATION TO THE PROPOSED BUILDING SYSTEM CAUSED BY SELECTION OF THE, NON-DESIGN BASE EQUIPMENT. DEVIATIONS FROM BASIS OF DESIGN THAT AFFECT OTHER TRADES, ARE THE RESPONSIBILITY OF THIS CONTRACTOR. ADDITIONAL COSTS TO PROVIDE LARGER, ELECTRICAL CIRCUITS, MORE FLOOR SPACE, ADDITIONAL SUPPORTS, ADDITIONAL MATERIALS, ETC., SHALL BE BORNE BY THIS CONTRACTOR. COORDINATE ALL WORK WITH OTHER TRADES., , DATE, , TS, , 2., , REVISION, , REFRIGERANT GAS, , IDENTIFICATION, INVERT ELEVATION, INTAKE HOOD, IN JOIST SPACE, INCHES, INFRARED TUBE HEATER, IN WALL SPACE, LOUVER, LEAVING AIR TEMPERATURE, POUNDS OR POUND, LEAVING DRY BULB, LAB EQUIPMENT CONTRACTOR, LEAVING WET BULB, MAKE-UP AIR UNIT, MAXIMUM, MOP BASIN, 1000 BRITISH THERMAL UNITS PER HOUR, MECHANICAL CONTRACTOR, MOTORIZED DAMPER, MECHANICAL, MANUFACTURER, MINIMUM, MOUNTED, MOUNTING, NOT APPLICABLE, NORMALLY CLOSED, NUMBER OR NORMALLY OPEN, NOT TO SCALE, OUTSIDE AIR, OUTSIDE SCREW & YOKE, PLUMBING CONTRACTOR, PRESSURE DROP, PHASE, PLUMBING, PRESSURE, POUNDS PER SQUARE INCH, RETURN AIR, REQUIRED, RELIEF AIR FAN, RETURN GRILLE / REFRIGERANT GAS, RELIEF AIR HOOD, REFRIGERANT LIQUID, ROOM, REVOLUTIONS PER MINUTE, ROUND, ROOF TOP UNIT, SMOKE DAMPER, SUPPLY AIR, SUPPLY DIFFUSER, SENSIBLE, SUPPLY GRILLE, SHEET METAL, STATIC PRESSURE, SQUARE FEET, STAINLESS STEEL, STORAGE TANK, THERMOSTAT, STANDARD, STRUCTURAL, SINGLE WALL, SYSTEM, TEMPERATURE CONTROL PANEL, TEMPERATURE, TO FLOOR ABOVE, TO FLOOR BELOW, THERMOMETER, THREADED, THROUGH, TOTAL STATIC PRESSURE, TYPICAL, UNDER GROUND, WITH, WATER COLUMN, WATER HEATER, WALL LOUVER W/ SCREEN, WALL OPENING, WATER PRESSURE DROP, WATER TEMPERATURE DIFFERENCE, WATER, , NO., , RG, , ID, IE, IH, IJS, IN, IRTH, IWS, L, LAT, LBS/LB, LDB, LEC, LWB, MAU, MAX, MB, MBH, MC, MD, MECH, MFGR, MIN, MTD, MTG, NA, NC, NO, NTS, OA, OS&Y, PC, PD, PH, PLBG, PRESS, PSI, RA, REQ'D, RF, RG, RH, RL, RM, RPM, RND, RTU, S, SA, SD, SENS, SG, SHT MTL, SP, SQFT, SS, ST, STAT, STD, STRUCT, SW, SYST, TCP, TEMP, TFA, TFB, THERM, THRD, THRU, TSP, TYP, UG, W/, WC, WH, WLSN, WO, WPD, WTD, WT, , DESIGNED: KB, , THERMOSTAT, , AIR COOLED CONDENSING UNIT, ABOVE CEILING SPACE, ADJUSTABLE, ABOVE FINISHED FLOOR, AIR HANDLING UNIT, AMPERES, AIR PRESSURE DROP, AUTOMATIC TEMPERATURE CONTROL, ABOVE SUSPENDED CEILING, AVERAGE, BACKFLOW PREVENTER, BRAKE HORSE POWER, BELOW, BUILDING, BOTTOM OF DUCT, BOTTOM OF PIPE, BASEMENT, BOTTOM, CAPACITY, COOLING COIL, CENTRIFUGAL, CUBIC FEET PER MINUTE, CHILLED WATER, CEILING, CONDENSATE, COMPANY, CONCRETE, CONNECT, CONSTANT, CONTRACTOR, CIRCULATING PUMP, CLOSE TO WALL, CONDENSING UNIT, DRAIN, DRY BULB, DEGREE, DIAMETER, DISCHARGE, DOWN, DUCT STATIC PRESSURE, EXHAUST AIR, ENTERING AIR TEMPERATURE, ENTERING DRY BULB, EXHAUST FAN, EFFICIENCY, EXHAUST GRILLE, ELEVATION, ELECTRICAL, EXTERNAL STATIC PRESSURE, EXPANSION TANK, ENTERING WET BULB, EXIST/EXISTING, EXHAUST, FURNACE, FIRE DAMPER, FROM FLOOR ABOVE, FROM FLOOR BELOW, FINISHED, FLEXIBLE, FLOOR, FEET PER MINUTE, FILTER/REGULATOR/LUBRICATOR, FIRE/SMOKE, FEET, FEET OF HEAD, NATURAL GAS, GAUGE, GALLON, GALVANIZED, GENERAL CONTRACTOR, GENERAL, GALLONS PER MINUTE, GAS UNIT HEATER, GLYCOL WATER RETURN, GLYCOL WATER SUPPLY, HEATING COIL, HEATING HOT WATER, HORIZONTAL, HORSE POWER, HOUR, HEATING, HEATER, HEATING, VENTILATING & AIR CONDITIONING, , CHK'D: MLV, , T, , ACCU, ACS, ADJ, AFF, AHU, AMPS, APD, ATC, ASC, AVG, BFP, BHP, BL, BLDG, BOD, BOP, BSMT, BTM, CAP, CC, CENT, CFM, CHW, CLG, CND, CO, CONC, CONN, CONST, CONTR, CP, CTW, CU, D, DB, DEG, DIA, DISCH, DN, DSP, EA, EAT, EDB, EF, EFF, EG, EL, ELECT, ESP, ET, EWB, EX, EXH, F, FD, FFA, FFB, FIN, FLEX, FLR, FPM, FRL, F/S, FT, FTHD, G, GA, GAL, GALV, GC, GEN, GPM, GUH, GWR, GWS, HC, HHW, HORIZ, HP, HR, HTG, HTR, HVAC, , ALL MECHANICAL WORK SHALL BE IN ACCORDANCE WITH OHIO MECHANICAL CODE, LATEST, APPLICABLE EDITION, AND AS SPECIFIED (WHICHEVER IS MORE STRINGENT)., , DRAWN: KB, , REFRIGERANT LIQUID, , 1., , OHIO, , RL, , GENERAL NOTES, , MECHANICAL, , ABBREVIATIONS, , SYMBOLS
Page 15 :
M1.1 CODED NOTES, , B, C, D, E, , REMOVE EX STEAM RADIATOR. SAW CUT STEAM PIPING TO EX FLOOR, LEVEL AND CAP., REMOVE EXPOSED VERTICAL PIPE RISER. SAW CUT STEAM PIPING TO, EX FLOOR LEVEL AND CAP., REMOVE STEAM PIPING., REMOVE EX THERMOSTAT. PATCH AND REPAIR ANY WALL OPENINGS., SAW CUT STEAM PIPING TO EX WALL AND CAP., , DLZ OHIO, INC, , A, , EX L TO REMAIN., , E, , C, , C, , C, B-EX, DISCONNECT AND REMOVE EX, STEAM BOILERS, FAN, AND, ASSOCIATED APPURTENANCES., , REMOVE EX 12", FLUE FROM STEAM, BOILERS AND 3", FLUE FROM WH., EF-EX, , B-EX, , E, , E, , 1, M1.1, , BASEMENT MECHANICAL REMOVAL, SCALE: 3/16" = 1'-0", , REVISION, , DATE, , NORTH, , REMOVE EX CEILING EF,, EXH DUCT, AND WALL CAP., , T, , D, , T, , D, , A, , B, , A, A, , C, , A, , 2, M1.1, NORTH, , LOWER LEVEL MECHANICAL REMOVAL, SCALE: 3/16" = 1'-0", , LANCASTER, , A, , DRAWING NUMBER, , B, , 11/26/2018 12:48:58 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , A, , 1821-7001-50, , M1.1, , T, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , C, , MECHANICAL, , A, , A, , BASEMENT & FIRST FLOOR MECHANICAL REMOVAL, , A, , OHIO, , DRAWN: KB, , REMOVE EX, EXH FLUE, , PROJECT NUMBER, , EF-EX, , ESA, , M3.1, , APPRV'D:, , 8, , _____________________, , December 6th, 2018, , A, , DESIGNED: KB, , C, , A, , CHK'D: MLV, , C, , NO., , REMOVE EX ELECTRIC, BASEBOARD HEATER., , DATE:, , A
Page 16 :
M1.2 CODED NOTES, A, , DLZ OHIO, INC, , B, C, , REMOVE EX STEAM RADIATOR. REMOVE ANY EXPOSED STEAM PIPING., SAW CUT STEAM PIPING TO EX FLOOR LEVEL AND CAP., REMOVE STEAM AND CONDENSATION PIPING., REMOVE EX WINDOW MOUNTED AC., , C, , B, A, DISCONNECT AND REMOVE EX, CEILING EF, FLEX DUCT, AND, ASSOCIATED APPURTENANCES., , 8, , _____________________, , M3.1, , C, A, EF-EX, , B, , A, , A, , REMOVE EX ELECTRIC, BASEBOARD HEATER., , A, , DATE, , A, , A, , A, , 1821-7001-50, , PROJECT NUMBER, , December 6th, 2018, DATE:, , ESA, , SECOND FLOOR MECHANICAL REMOVAL, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , MECHANICAL, , M1.2, , LANCASTER, DRAWING NUMBER, , 11/26/2018 12:49:00 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , OHIO, , DRAWN: KB, , NORTH, , SCALE: 3/16" = 1'-0", , APPRV'D:, , M1.2, , SECOND FLOOR MECHANICAL REMOVAL, , NO., , 1, , DESIGNED: KB, , B, , REVISION, , B, , CHK'D: MLV, , B
Page 19 :
DLZ OHIO, INC, 4" MANUFACTURER, PROVIDED CONCENTRIC, FLUE FROM ROOF. REFER, TO 9/M5.1 FOR DETAIL., , 4" MANUFACTURER, PROVIDED CONCENTRIC, FLUE FROM ROOF. REFER, TO 9/M5.1 FOR DETAIL., , 4" MANUFACTURER, PROVIDED CONCENTRIC, FLUE FROM ROOF. REFER, TO 9/M5.1 FOR DETAIL., , OA DUCTWORK THRU ROOF., PROVIDE GOOSENECK AT, DUCT TERMINATION REFER, TO 5/M5.1 FOR DETAIL., , 10"ø OA, , 4" MANUFACTURER, PROVIDED CONCENTRIC, FLUE FROM ROOF. REFER, TO 9/M5.1 FOR DETAIL., , 8"ø OA, , REVISION, , DATE, , 4" MANUFACTURER, PROVIDED CONCENTRIC, FLUE FROM ROOF. REFER, TO 9/M5.1 FOR DETAIL., , 1821-7001-50, , PROJECT NUMBER, , December 6th, 2018, DATE:, , ESA, APPRV'D:, , DESIGNED: KB, , ROOF HVAC PLAN, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , MECHANICAL, , M2.3, , LANCASTER, DRAWING NUMBER, , 11/26/2018 12:49:10 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , OHIO, , DRAWN: KB, , CHK'D: MLV, , NORTH, , ROOF HVAC PLAN, SCALE: 3/16" = 1'-0", , NO., , 1, M2.3
Page 22 :
W2, , UNION, OPEN TO ATMOSPHERE, , 2"., , 15°., , CONICAL SPIN-IN FITTING W/ MANUAL, DAMPER, HANDLE & LOCK NUT, , ROUTE CND AS INDICATED ON PLANS. IF NOT, INDICATED ROUTE FULL SIZE INTO NEAREST, CODE-APPROVED TERMINATION POINT. TERMINATE, WITH AIR GAP. COORDINATE WITH PLUMBING, FIXTURE SUPPLIER FOR FITTINGS AND LOCATIONS., , AIR FLOW, FINISHED CEILING, , 1-1/2 TIMES TOTAL SYSTEM STATIC, (MINIMUM 2" ON BLOW THRU UNITS), , CLEANOUT, PLASTIC, GRILLE, , 4, M5.1, , SEAL DUCT, TO CAP, , W1+3/4 W3 HEAL RADIUS, 3/4 W3 THROAT RADIUS, , FLEX DUCT WHEN USED., WORM DRIVE STAINLESS, STEEL CLAMP, , W1, , 3, , TYPICAL CEILING EXHAUST FAN DETAIL, , M5.1, , SCALE: N.T.S., , AIR FLOW, , COOLING, COIL DRAIN, PAN, , W3, , FACTORY PROVIDED, SIDEWALL VENT CAP WITH, BACKDRAFT DAMPER, ATTACHED TO WALL, , AIR FLOW, , EXHAUST DUCT MINIMUM, SIZE OF FAN DISCHARGE, UNLESS OTHERWISE NOTED, , NOTE: W1 IS LESS, THAN W2, , MINIMUM 0" FOR BLOW, THRU UNITS, , DLZ OHIO, INC, , EXTERIOR, WALL, , 2, , COOLING COIL DRAIN TRAP DETAIL, , 1, , MAIN BRANCH DUCT TAKE-OFF, , M5.1, , SCALE: N.T.S., , ROUND DUCT BRANCH TAKE-OFF, , M5.1, , SCALE: N.T.S., , SCALE: N.T.S., , DUCTWORK, , AIRFLOW, , 1/2" BIRDSCREEN, SEAL ALL JOINTS, W/ WEATHERPROOF, MASTIC, FLASHING, , VOLUME DAMPER, (TYPICAL OF ALL, TAKE-OFFS), , 3"x3" STRIP, LO, W, , FLEXIBLE DUCTWORK, TO SUPPLY OUTLET, , 6, M5.1, , ROOFING, , NOTE:, MAXIMUM FLEX DUCTWORK, SHALL NOT EXCEED 5'-0", IN LENGTH., , E, OP, SL, , F, , CURB, , ROOF, CONSTRUCTION, , 5, , BRANCH DUCT TAKE-OFF DETAIL, , M5.1, , SCALE: N.T.S., , DATE, , AIR, F, , A, , WORM DRIVE STAINLESS, STEEL CLAMP, , 18" MIN., , C, , R, , 00°, 45., , B, , TO, RA, O, AP, ), EV OOR, D, (IN, , Gooseneck Detail, SCALE: N.T.S., , BALANCING, DAMPER, , EXHAUST FLUE, , FLEXIBLE DUCT, 5 FT. MAXIMUM, , 5. PROVIDE LIQUID-LINE SOLENOID VALVE., , CONCENTRIC, ADAPTER, , LEGEND:, , 11/26/2018 12:49:17 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , M5.1, , CONDENSING UNIT DETAIL, SCALE: N.T.S., , REDUCER AS, REQUIRED, , CENTERLINE RADIUS, 1.5xDIAM. (MIN.), , MAX. OFFSET 1/2", PER FOOT OF, FLEX. DUCT LENGTH, , SHEET METAL, ELBOW, , BALANCING, DAMPER, 1" (MIN.) BAND, CLAMP SUPPORT, , REDUCER AS, REQUIRED, , EXHAUST FLUE, SUPPLY DIFFUSER, , 9, M5.1, , CONCENTRIC ROOF VENT DETAIL, SCALE: N.T.S., , 8, M5.1, , SUPPLY, DIFFUSER, , RETURN GRILLE, , TYPICAL CEILING SD AND RG INSTALLATIONS, SCALE: N.T.S., , LANCASTER, , 10, , FILTER-DRIER, SIGHTGLASS/MOISTURE INDICATOR, THERMAL EXPANSION VALVE, SUCTION LINE, PITCHED TOWARD COMPRESSOR, LIQUID LINE, LIQUID-LINE SOLENOID VALVE, , CONICAL TEE, , SHEET METAL, ELBOW, , COMBUSTION AIR PIPE, , FLEXIBLE DUCT, 5 FT. MAXIMUM, , DRAWING NUMBER, , A., B., C., D., E., F., , SUPPLY DUCT, BALANCING, DAMPER, , MECHANICAL, , 4. UNIT MANUFACTURER SHALL PROVIDE REFRIGERANT PIPING, SCHEMATIC INCLUDING ALL LINES AND VALVE SIZES AND EXACT, LINE ROUTING., , 1821-7001-50, , 1" (MIN.) BAND, CLAMP SUPPORT, , DETAILS, , SUPPORT (FIELD SUPPLIED), , M5.1, , 3. INSULATE ALL SUCTION LINES., , PROJECT NUMBER, , TYPICAL DUCT SIDEWALL, REGISTER INSTALLATION, , TYPICAL CEILING SUPPLY DIFFUSER INSTALLATION, , December 6th, 2018, , SUPPLY DIFFUSER, , DATE:, , 2. PITCH ALL HORIZONTAL LINES A MINIMUM OF 1/2" IN 10 FEET IN, THE DIRECTION OF REFRIGERANT FLOW., , ESA, , SIDEWALL REGISTER, WITH OPPOSED BLADE, DAMPER., , ROOF, , APPRV'D:, , 1. ALL PIPING AND PIPING COMPONENTS BY M.C., , REDUCER AS, REQUIRED, , DRAWN: KB, , ROOF FLASHING, (FIELD SUPPLIED), , CENTERLINE RADIUS, 1.5xDIAM. (MIN.), , EXTRACTOR W/, LOCKING, CONTROL ROD, , OHIO, , NOTES:, , 2'-0" MIN., , 4" CONCRETE PAD, , AIRFLOW, , NO., , MAX. OFFSET 1/2", PER FOOT OF, FLEX. DUCT LENGTH, , CHK'D: MLV, , COMBUSTION AIR INLET, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , SHEET METAL, ELBOW, , DESIGNED: KB, , ING, NS, E, ND IT, CO U N, ), OR, O, D, UT, (O, , E, , REVISION, , D
Page 23 :
FURNACE, FURNACE, MODEL, , TAG MANUF., F-1, F-2, F-3, F-4, F-5A, F-5B, F-6, , TRANE, TRANE, TRANE, TRANE, TRANE, TRANE, TRANE, , S9X2B060U4PSA, S9X2B060U4PSA, S9X2C080U5PSA, S9X2B060U4PSA, S9X2B060U4PSA, S9X2B060U4PSA, S9X2B060U4PSA, , AIRFLOW MIN O.A., (CFM), (CFM), 1,500, 1,500, 1,600, 1,310, 1,225, 1,225, 1,285, , TOTAL, GAS INPUT, (BTUH) EAT/LAT (F), (BTUH), , 240, 235, 200, 160, 140, 140, 160, , 58,000, 58,000, 78,000, 58,000, 58,000, 58,000, 58,000, , 60.0/95.8, 60.0/95.8, 60.0/105.9, 60.0/101.0, 60.0/103.8, 60.0/103.8, 60.0/101.8, , GAS OUTPUT EFF ESP, (BTUH), (%) (IN WC), , 60,000, 60,000, 80,000, 60,000, 60,000, 60,000, 60,000, , 58,000, 58,000, 78,000, 58,000, 58,000, 58,000, 58,000, , 96.0, 96.0, 96.0, 96.0, 96.0, 96.0, 96.0, , 0.5, 0.5, 0.5, 0.5, 0.5, 0.5, 0.5, , SUPPLY FAN, VOLT/ MCA, PH, (A), HP, 0.75, 0.75, 1.00, 0.75, 0.75, 0.75, 0.75, , 120/1, 120/1, 120/1, 120/1, 120/1, 120/1, 120/1, , MOCP, (A), , 11.3, 11.3, 14.4, 11.3, 11.3, 11.3, 11.3, , 15.0, 15.0, 15.0, 15.0, 15.0, 15.0, 15.0, , APD, COIL MODEL (IN WC), , COOLING COIL, EAT (F) LAT (F) TOTAL SENSIBLE OUTDOOR, DB/WB, DB/WB (BTUH) (BTUH), UNIT, WEIGHT, , NOTES, , 4TXCB006DS3, 4TXCB006DS3, 4TXCC007DS3, 4TXCB006DS3, 4TXCB006DS3, 4TXCB006DS3, 4TXCB006DS3, , 78.8/64.1, 78.3/64.4, 78.4/64.2, 78.9/64.1, 78.1/64.2, 78.1/64.2, 78.0/64.2, , 1,2,3,4, 1,2,3,6, 1,2,3,4, 1,2,3,4, 1,2,3,4,5, 1,2,3,4,5, 1,2,3,4, , 0.56, 0.56, 0.36, 0.34, 0.30, 0.30, 0.33, , 54.5/53.4, 54.8/53.8, 54.9/54.0, 55.9/53.8, 55.3/53.3, 55.3/53.3, 55.8/53.7, , 45,700, 45,900, 46,300, 38,700, 38,400, 38,400, 38,700, , 38,900, 37,600, 39,500, 32,100, 29,800, 29,800, 30,400, , ACCU-1, ACCU-2, ACCU-3, ACCU-4, ACCU-5A, ACCU-5B, ACCU-6, , 175 LB, 175 LB, 190 LB, 175 LB, 175 LB, 175 LB, 175 LB, , DLZ OHIO, INC, , FURNACE SCHEDULE, , 1. PROVIDE STARTER/DISCONNECT PER DIVISION 26., 2. PROVIDE FILTER AND RACK, AND LIQUID-LINE SOLENOID VALVE., 3. PROVIDE WITH COMBINATION CONCENTRIC VENT. REFER TO 9/M5.1., 4. PROVIDE PROGRAMMABLE CONTROLLER WITH A CONTROL SEQUENCE TO BE PROVIDED PER SPECIFICATION. UNIT SHALL BE PROVIDED WITH STANDARD TEMPERATURE CONTROLS AND SAFETIES PRE-WIRED TO TERMINAL STRIP FOR USE BY BUILDING AUTOMATION SYSTEM., 5. PROVIDE TWINNING KIT AND INSTALL PER MANUFACTURER RECOMMENDATION., 6. PROVIDE WITH COMBINATION CONCENTRIC SIDE WALL VENT KIT., , AIR COOLED CONDENSING UNIT SCHEDULE, , 95, 95, 95, 95, 95, 95, 95, 95, , 14.50, 14.50, 15.00, 15.00, 15.00, 15.00, 15.00, 15.30, , R-410, R-410, R-410, R-410, R-410, R-410, R-410, R-410, , NO., 1, 1, 1, 1, 1, 1, 1, 1, , 18.5/124.0, 18.5/124.0, 18.5/124.0, 16.7/109.0, 16.7/109.0, 16.7/109.0, 16.7/109.0, -/-, , 24, 24, 24, 22, 22, 22, 22, 13, , 40, 40, 40, 35, 35, 35, 35, 15, , NOTES, , MODEL NO., , EUH-1 MARLEY ENGINEERED PRODUCTS, , 1,2,3,4, 1,2,3,4, 1,2,3,4, 1,2,3,4, 1,2,3,4, 1,2,3,4, 1,2,3,4, 1,2,3,4, , TAG, , MANUFACTURER, , MODEL NO., , EBH-1 MARLEY ENGINEERED PRODUCTS, , ELECTRICAL DATA, CAPACITY, (BTUH) VOLT/PH WATTS AMPS LENGTH, , BERKO BKOC2506W, , 5,120, , 208/1, , 1500, , 1,2,3, , MODEL NO., , EWH-1 MARLEY ENGINEERED PRODUCTS, , QMARK AWH3150F, , 5,118, , 120/1, , 1500, , LOREN COOK, LOREN COOK, LOREN COOK, LOREN COOK, LOREN COOK, , GC-128, GC-128, GC-128, GC-128, GC-128, , 70, 70, 70, 70, 65, , 0.12, 0.07, 0.12, 0.07, 0.07, , RPM, 750, 750, 750, 750, 750, , POWER (W) VOLT/PH, 28.1, 28.1, 28.1, 28.1, 28.1, , 115/1, 115/1, 115/1, 115/1, 115/1, , 1. PROVIDE INTEGRAL THERMOSTAT WITH LABEL, THERMAL OVERLOAD PROTECTION, BUILT-IN DISCONNECT SWITCH., , PUMP SCHEDULE, , NOTES, 1,2,3,4, 1,2,3,4, 1,2,4,5, 1,2,4,5, 1,2,3,4, , TAG MANUF., CP-1, , 11/26/2018 12:49:19 PM, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , LD-1, LR-1, RG-1, RG-2, RG-3, RG-4, RG-5, RG-6, SD-1, SD-2, SD-3, SD-4, SD-5, SR-1, , 6, 6, 6x6, 10x10, 16x8, 10x22, 10x10, 10x22, 6, 6, 8, 10, 12, 16x8, , PRICE, PRICE, PRICE, PRICE, PRICE, PRICE, PRICE, PRICE, PRICE, PRICE, PRICE, PRICE, PRICE, PRICE, , SDS75, SDR75, 530, 530, 530, 530, 80, 80, SCDA, SCDA, SCDA, SCDA, SCDA, 510, , 48", 48", 8x8, 12x12, 18x10, 12x24, 12x12, 12x24, 12x12, 24x24, 24x24, 24x24, 24x24, 18x10, , MAX PRESSURE, CFM, (IN), 150, 120, 50, 200, 200, 445, 340, 695, 65, 70, 160, 270, 465, 225, , 0.077, 0.040, 0.022, 0.031, 0.018, 0.044, 0.043, 0.036, 0.018, 0.015, 0.020, 0.033, 0.033, 0.017, , MODEL, MODEL 521, , 1, , 11, , 1/6, , 115 V, , 1, , 2'-4", , 1, , 1,2, , CHK'D: MLV, , AIR TERMINAL SCHEDULE, NECK PANEL, SIZE, SIZE, , ZOELLER, , ELECTRICAL, CAPACITY, GALLON FEET HD MOTOR VOLTS PHASE REMARKS, , 1. PROVIDE INVERTED U AT THE HIGHEST POINT OF THE DISCHARGE LINE., 2. INSTALL UNIT ON FLOOR CLOSE TO WALL., , 1. MANUFACTURER PROVIDED STARTER/DISCONNECT PER DIVISION 26 SPECIFICATIONS., 2. FAN SHALL OPERATE WHEN THE LIGHT SWITCH IS ON., 3. REFER TO DETAIL 4/M5.1., 4. PROVIDE SIDEWALL VENT WITH WALL CAP AND BACKDRAFT DAMPER., 5. REFER TO ARCHITECTURAL DETAIL FOR DUCT TERMINATION AT ROOF SOFFIT. PROVIDE INSECT, SCREEN AT TERMINATION., , TAG MANUF. MODEL, , 12.5, , NOTES, , STYLE, , INSTALLATION, , FINISH, , NC, , LINEAR SUPPLY DIFFUSER, 3/4" @ 2 SLOTS, 45° THROW, W - FLANGE END, SDBI TO FIT SDS75, LINEAR RETURN GRILLE, 3/4" @ 2 SLOTS, W - FLANGE END, SDBI TO FIT SDR75, RETURN GRILLE, 3/4" SPACING, 45° SINGLE DEFLECTION, RETURN GRILLE, 3/4" SPACING, 45° SINGLE DEFLECTION, RETURN GRILLE, 3/4" SPACING, 45° SINGLE DEFLECTION, RETURN GRILLE, 3/4" SPACING, 45° SINGLE DEFLECTION, RETURN GRILLE, 1/2" SQUARE, 1/2" DEPTH, 0 CORE° DEFLECTION, RETURN GRILLE, 1/2" SQUARE, 1/2" DEPTH, 0 CORE° DEFLECTION, SUPPLY DIFFUSER, 3 CONE, SUPPLY DIFFUSER, 4 CONE, SUPPLY DIFFUSER, 4 CONE, SUPPLY DIFFUSER, 4 CONE, SUPPLY DIFFUSER, 4 CONE, SUPPLY REGISTER, 3/4" SPACING, 22.5° DOUBLE DEFLECTION, , WALL MOUNT, WALL MOUNT, DUCTED, LAY-IN, WALL MOUNT, LAY-IN, LAY-IN, LAY-IN, LAY-IN / DUCTED, LAY-IN, LAY-IN, LAY-IN, LAY-IN, WALL MOUNT, , B12 WHITE, B12 WHITE, B12 WHITE, B12 WHITE, B12 WHITE, B12 WHITE, B12 WHITE, B12 WHITE, B12 WHITE, B12 WHITE, B12 WHITE, B12 WHITE, B12 WHITE, B12 WHITE, , <15, 15, <15, <15, <15, 15, <15, <15, <15, <15, <15, <15, <15, <15, , MECHANICAL, , ACCU-7, , MANUFACTURER, , 1821-7001-50, , 0.33, , TAG, , EQUIPMENT SCHEDULES, , NOTES, , ELECTRICAL DATA, CAPACITY, MOUNTING, (BTUH) VOLT/PH WATTS AMPS HEIGHT, , PROJECT NUMBER, , EF-1, EF-2, EF-3, EF-4, EF-5, , MODEL NO. CFM SP (IN WC), , 1, , M6.1, , 1, , FLA, , OUTDOOR, UNIT, , CEILING FAN SCHEDULE, MANUF., , 6' - 0", , ELECTRIC WALL UNIT HEATER SCHEDULE, , 1. PROVIDE STARTER/DISCONNECT PER DIVISION 26., 2. REFER TO DETAIL 10/M5.1. SIZE REFRIGERANT PIPING PER MANUFACTURER RECOMMENDATION., 3. PROVIDE OPTIONAL DRAIN PUMP FROM MANUFACTURER., , TAG, , 7.2, , NOTES, , 1. PROVIDE INTEGRAL THERMOSTAT WITH LABEL, THERMAL OVERLOAD PROTECTION, BUILT-IN DISCONNECT SWITCH., , ELECTRICAL, VOLT / PH., MCA, 208/1, , 1, , December 6th, 2018, , 425, , 6'-0", , DATE:, , 18,000, , 1/100, , ESA, , PKA-A18HA7, , 1600, , APPRV'D:, , MITSUBISHI ELECTRIC, , 350, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , DSS-1, , CFM, , 24, , DATE, , MODEL, , 5, , REVISION, , MANUFACTURER, , 208/1, , ELECTRIC BASEBOARD HEATER SCHEDULE, , DUCTLESS SPLIT INDOOR UNIT SCHEDULE, TAG, , 17, , 1. PROVIDE THERMAL OVERLOAD PROTECTION, BUILT-IN DISCONNECT SWITCH AND FAN DELAY SWITCH, BUILT-IN DISCONNECT SWITCH., , 1. PROVIDE STARTER/DISCONNECT PER DIVISION 26., 2. PROVIDE CRANKCASE HEATER, LOW-AMBIENT KIT, WINTER START KIT, AND WIND BAFFLE., 3. REFER TO DETAIL 10/M5.1. SIZE REFRIGERANT PIPING PER MANUFACTURER RECOMMENDATION., 4. FURNISH WITH 4" CONCRETE PAD., , CAPACITY, (BTUH), , QMARK MUH05-81, , NO., , 4.0, 4.0, 4.0, 3.6, 3.6, 3.6, 3.6, 1.5, , MANUFACTURER, , DESIGNED: KB, , 208/1, 208/1, 208/1, 208/1, 208/1, 208/1, 208/1, 208/1, , TAG, , ELECTRICAL DATA, FAN MOTOR DATA MOUNTING, CAPACITY, (MBH) VOLT/PH K.W. AMPS CFM RPM HP, HEIGHT, NOTES, , DRAWN: KB, , F-1, F-2, F-3, F-4, F-5A, F-5B, F-6, DSS-1, , ELECTRICAL, MCA, (A) MCB, RLA/LRA, , OHIO, , MODEL, , TRANE, 4TTR4048L1, TRANE, 4TTR4048L1, TRANE, 4TTR4048L1, TRANE, 4TTR4043L1, TRANE, 4TTR4043L1, TRANE, 4TTR4043L1, TRANE, 4TTR4043L1, MITSUBISHI ELECTRIC PUZ-A30NHA7, , COMPRESSOR, , LANCASTER, , MANUFACTURER, , DESIGN, EQUIPMENT VOLT/ NOMINAL AMBIENT, REF, SERVED, PH, TONS TEMP (F) SEER TYPE, , DRAWING NUMBER, , TAG, ACCU-1, ACCU-2, ACCU-3, ACCU-4, ACCU-5A, ACCU-5B, ACCU-6, ACCU-7, , ELECTRIC UNIT HEATER SCHEDULE
Page 24 :
MECHANICAL, , X1.1, , DRAWING NUMBER, , LANCASTER, , 11/26/2018 12:49:45 PM, , CONTROLS INFORMATION, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , OHIO, , December 6th, 2018, , -, , CHK'D: -, , 1821-7001-50, , PROJECT NUMBER, , DATE:, , APPRV'D:, , DESIGNED: -, , DRAWN: -, , NO., , REVISION, , DATE, , DLZ OHIO, INC
Page 25 :
MECHANICAL, , X1.2, , DRAWING NUMBER, , LANCASTER, , 11/26/2018 12:49:45 PM, , MSTP BUS ROUTING - FIRST FLOOR, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , OHIO, , December 6th, 2018, , -, , CHK'D: -, , 1821-7001-50, , PROJECT NUMBER, , DATE:, , APPRV'D:, , DESIGNED: -, , DRAWN: -, , NO., , REVISION, , DATE, , DLZ OHIO, INC
Page 26 :
MECHANICAL, , X1.3, , DRAWING NUMBER, , LANCASTER, , 11/26/2018 12:49:45 PM, , MSTP BUS ROUTING - SECOND FLOOR, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , C:\Users\khbang\Documents\7001.50_Fairfield_MEP_khbang.rvt, , OHIO, , December 6th, 2018, , -, , CHK'D: -, , 1821-7001-50, , PROJECT NUMBER, , DATE:, , APPRV'D:, , DESIGNED: -, , DRAWN: -, , NO., , REVISION, , DATE, , DLZ OHIO, INC
Page 27 :
A., , DASHED LINES INDICATE EXISTING ELECTRICAL EQUIPMENT TO BE, REMOVED. REMOVE ASSOCIATED ELECTRICAL ITEMS (I.E. CABLE, CONDUIT,, SUPPORTS, DISCONNECTS, ETC) COMPLETE BACK TO POWER AND/OR, SIGNAL SOURCE OR TO NEAREST REMAINING DEVICE(S) U.O.N., , B., , SHADED LINES INDICATE EXISTING ELECTRICAL ITEMS TO REMAIN., , C., , ALL EXISTING LIGHTING, POWER AND SYSTEMS TO BE REMOVED, COMPLETE. UNLESS OTHERWISE NOTED, DISCONNECT AND REMOVE ALL, ASSOCIATED ELECTRICAL ITEMS (I.E. CABLE, CONDUIT, SUPPORTS,, DISCONNECTS, ETC) COMPLETE BACK TO SOURCE. ALL EXISTING FLUSH, MOUNTED BACK BOXES TO REMAIN., , D4, , DLZ OHIO, INC, , GENERAL NOTES, , J, 6, , J, , D3, , 5, , D3, , B-EX, , ED2.0, , D1, , D4, , ED2.0 3, , 7, 8, , EF-EX, , D1, , ED2.0, , D4, , J, , D4, , J, , D4, , P#, , ED2.0, , D4, , ED2.0, , D4, , D4, , D3, D3, , J, , ED2.0 4, , ED2.0 2, , B-EX, , J, , D1, , D4, , D4, , D4, J, , WH-EX, D1, D3, , D1, , D2, D3, D4, D5, D6, D7, D8, D9, D10, D11, D12, , D13, , D3, J, , D14, , EXISTING EQUIPMENT TO BE REMOVED COMPLETE. DISCONNECT AND, REMOVE ALL ASSOCIATED ELECTRICAL ITEMS (I.E. CABLING, CONDUIT,, DISCONNECTS, BOXES, SUPPORTS, ETC) COMPLETE BACK TO POWER, SOURCE., EXISTING PENDANT MOUNTED FIXTURE TO BE REMOVED., EXISTING SURFACE MOUNTED FIXTURE TO BE REMOVED., EXISTING SURFACE MOUNTED DEVICE(S) TO BE REMOVED., EXISTING FLUSH MOUNTED DEVICE(S) TO BE REMOVED., EXISTING FLOOR MOUNTED DEVICE TO BE REMOVED., EXISTING RECESSED/GRID FIXTURE TO BE REMOVED., EXISTING WALL SCONCE LIGHT FIXTURE TO BE REMOVED., EXISTING ELECTRICAL PANEL TO BE REMOVED COMPLETE., EXISTING POWER POLE TO BE REMOVED COMPLETE., EXISTING DATA RACK TO REMAIN, PROTECT DURING CONSTRUCTION., EXISTING DUPLEX REMOVED FOR REPLACEMENT. DISCONNECT AND, REMOVE DEVICE AND ASSOCIATED CIRCUITRY BACK TO SOURCE., EXISTING BACK BOX TO REMAIN., EXISTING WEATHERHEAD AND UTILITY SERVICE TO BE REMOVED, COMPLETE., EXISTING UTILITY (AEP) METER WITH RISER TO WEATHERHEAD TO BE, REMOVED COMPLETE., EXISTING CARD ACCESS TO BE REMOVED COMPLETE., EXISTING DOORBELL BUTTON TO BE REMOVED COMPLETE., EXISTING PHOTOCELL NEAR GRADE TO BE REMOVED COMPLETE., EXISTING SURFACE MOUNTED EXTERIOR SPOT LIGHT TO BE REMOVED, COMPLETE., , DATE, , D15, D16, D17, D18, , 1, , REMOVAL KEYNOTES, , LOWER LEVEL REMOVALS PLAN, , ED2.0 SCALE: 1/4" = 1'-0", , 1821-7001-50, , PROJECT NUMBER, , DECEMBER 06, 2018, DATE:, , TKF, APPRV'D:, , DESIGNED: RDW, , OHIO, , DRAWN: RDW, , CHK'D: MLH, , NO., , REVISION, , NORTH, , PHOTO 1, , PHOTO 2, , PHOTO 3, , ED2.0 SCALE: N.T.S., , 5, , PHOTO 4, , ED2.0 SCALE: N.T.S., , LANCASTER, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , ED2.0 SCALE: N.T.S., , 4, , 7, , PHOTO 6, , ED2.0 SCALE: N.T.S., , 8, , PHOTO 7, , ED2.0 SCALE: N.T.S., , ELECTRICAL, , PHOTO 5, , ED2.0, , 6, , ED2.0 SCALE: N.T.S., , DRAWING NUMBER, , 12/5/2018 12:46:21 PM, , C:\users\rwilley\Documents\7001.50_Fairfield_rwilley.rvt, , ED2.0 SCALE: N.T.S., , 3, , LOWER LEVEL REMOVAL PLAN, , 2
Page 29 :
J, D3, , A., , DASHED LINES INDICATE EXISTING ELECTRICAL EQUIPMENT TO BE, REMOVED. REMOVE ASSOCIATED ELECTRICAL ITEMS (I.E. CABLE, CONDUIT,, SUPPORTS, DISCONNECTS, ETC) COMPLETE BACK TO POWER AND/OR, SIGNAL SOURCE OR TO NEAREST REMAINING DEVICE(S) U.O.N., , B., , SHADED LINES INDICATE EXISTING ELECTRICAL ITEMS TO REMAIN., , C., , ALL EXISTING LIGHTING, POWER AND SYSTEMS TO BE REMOVED, COMPLETE. UNLESS OTHERWISE NOTED, DISCONNECT AND REMOVE ALL, ASSOCIATED ELECTRICAL ITEMS (I.E. CABLE, CONDUIT, SUPPORTS,, DISCONNECTS, ETC) COMPLETE BACK TO SOURCE. ALL EXISTING FLUSH, MOUNTED BACK BOXES TO REMAIN., , P#, , D1, , J, D4, J, D3, D3, , J, D3, , J, D3, , J, D3, , J, D3, , D2, D3, D4, D5, D6, D7, D8, D9, D10, D11, D12, , D13, D14, , REMOVAL KEYNOTES, EXISTING EQUIPMENT TO BE REMOVED COMPLETE. DISCONNECT AND, REMOVE ALL ASSOCIATED ELECTRICAL ITEMS (I.E. CABLING, CONDUIT,, DISCONNECTS, BOXES, SUPPORTS, ETC) COMPLETE BACK TO POWER, SOURCE., EXISTING PENDANT MOUNTED FIXTURE TO BE REMOVED., EXISTING SURFACE MOUNTED FIXTURE TO BE REMOVED., EXISTING SURFACE MOUNTED DEVICE(S) TO BE REMOVED., EXISTING FLUSH MOUNTED DEVICE(S) TO BE REMOVED., EXISTING FLOOR MOUNTED DEVICE TO BE REMOVED., EXISTING RECESSED/GRID FIXTURE TO BE REMOVED., EXISTING WALL SCONCE LIGHT FIXTURE TO BE REMOVED., EXISTING ELECTRICAL PANEL TO BE REMOVED COMPLETE., EXISTING POWER POLE TO BE REMOVED COMPLETE., EXISTING DATA RACK TO REMAIN, PROTECT DURING CONSTRUCTION., EXISTING DUPLEX REMOVED FOR REPLACEMENT. DISCONNECT AND, REMOVE DEVICE AND ASSOCIATED CIRCUITRY BACK TO SOURCE., EXISTING BACK BOX TO REMAIN., EXISTING WEATHERHEAD AND UTILITY SERVICE TO BE REMOVED, COMPLETE., EXISTING UTILITY (AEP) METER WITH RISER TO WEATHERHEAD TO BE, REMOVED COMPLETE., EXISTING CARD ACCESS TO BE REMOVED COMPLETE., EXISTING DOORBELL BUTTON TO BE REMOVED COMPLETE., EXISTING PHOTOCELL NEAR GRADE TO BE REMOVED COMPLETE., EXISTING SURFACE MOUNTED EXTERIOR SPOT LIGHT TO BE REMOVED, COMPLETE., , DATE, , D15, D16, D17, D18, , DLZ OHIO, INC, , GENERAL NOTES, , 1, , ATTIC REMOVALS PLAN, , 1821-7001-50, , PROJECT NUMBER, , DECEMBER 06, 2018, DATE:, , TKF, APPRV'D:, , DESIGNED: RDW, , ATTIC REMOVALS PLAN, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , ELECTRICAL, , ED2.2, , LANCASTER, DRAWING NUMBER, , 12/5/2018 12:46:28 PM, , C:\users\rwilley\Documents\7001.50_Fairfield_rwilley.rvt, , OHIO, , DRAWN: RDW, , CHK'D: MLH, , NO., , NORTH, , REVISION, , ED2.2 SCALE: 1/8" = 1'-0"
Page 30 :
ONE-LINE DIAGRAM SYMBOLS:, COMBINATION TELEPHONE/DATA 6-PORT OUTLET SINGLE GANG., NUMBER = TOTAL QUANTITY OF JACKS AND CAT.6 CABLES TO EACH DEVICE., TC = TIME CLOCK, COORDINATE EXACT LOCATION WITH OWNER BEFORE ROUGH-IN., SCREEN = INFORMATION SCREEN, COORDINATE EXACT LOCATION WITH OWNER, BEFORE ROUGH-IN., INSTALL WITHIN A 4" x 4" EXTRA DEEP BOX AT +18" A.F.F., U.O.N., , COMBINATION TELVISION/DATA 4-PORT OUTLET., PROVIDE 1-DATA AND 1-TELEVISION JACK WITHIN RECEPTACLE. PROVIDE (1) CAT.6, CABLE AND (1) COAX CABLE. INSTALL WITHIN A 4" x 4" EXTRA DEEP BOX., RECESSED POKE-THROUGH OUTLET IN FLOOR WITH FURNITURE FEED. REFER TO, KEYNOTES FOR QUANTITY OF CAT.6 CABLES TO BE INSTALLED., , E. SEE MECHANICAL DRAWINGS FOR MECHANICAL EQUIPMENT RATINGS AND SIZES., , CONDUIT CONCEALED IN GROUND OR FLOOR., CONDUIT UP AND DOWN RESPECTIVELY., , 200, 200, , QUAD RECEPTACLE, 125V, 20A. INSTALL DEVICE AT +18" A.F.F., U.O.N., , ELECTRIC STRIKE PROVIDED BY DOOR HARDWARE CONTRACTOR, CARD ACCESS POINT. PROVIDE 1-GANG BOX WITH (2)-1/2"C WITH PULLSTRINGS., STUBBED OUT ABOVE NEAREST ACCESSIBLE CEILING FOR CONTROL AND POWER, WIRING. MOUNT BOX AT +48" AFF U.O.N., ACCESS CONTROL KEYPAD (TO ACTIVATE/DEACTIVATE SYSTEM) MOUNT AT +54" AFF, MAX., , BUS BAR., , SECURITY CAMERA, , FEEDER CIRCUIT., , JUNCTION BOX, RELAY, , R, , 1, A, , TOGGLE SWITCH, THREE WAY TYPE, 120/277V, 20A., , S3, , TOGGLE SWITCH, FOUR WAY TYPE, 120/277V, 20A., , S, , DIMMABLE SWITCH, 120/277V, 20A., , S, , 100A, , ENCLOSURE OUTLINE., , SHORT LINE INDICATES PHASE CONDUCTOR(S), , XX, , CABLE/CONDUIT EQUIPMENT SCHEDULE NUMBER., , ATS, , AUTOMATIC TRANSFER SWITCH, , SB, , SWITCHBOARD, , DISTRIBUTION PANELBOARD, SEE SCHEDULE FOR ADDITIONAL INFORMATION., NON-FUSED DISCONNECT SWITCH, SEE DRAWINGS FOR ADDITIONAL INFORMATION, , F 135, S, , P, , OR S, , R, , AMPERE FUSE, , MTS., , MANUAL TRANSFER SWITCH, , T. TO REDUCE NOISE BETWEEN WALLS, CONTRACTOR SHALL:, , A.F.C., , ABOVE FINISHED COUNTER, , NEC, , NATIONAL ELECTRICAL CODE, , A.F.F., , ABOVE FINISHED FLOOR, , NL, , NON-SWITCHED NIGHT LIGHT, , VARIABLE FREQUENCY DRIVE, SEE DRAWINGS FOR ADDITIONAL INFORMATION, , A.F.G., , ABOVE FINISHED GRADE, , NTRL., , NEUTRAL, , VARIABLE FREQUENCY DRIVE AND DISCONNECT COMBINATION, SEE DRAWINGS FOR, ADDITIONAL INFORMATION, , A.I.C., , AMPERES INTERRUPTING CAPACITY, , NTS, , NOT TO SCALE, OVERLOADS, , ATS, , AUTOMATIC TRANSFER SWITCH, , OL., , MAGNETIC MOTOR STARTER NUMBER INDICATES NEMA RATING, SIZE 1 U.O.N., , A.W.G., , AMERICAN WIRE GAUGE, , P, , POLE, , MOTOR. BY OTHERS, U.O.N., , BSMT., , BASEMENT, , POE, , POWER OVER ETHERNET, , SMOKE DAMPER. BY OTHERS, U.O.N. CONNECT TO 120V BRANCH CIRCUIT AND FIRE ALARM, CONTROL. PROVIDE DUCT DETECTOR AND TURN ON DAMPER., , C., , CONDUIT, , ∅, , PHASE, , C.B., , CIRCUIT BREAKER, , RCPT., , RECEPTACLE, , FIRE ALARM RELAY ADDRESSABLE INTERFACE DEVICE, , DED., , DEDICATED, , RECEPT., , RECEPTACLE, , DFA, , DROP FROM ABOVE, , RM., , ROOM, , DIV., , DIVISION, , SP., , SPARE, , FIRE ALARM HEAT DETECTOR. SURFACE MOUNT ON CEILING, , D.S, , DISCONNECT SWITCH, , SPEC, , SPECIFICATIONS, , FIRE ALARM SMOKE DETECTOR; P=PHOTOELECTRIC; R=ELEVATOR RECALL, , EX, , EXISTING TO REMAIN, , SSOL, , SOLID STATE OVERLOADS, , EC, , ELECTRICAL CONTRACTOR, , ST, , SAFETY TYPE, , FAAP, , FIRE ALARM ANNUNCIATOR PANEL, , SW., , SWITCH, , FACP, , FIRE ALARM CONTROL PANEL, , G., , GROUND, , T.B.I., , TO BE INSTALLED, , GFI, , GROUND FAULT INTERRUPT, , T.B.R., , TO BE REMOVED, , TWSH., , TWISTED SHIELDED, , TYP., , TYPICAL, , U.O.N., , UNLESS OTHERWISE NOTED, , U.P.S., , UNINTERRUPTABLE POWER SOURCE, , V, , VOLTS, , V.F.D., , VARIABLE FREQUENCY DRIVE, , W, , WIRE, , WP, , WEATHERPROOF, , FIRE ALARM AUDIBLE AND VISUAL STROBE COMBO DEVICE; WP=WEATHERPROOF, , F, , FIRE ALARM VISUAL STROBE ANNUNCIATOR., , GFCI, , GROUND FAULT CIRCUIT INTERRUPT, , WP, F, , FIRE ALARM AUDIBLE DEVICE; WP=WEATHERPROOF, , GRND, , GROUND, , H.O.A., , HAND OFF AUTOMATIC, , H.L.O.A., , HIGH LOW OFF AUTOMATIC, , HNDLR, , HANDLER, , KAIC, , KILO-AMPERES INTERRUPTING CAPACITY, , KVA, , KILO-VOLT-AMPS, , KW, , KILOWATTS, , LTG., , LIGHTING, , MCB, , MAIN CIRCUIT BREAKER, , MCC, , MOTOR CONTROL CENTER, , MFR., , MANUFACTURER, , FACP, , 12/5/2018 12:45:58 PM, , C:\users\rwilley\Documents\7001.50_Fairfield_rwilley.rvt, , M, , R. THE CONTRACTOR SHALL COORDINATE RECEPTACLE HEIGHTS AND LOCATIONS WITH THE, CASEWORK SHOP DRAWINGS TO DETERMINE EXACT FINAL LOCATIONS AND HEIGHTS FOR, OUTLET INSTALLATION., , A.F, , S, , FAAP, , Q. ALL CONDUITS CROSSING EXPANSION JOINTS SHALL BE INSTALLED WITH EXPANSION FITTINGS,, UNLESS THE CONDUIT IS BELOW SLAB IN THE COMPACTED GRANULAR FILL. EXPANSION, FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE NEC AND MANUFACTURER'S, WRITTEN RECOMMENDATIONS. REFER TO STRUCTURAL DRAWINGS FOR EXPANSION JOINT, LOCATIONS., , MAIN LUG ONLY, , FIRE ALARM DUCT MOUNTED SMOKE DETECTOR, HOUSING , AND SAMPLING TUBE., PROVIDE CONNECTION FOR DAMPER/FAN MOTOR CONTROL., WP, F, , ABBREVIATIONS:, , P. INDOOR CONTROL EQUIPMENT ENCLOSURES SHALL BE NEMA 1 RATED U.O.N. ALL EXTERIOR, ENCLOSURES SHALL BE NEMA 3R UNLESS OTHERWISE NOTED., , MLO, , FIRE ALARM MANUAL PULL STATION, , F, , N. ALL FIRE ALARM CABLING SHALL BE RED, PLENUM RATED, AND INSTALLED IN RED CONDUIT., , AMPERES, , STARTER/DISCONNECT COMBINATION, SEE DRAWINGS FOR ADDITIONAL INFORMATION, , RAID, , M. MAJOR FEEDERS FROM THE SWITCHBOARD TO PANELBOARDS, TRANSFORMERS, MOTORS, AND OTHER LARGE EQUIPMENT ARE NOT SHOWN ON THE FLOOR PLAN DRAWINGS. THESE, FEEDERS ARE INCLUDED WITHIN THE SCOPE OF THE ELECTRICAL WORK AND ARE SHOWN ON, THE ONE-LINE DIAGRAM., , A, , STARTER, SEE DRAWINGS FOR ADDITIONAL INFORMATION, , FD, , DISCONNECT SWITCH RATINGS SHALL BE AS INDICATED ON THE DRAWINGS., , S. TEMPERATURE CONTROL CONTRACTOR RESPONSIBLE FOR LOCATION AND QUANTITY OF, TRANSFORMERS REQUIRED FOR 24V CONTROL COMPONENTS. COORDINATE WITH DIVISION 26, TO PROVIDE REQUIRED POWER TO COMPONENTS., , FUSED DISCONNECT SWITCH, SEE DRAWINGS FOR ADDITIONAL INFORMATION, , 3, , L., , O. HVAC CONTROL WIRING AND CONDUITS FURNISHED AND INSTALLED BY MECHANICAL, CONTRACTOR. POWER TO THE BMS CONTROL PANEL PROVIDED BY DIVISION 26., , DUAL TECHNOLOGY OCCUPANCY SENSOR WALL SWITCH. COVERAGE OF SENSOR, DEPENDENT ON ROOM SIZE., , S, OS, , NON-FUSED DISCONNECT SWITCH. NUMBER INDICATES RATING IN AMPERES., , LONG LINE INDICATES NEUTRAL CONDUCTOR(S), , DUAL TECHNOLOGY OCCUPANCY SENSOR, CEILING MOUNT, COVERAGE OF SENSOR, DEPENDENT ON ROOM SIZE., , OC, , GROUND., , BRANCH CIRCUIT HOME-RUN SYMBOLOGY:, SOLID CIRCLE INDICATES GROUND CONDUCTOR, , MANUAL MOTOR STARTER., , M, , TRANSFORMER. PRIMARY VOLTAGE, SECONDARY VOLTAGE, RATING IN KVA AS, INDICATED. K FACTOR AS INDICATED., , PHOTOCELL, , PC, , D, , 480-208/120V, 150 KVA, K=13, , WALL MOUNTED SPEAKER, TIED TO PAGING SYSTEM, , W, , MOTOR WITH HORSEPOWER INDICATED., , K. SUPPORTING WIRE FOR THE SUSPENDED CEILING GRID SHALL NOT BE USED AS RACEWAY, SUPPORT., , CEILING MOUNTED SPEAKER, TIED TO PAGING SYSTEM, , S, S, , S4, , LIGHT FIXTURE WITH HALF SOLID SHADING INDICATES FIXTURE IS TO CONTAIN AN, EMERGENCY BATTERY BACKUP. REFER TO LIGHT FIXTURE SCHEDULE ON E5.1., , 1, , TOGGLE SWITCH, 120/277V, 1-POLE, 20A., , S, , LIGHT FIXTURE. "A" INDICATES FIXTURE TYPE. REFER TO LIGHT FIXTURE, SCHEDULE ON E5.1, , EACH SINGLE PHASE BRANCH CIRCUIT CONDUCTOR SHALL HAVE A DEDICATED NEUTRAL BACK, TO THE PANELBOARD., , FIRE ALARM REMOTE ANNUNCIATOR PANEL., FIRE ALARM CONTROL PANEL., , MAGNETIC HOLD OPENS TIED TO FIRE ALARM, , 1. AVOID INSTALLING POWER RECEPTACLES OR DATA OUTLETS LOCATED BACK TO BACK., , DEMOLITION NOTES:, A. ALL EXISTING SYSTEMS (LIGHTING, POWER, SYSTEMS) TO BE REMOVED COMPLETE, UNLESS, OTHERWISE NOTED. DISCONNECT AND REMOVE ALL ASSOCIATED ELECTRICAL ITEMS (I.E., CABLE, CONDUIT, SUPPORTS, DISCONNECTS, ETC) COMPLETE BACK TO SOURCE., B. WHERE EXISTING EQUIPMENT OR MATERIALS ARE REMOVED OR CHANGED, ALL BRANCH, CONDUITS WHICH NO LONGER ARE IN SERVICE, SHALL BE REMOVED., C. ALL BUILDING SURFACES DAMAGED, OR OPENINGS LEFT BY REMOVAL OF BOXES, PIPING OR, OTHER EQUIPMENT, SHALL BE REPAIRED BY THE CONTRACTOR., D. WHERE NEW OPENINGS ARE CUT AND CONCEALED CONDUITS, ETC ARE ENCOUNTERED THEY, SHALL BE REMOVED OR RELOCATED AS REQUIRED. WHERE CONDUIT TO BE REMOVED TO THE, POINT WHERE THE FINISH SURFACES CAN BE PATCHED ADEQUATELY SO THAT NO EVIDENCE, OF THE FORMER INSTALLATION REMAINS., , 2. WHERE OUTLETS ARE REQUIRED TO BE LOCATED BACK TO BACK, CONTRACTOR SHALL, PROVIDE SOUNDPROOFING MATERIAL BETWEEN JUNCTION BOXES, U. THE WORD "PROVIDE" IS TO BE DEFINED AS "FURNISH AND INSTALL"., V. ELEVATOR SHAFTS SHALL NOT BE USED FOR NON-ELEVATOR RELATED ITEMS (I.E. PIPING,, CONDUITS, ETC.), , E. REFER TO THE ARCHITECTURAL DRAWINGS WHICH SHOW THE TOTAL DEMOLITION IN SPECIFIC, AREAS. CONTRACTOR SHALL COOPERATE IN THIS DEMOLITION TO ENSURE THAT POWER IS, OFF AND THAT ELECTRICAL EQUIPMENT WHICH MUST REMAIN IS PROPERLY PROTECTED., F. SALVAGE: ALL RE-USABLE DEVICES, FIXTURES AND EQUIPMENT SHALL BECOME THE, PROPERTY OF THE OWNER AND SHALL BE STORED BY THE CONTRACTOR IN A ROOM TO BE, DESIGNATED BY THE OWNER. ALL OTHER SALVAGE AND DEBRIS SHALL BE REMOVED FROM, THE PREMISIS DAILY., , ELECTRICAL, , A, , J., , 1821-7001-50, , J, , 20, , HOME RUNS SHALL NOT BE COMBINED IN A RACEWAY UNLESS SHOWN ON THE CONTRACT, DRAWINGS. SINGLE PHASE BRANCH CIRCUIT HOME RUNS MAY BE COMBINED AT THE, CONTRACTOR'S DISCRETION NOT GREATER THAN (3) PHASE CONDUCTORS, (3) NEUTRAL, CONDUCTORS, AND REQUIRED GROUNDING CONDUCTOR(S). CONTRACTOR MUST INCREASE, WIRE SIZE AND DERATE CONDUCTOR CAPACITY ACCORDING TO NEC., , GENERAL NOTES, SYMBOLS & ABBREVIATIONS, , SPECIAL RECEPTACLE ON EMERGENCY CIRCUIT, REFER TO MANUFACTURER, REQUIREMENTS. INSTALL DEVICE AT +18" A.F.F., U.O.N., , WIRELESS ACCESS POINT; DEVICE PROVIDED BY OWNER., , WAP, , I., , PROJECT NUMBER, , SPECIAL RECEPTACLE, REFER TO MANUFACTURER REQUIREMENTS. INSTALL, DEVICE AT +18" A.F.F., U.O.N., , H. ALL CABLES INSTALLED IN AIR HANDLING PLENUMS SHALL BE PLENUM RATED CABLE., , E1.0, , KP, , THERMAL MAGNETIC CIRCUIT BREAKER. TOP NUMBER INDICATES TRIP RATING IN, AMPERES. BOTTOM NUMBER INDICATES FRAME RATING IN AMPERES., , DECEMBER 06, 2018, , QUAD RECEPTACLE ON EMERGENCY CIRCUIT, 125V, 20A. INSTALL DEVICE AT +18", A.F.F., U.O.N., , 200AT, 200AF, , DATE:, , CA, , QUAD RECEPTACLE ON EMERGENCY CIRCUIT, 125V, 20A. INSTALL DEVICE ABOVE, COUNTER. REFER TO ARCHITECTURAL PLANS FOR ELEVATIONS., , G. ALL CONTROL WIRING SHALL BE NOT LESS THAN (2) #14, (1) #14G, 3/4"C, UON., , TKF, , S, , APPRV'D:, , E, QUAD RECEPTACLE, 125V, 20A. INSTALL DEVICE ABOVE COUNTER. REFER TO, ARCHITECTURAL PLANS FOR ELEVATIONS., , FUSED SWITCH. TOP NUMBER INDICATES SWITCH RATING IN AMPERES. BOTTOM, NUMBER INDICATES FUSE RATING IN AMPERES., , F. ALL POWER AND LIGHTING CIRCUITS SHALL BE MINIMUM (2 )#12, AND (1) #12 G, IN 3/4" CONDUIT, UNLESS OTHERWISE NOTED. CIRCUITS EXCEEDING 125 FEET IN LENGTH SHALL BE MINIMUM (2), #10, AND (1)#10 G, IN 3/4" CONDUIT UNLESS OTHERWISE NOTED., , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , DUPLEX RECEPTACLE FLOOR BOX 125V, 20A. REFER TO SPECIFICATIONS AND, DRAWINGS FOR FURTHER DETAILS., , D. PENETRATIONS THROUGH FIRE RATED WALLS BY DIVISION 26 CONTRACTOR SHALL BE SEALED, WITH THE APPROPRIATE FIRE STOPPING MATERIAL TO MAINTAIN WALL FIRE RATING. SEE, ARCHITECTURAL DRAWING FOR FIRE RATED WALL LOCATIONS., , DATE, , DUPLEX RECEPTACLE CEILING MOUNTED ON EMERGENCY CIRCUIT 125V, 20A. REFER, TO SPECIFICATIONS AND DRAWINGS FOR FURTHER DETAILS., , MAIN CIRCUIT BREAKER PANELBOARD. "PANEL" INDICATES PANEL DESIGNATION., "120/208" INDICATES PANEL OPERATING VOLTAGE. "3∅, 4W" INDICATES PHASE AND, WIRE. "200A 3P" INDICATES 3 POLE MAIN LUGS RATED FOR 200A., , REVISION, , DUPLEX RECEPTACLE CEILING MOUNTED 125V, 20A. REFER TO SPECIFICATIONS AND, DRAWINGS FOR FURTHER DETAILS., , PANEL, 200 AMP, 120/208V, 3∅, 4W, MCB, , NO., , TV, , C. ALL CONNECTIONS TO EQUIPMENT SUBJECT TO MOVEMENT OR VIBRATION SHALL BE LIQUID, TIGHT FLEXIBLE METAL CONDUIT, NOT LESS THAN 12" IN LENGTH, NOR GREATER THAN 36" IN, LENGTH., , DESIGNED: RDW, , DUPLEX RECEPTACLE ON EMERGENCY CIRCUIT, 125V, 20A. INSTALL DEVICE ABOVE, COUNTER. REFER TO ARCHITECTURAL PLANS FOR ELEVATIONS., , CHK'D: MLH, , DUPLEX RECEPTACLE ON EMERGENCY CIRCUIT, 125V, 20A. INSTALL DEVICE AT +18", A.F.F., U.O.N., , B. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL ELECTRICAL CODE 2017 EDITION ,, THE OHIO ELECTRICAL CODE AMENDMENTS, LOCAL/MUNICIPAL CODES, AND THE AUTHORITY, HAVING JURISDICTION., , DRAWN: RDW, , TC, SCREEN, , A. DRAWINGS ARE DIAGRAMMATIC. ALL DIMENSIONS SHOWN ARE APPROXIMATE. ALL LOCATIONS, SHALL BE FIELD VERIFIED., , OHIO, , 2, , MAIN LUG ONLY PANELBOARD. "PANEL" INDICATES PANEL DESIGNATION. "120/208", INDICATES PANEL OPERATING VOLTAGE. "3∅, 4W" INDICATES PHASE AND WIRE., "200A 3P" INDICATES 3 POLE MAIN LUGS RATED FOR 200A., , LANCASTER, , DUPLEX RECEPTACLE, 125V, 20A. INSTALL DEVICE ABOVE COUNTER. REFER TO, ARCHITECTURAL PLANS FOR ELEVATIONS., , PANEL, 200 AMP, 120/208V, 3∅, 4W, MLO, , PLAIN OLD TELEPHONE SYSTEM OUTLET. PROVIDE (1) CAT 6 CABLE WITH (1) RJ11, JACK. INSTALL DEVICE WITH BOTTOM AT +16" AFF., U.O.N., , DRAWING NUMBER, , POTS, , DUPLEX RECEPTACLE, 125V, 20A. INSTALL DEVICE AT +18" A.F.F., U.O.N., , GENERAL NOTES:, DLZ OHIO, INC, , ELECTRICAL SYMBOLS:
Page 32 :
2P-32, , F-4, 3P-12, , P1, 2P-34, , 2P-34, , APPRAISAL, X29, , CORRIDOR, X25, , GIS OFFICE, X22, , 2P-24, , 2P-28, , 2P-26, TV,+60", P2, , P1, , 2P-34, , NOT ALL KEYNOTES ARE USED ON EVERY SHEET., , P1, 2P-28, , 2P-30, , P1, , P1, , 2P-26, P2, , 2P-24, , 2P-30, P1, , 2P-28, , P#, , DSS-1, 2P-10,12, , DATA, COLLECT./, CAUV, X23, , P3, , 2P-26, P1, , 2P-26, , P4, P5, , 2P-24, , P6, P7, , 1, E2.1, , P8, P9, , SECOND FLOOR POWER PLAN, SCALE: 1/8" = 1'-0", , NORTH, P10, , P11, P12, , P13, P14, P15, , P16, , P17, P18, P19, , F-5A, 2P-41, , F-5B, 2P-35, , 2P-31, GFCI, , 2P-31, GFCI, P20, , F-3, 2P-37, , F-6, 2P-39, , P21, P22, P23, , 2, E2.1, , PROVIDE ONE 4" FURNITURE FEED POKE-THRU DEVICE LIKE WIREMOLD, #4FFATC15 OR APPROVED EQUAL. PROVIDE 3/4" FLEX FEED TO FURNITURE,, COORDINATE EXACT LOCATION BEFORE ROUGH-IN. CONNECT TO DEVICE, USING 2#12+G. IN 3/4"C., RECEPTACLE FOR TV, COORDINATE EXACT LOCATION WITH OWNER, BEFORE ROUGH-IN. TV AND MOUNTING BRACKET PROVIDED BY OWNER,, INSTALLED BY CONTRACTOR., AUTOMATIC FLUSH VALVE, REFER TO AUTOMATIC ELECTRONIC FLUSH, VALVE DETAIL #7 ON SHEET E5.3., MAIN GROUND BUS BAR #1. REFER TO BUILDING GROUND BUS DETAIL #5, ON SHEET E5.3. MOUNT AT +7-0" AFF., PROVIDE (1) FLUSH IN CONCRETE 3-GANG FLOOR BOX LIKE WALKER, #880CS3-1 OR APPROVED EQUAL. FURNISH WITH 3-GANG BRASS, CARPET/TILE FLANGE (#837B), (2) FLIP LIDS (#828R) FOR TWO 20A DUPLEX, RECEPTACLES AND (1) COVER PLATE (#828COM) FOR FOUR CAT.6, COMMUNICATIONS CABLES. VERIFY EXACT LOCATION WITH OWNER AND, ARCHITECT BEFORE ROUGH-IN., NEW DEVICE TO BE SURFACE MOUNTED ON EXISTING WALL., 1-GANG WALL BOX WITH FURNITURE FEED FOR POWER TO MODULAR, FURNITURE. PROVIDE 3/4" FLEX FEED TO FURNITURE, COORDINATE EXACT, LOCATION BEFORE ROUGH-IN. CONNECT TO DEVICE USING 2#12+G. IN 3/4"c., CONNECT TO CIRCUIT SHOWN USING 2#10+G. IN 3/4"C., FURNISH AS REQUIRED TOGGLE SWITCH FOR GARBAGE DISPOSAL, CONTROL WITH RACEWAY AND CONDUCTORS FROM SWTICH TO GARBAGE, DISPOAL UNIT, 1/2HP, 120V. MOUNT SWITCH ABOVE COUNTERTOP. CIRCUIT, AS SHOWN., FURNISH ONE 8" POKE-THRU DEVICE LIKE WIREMOLD #8AT EVOLUTION, SERIES OR APPROVED EQUAL. DEVICE TO HAVE (4) 20A DUPLEX, RECEPTACLES AND PROVISIONS FOR (6) COMMUNICATIONS PORTS. FINISH, TO BE SELECTED BY ARCHITECT. PROVIDE WITH (2) #8DP AND (1) #8ACT6A, CENTER MOUNT DEVICE PLATES AND (2) #68REC SIDE MOUNT DEVICE, PLATES. COORDINATE EXACT LOCATION BEFORE ROUGH-IN. PROVIDE ALL, ACCESSORIES NEEDED FOR A COMPLETE INSTALLATION. CONNECT TO, DEVICE USING 2#12+G. IN 3/4"C., FURNISH AND INSTALL NEW 20A, DUPLEX RECEPTACLE IN SAME BOX AS, REMOVED RECEPTACLE. CIRCUIT AS SHOWN., AUTOMATIC DOOR OPENER. PUSHBUTTONS BY MANUFACTURER, WIRE PER, MANUFACTURER'S RECOMMENDATION, 120V. COORDINATE EXACT, LOCATION BEFORE ROUGH-IN., ELECTRIC DOOR. VERIFY WITH MANUFACTURER ALL FINAL CONNECTIONS., NON-GFCI RECEPTACLE FOR SUMP PUMP. MOUNT ON PIT WALL NEAR SUMP, BASIN. COORDINATE EXACT LOCATION BEFORE ROUGH-IN., ELEVATOR DISCONNECT SWITCH 'DIS-ELEV', SWITCH PROVIDED BY, ELEVATOR SUPPLIER INSTALLED BY E.C. MOUNT IN ELEVATOR WITH TOP A, MINIMUM OF 6" BELOW BOTTOM OF ENTRY DOOR INTO PIT. COORDINATE, EXACT LOCATION WITH ELEVATOR SUPPLIER. CONNECT TO CIRCUIT, SHOWN USING 4#1/0 + #1/0G. IN 2"C., FURNISH AND INSTALL NEMA 3R, SURFACE, 30A LOCKABLE MOTOR RATED, TOGGLE SWITCH WITH WEATHERPROOF COVER FOR DISCONNECTING THE, 120V ELEVATOR CAB LIGHT AND FAN POWER. CIRCUIT AS SHOWN., COORDINATE EXACT LOCATION WITH ELEVATOR SUPPLIER., CONTROL PANEL 'CP-O', 120V. PANEL TO BE PROVIDED BY OWNER., CONNECT TO CIRCUIT SHOWN USING 2#12+G. IN 3/4"C., NEW ELECTRIC UTILITY METER 'M-1' LOCATION, REFER TO ONE-LINE, DIAGRAM ON SHEET E5.0 FOR MORE INFORMATION., NEW 3-1/2" RACEWAY #100 FROM NEW UTILITY METER 'M-1' TO NEW MAIN, DISTRIBUTION PANEL 'MDP', REFER TO CONDUIT AND CABLE SCHEDULE ON, DRAWING E5.0 FOR MORE INFORMATION. PROVIDE SEAL FOR PENETRATION, THRU EXISTING WALL. REFER TO LINK SEAL DETAIL - OUTDOOR, PENETRATIONS THROUGH WALL DETAIL #4 ON DRAWING E5.3., TRI-ROD GROUND. SPACE GROUND ELECTRODE RODS A MINIMUM OF 10'-0", APART., #1/0 AWG BARE COPPER CABLE., FURNISH AND INSTALL A 3/4" DIA., 10'-0" LONG COPPER GROUND ROD., COPPERWELD TO GROUND LOOP., PROVIDE GROUND TEST WELL FOR ONE (1) OF THREE GROUNDING, ELECTRODES. REFER TO DETAIL #8, SHEET E5.3., NEW WATER METER. BOND TO MAIN GROUND BUS BAR #1 IN BASEMENT., REFER TO DETAIL #2, SHEET E5.1., , ATTIC POWER PLAN, SCALE: 1/8" = 1'-0", , DRAWING NUMBER, , LANCASTER, , NORTH, , 12/5/2018 12:51:24 PM, , C:\users\rwilley\Documents\7001.50_Fairfield_rwilley.rvt, , P24, , POWER KEYNOTES, , ELECTRICAL, , 2P-30, , 2P-22, , P8, 2P-14,16, NEMA L5-30R, , 1821-7001-50, , 3P-10, , P1, , G., , IT/DATA, X21, , SECOND FLOOR AND ATTIC POWER PLANS, , 2P-36, COPIER, , P17, CP-O, , 2P-22, , 2P-28, , 2P-32, , P1, , 2P-22, +48", , 2P-22, , 2P-32, , 2P-32, , 3P-11, GFCI, , 2P-22, , 2P-8, +84", , PROJECT NUMBER, , P9, 2P-25, , 2P-22, , CORRIDOR, X24, , 3P-11, , 3P-10, 3P-10, TV,+84", P2, , 2P, , 2P-11, GFCI, , E2.1, , 3P-8, , 2P-13, , WIRING DEVICES AND RACEWAYS ON EXISTING WALLS TO BE SURFACE, MOUNTED, U.O.N. RACEWAYS AND RACEWAY ACCESSORES SHALL BE LOW, PROFILE, NON-METALLIC RACEWAY SUITABLE TO FINISHED OFFICE AREAS, (I.E. LEGRAND/WIREMOLD 400/800/2300 SERIES OR APPROVED EQUAL)., INSTALL IN NEAT AND WORKMANLIKE MANNER TO MINIMIZE LENGTHS,, BENDS, ELBOWS, ETC. PAINT RACEWAYS TO MATCH WALL FINISH COLOR., , DECEMBER 06, 2018, , 3P-10, , 2P-13, , RE, CONTRACT, X27, 2P-11, , DATE:, , 3P-8, , P1, , 2P-21, M GFCI+42", , CLOSET, X26, , P10, , TKF, , P1, , 3P, , P10, , F., , 2P-15, 2P-11, , 2P-19, , 2P-29, MICRO+60", , MECH/ ELEC, 207, , 3P-10, CONFERENCE, 203, , 2P-21, , REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND, CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE RATED, PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS AND OFFSET, BACK TO BACK BOXES., , APPRV'D:, , 3P-8, , 2P-27, COFFEE, GFCI+42", 2P-23, REFRIG, +48", , E., , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , 3P-9, EF-4, , 3P-9, EF-3, , MEN'S RR, 206, , CONTRACTOR SHALL COORDINATE ALL DEVICE HEIGHTS AND EXACT, LOCATIONS WITH CASEWORK SHOP DRAWINGS AND ARCHITECTURAL, ELEVATION DETAILS., , DATE, , P3, , 2P-17, , D., , REVISION, , 2P-19, , SEE MECHANICAL EQUIPMENT - ELECTRICAL CONNECTION SCHEDULE ON, DRAWING E5.0 FOR EQUIPMENT CIRCUITING AND ADDITIONAL ELECTRICAL, REQUIREMENTS FOR MECHANICAL EQUIPMENT (I.E. DISCONNECT,, STARTER, ETC) AND LOAD INFORMATION., , NO., , J J, , 2P-11, , P2, 2P-21, TV,+84", , C., , DESIGNED: RDW, , P3, , ELEV, 3P-11, 106, GFCI, 3P-7 J J 3P-7, ELEVATOR, GFCI+48", LOBBY GFCI+48", RP-1, P3, P3, 3P-15, 201, 3P-11 CORRIDOR, 3P-11, 3P-11, 204, 3P-11, GFCI+48", SCREEN, , 3P-8, , 2P-21, , FOR SERVICE GROUNDING ELECTRODE SCHEMATIC, SEE DETAIL #2 ON, DRAWING E5.1., , CHK'D: MLH, , 3P-7, , 2P-21, , 3P-13, WH-1, , F-1, 3P-14, , BREAK, ROOM, X28, , 3P-16, EWH-1, , B., , DRAWN: RDW, , 3P-18, EWH-1, , FOR PANELBOARD SCHEDULES, SEE DRAWINGS E5.2., , OHIO, , WOMEN'S, RR, 205, , 2P-20, , MECH/, STORAGE, 202, , A., , DLZ OHIO, INC, , GENERAL NOTES
Page 35 :
A., , CONTRACTOR SHALL COORDINATE ALL DEVICE HEIGHTS AND EXACT, LOCATIONS WITH CASEWORK SHOP DRAWINGS AND ARCHITECTURAL, ELEVATION DETAILS., , B., , REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND, CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE RATED, PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS AND OFFSET, BACK TO BACK BOXES., , C., , REFER TO DRAWING E5.3, DETAIL #1 FOR FIRE ALARM DEVICES MOUNTING, REQUIREMENTS PER NFPA., , D., , ALL FIRE ALARM CONDUITS SHALL BE FACTORY PAINTED "RED". ALL, PULL/JUNCTION BOX COVERS SHALL BE FACTORY PAINTED RED., , E., , WIRING DEVICES AND RACEWAYS ON EXISTING WALLS TO BE SURFACE, MOUNTED, U.O.N. RACEWAYS AND RACEWAY ACCESSORES SHALL BE LOW, PROFILE, NON-METALLIC RACEWAY SUITABLE TO FINISHED OFFICE AREAS, (I.E. LEGRAND/WIREMOLD 400/800/2300 SERIES OR APPROVED EQUAL)., INSTALL IN NEAT AND WORKMANLIKE MANNER TO MINIMIZE BENDS,, ELBOWS, ETC. PAINT RACEWAYS TO MATCH WALL FINISH COLOR., , F., , REFER TO DRAWING A3.2, GENERAL NOTE E, FOR ACCESS CONTROL, REQUIREMENTS., , G., , NOT ALL KEYNOTES ARE USED ON EVERY SHEET., , S7, , LOWER LEVEL SYSTEMS PLAN, , E4.0, , SCALE: 1/8" = 1'-0", S8, , NORTH, , S9, , S10, , S11, , S12, S13, , S14, , S15, S16, , S12, , 2, , P, , S9, , S8, , P, , 2, , FAA, 2, , 2 CONVEYANCE, 104, S4, , 1P, , S8, , CORRIDOR, X20, , 4, S12, , 2, , s, F, S12, , S8, CA, , P, , WAP, , F, s, 4, , P, , 2, MAP ROOM, X17, , P, , P, , P, , S12, , 4 TV, +84", , S12, , S8, CA, , F, , S, CA S8, , WAP, , S12, , INTERFACE FIRE ALARM CONTROL PANEL WITH ELEVATOR, CONTROLLER SO THAT ACTIVATION OF ELEVATOR LOBBY OR, ELEVATOR SHAFT SMOKE DETECTORS RECALLS THE ELEVATOR TO, THE FIRST FLOOR., ACCESS CONTROL KEYPAD. PROVIDE 1-GANG RECESSED BOX WITH, (2)-1/2"C. STUBBED OUT ABOVE ACCESSIBLE CEILING FOR CONTROL, WIRING AND DATA. COORDINATE EXACT LOCATION WITH OWNER, BEFORE ROUGH-IN., TELEPHONE TERMINAL BOARD 'TTB-1'. BOARD SHALL BE PLYWOOD, AND 8'-0"H. X 4'-0"W X 3/4"D. REFER TO SPECIFICATION 271100 FOR, DETAILED REQUIREMENTS. PAINT (2) COATS MARINE GRADE FIRE, RETARDENT PAINT TO MATCH WALL FINISH. ALSO, REFER TO SHEET, A2.2, KEYED NOTE 0607 FOR MORE INFORMATION., , S, BOR OFFICE, X12, , S4, S12, , TV, +84", , P, S11, , 4, , S9, S9, 4, , 4, , P, 4, , 4, , POTS, , 4, , 4, S9, , S12, , S12, , S12, , S11, F F, , S12, , P, , S12, , WAP, , HEARING, ROOM, X13, , S12, , S4, CA, S12, , 1, E4.0, NORTH, , FIRST FLOOR SYSTEMS PLAN, SCALE: 1/8" = 1'-0", , DRAWING NUMBER, , LANCASTER, , S, , 12/5/2018 12:46:13 PM, , C:\users\rwilley\Documents\7001.50_Fairfield_rwilley.rvt, , SERVICE, AREA, X16, , S19, , S KP S18, CA S8, , P, , S12, , S12, , S9, , CORRIDOR, X11, , P, , 2, , S9, 4, , HEARING, WAITING, X14, , 1,SCREEN, +84", , S8 CA, , S, , CORRIDOR, X15, , P, , S4, , WAP, , P, , S, , S8 CA, , 4, , S, , CA, , CA, S, , POTS, , VESTIBULE, 101, , S9, , 1,SCREEN, +84", CORRIDOR, 103, , S18, , F, , 1,TC, +48", , F, P, , S12, 4, , F, , s, , S CA, , R, LOBBY/, SERVICE, 102, , s, , F, , S12, , P, , P, , F, , S, , s, , S8, , 4, , S12, , F, , P, , MEN'S RR, 108, , S17, , S12, , s, , WOMEN'S, RR, 107, , 4, , GIS, X18, , F, , S18 KP, S8 CA, , MAP, STORAGE, X19, , F, , JAN., 105, , ELECTRICAL, , 2, , 1821-7001-50, , S6, , LOWER LEVEL AND FIRST FLOOR SYSTEMS PLANS, , S5, , PROJECT NUMBER, , S16, , E4.0, , S4, , DECEMBER 06, 2018, , S3, , DATE:, , P, , TKF, , S, , APPRV'D:, , 2,POTS, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , P, , DATE, , S, , REVISION, , F.A.C.P., , 2, , NO., , POTS, , S2, , SPD-MDP, , RAID, , DESIGNED: RDW, , MDP, , REFER TO SITE/CIVIL DRAWING, C07.0 FOR CONTINUATION, , CHK'D: MLH, , S17, , EQUIPMENT RACK FOR DATA EQUIPMENT (SERVERS, SWITCHES,, PATCH PANEL(S) AND UPS, ETC) FURNISHED BY OWNER., GROUND BUS BAR NO.2. MOUNT AT +7'-0" AFF. REFER TO TELE-DATA, EQUIPMENT GROUND BUS DETAIL #4, DRAWING E5.3. BOND TO MAIN, GROUND BUS BAR NO.1 (IN LOWER LEVEL ELECTRICAL ROOM) USE, #1/0 AWG COPPER GREEN INSULATED CABLE., STUB 2-3"C OUT INTO 1ST FLOOR ACCESSIBLE CEILING SPACE FOR, DATA/TEL CABLES, WIRELESS ACCESS POINT (WAP) LOCATED ON CEILING. WAP, PROVIDED BY OWNER, INSTALLED BY CONTRACTOR. FURNISH AND, INSTALL (2) CAT6 DATA CABLES WITH 10' OF SLACK FOR FINAL, PLACEMENT OF DEVICE., NEW FURNITURE FEED POKE-THRU, REFER TO KEYNOTE #P1 ON, SHEET #E2.1 FOR MORE INFORMATION. FURNISH AND INSTALL FOUR, (4) CAT6 CABLES TO FURNITURE, COORDINATE EXACT LOCATION, BEFORE ROUGH-IN., NEW FURNITURE FEED POKE-THRU, REFER TO KEYNOTE #P1 ON, SHEET #E2.1 FOR MORE INFORMATION. FURNISH AND INSTALL EIGHT, (8) CAT6 CABLES TO FURNITURE, COORDINATE EXACT LOCATION, BEFORE ROUGH-IN., #1/0 AWG COPPER GREEN INSULATED GROUND CABLE. BOND TO, MAIN GROUND BUS #1 (IN MECHANICAL #1502). REFER TO DETAIL #5,, DRAWING E5.3., CARD ACCESS POINT. PROVIDE 1-GANG RECESSED BOX WITH, (2)-1/2"C. STUBBED OUT ABOVE ACCESSIBLE CEILING FOR CONTROL, WIRING AND DATA. COORDINATE EXACT LOCATION WITH OWNER, BEFORE ROUGH-IN., POWER OVER ETHERNET SECURITY CAMERA. CAMERA PROVIDED BY, OWNER, INSTALLED BY CONTRACTOR. FURNISH AND INSTALL (1) CAT6, DATA CABLE WITH 10' OF SLACK FOR FINAL PLACEMENT OF CAMERA., NEW 8" POKE-THRU DEVICE, REFER TO KEYNOTE #P10 ON SHEET, #E2.1 FOR MORE INFORMATION. FURNISH AND INSTALL (4) CAT 6, CABLES TO DEVICE. COORDINATE EXACT LOCATION BEFORE, ROUGH-IN., NEW CONCRETE FLOOR BOX, REFER TO KEYNOTE #P5 ON SHEET, #E2.1 FOR MORE INFORMATION. FURNISH AND INSTALL FOUR (4) CAT6, CABLES AND ASSOCIATED JACKS TO EACH BOX, COORDINATE EXACT, LOCATION BEFORE ROUGH-IN., NEW DEVICE(S) TO BE SURFACE MOUNTED ON EXISTING WALL., NEW FURNITURE FEED POKE-THRU, REFER TO KEYNOTE #P1 ON, SHEET #E2.0 FOR MORE INFORMATION. FURNISH AND INSTALL FOUR, (6) CAT6 CABLES TO FURNITURE, COORDINATE EXACT LOCATION, BEFORE ROUGH-IN., UNIT PROVIDED WITH DUCT SMOKE DETECTOR IN RETURN DUCT., PROVIDE ADDRESSABLE CONNECTION AS NEEDED TO FACP IN, LOWER LEVEL., PROVIDE (1) CAT6 CABLE FROM PANEL 'CP-O' TO COUNTY IT SERVER., VERIFY WITH OWNER EXACT LOCATION OF SERVER., NEW 4"C. WITH PULLSTRING UP TO IT/DATA #X21 FOR UTILITY, COMMUNICATIONS FEED. STUB OUT ABOVE ACCESSIBLE CEILING IN, IT/DATA #X21. REFER TO SITE/CIVIL UTILITY PLAN, DRAWING C07.0, FOR CONTINUATION. COORDINATE EXACT LOCATION WITH OTHER, TRADES BEFORE ROUGH-IN. PROVIDE SEAL FOR PENETRATION THRU, EXISTING WALL. REFER TO LINK SEAL DETAIL - OUTDOOR, PENETRATIONS THROUGH WALL DETAIL #4 ON DRAWING E5.3., , DRAWN: RDW, , S1, , S16, , SYSTEMS KEYNOTES, , OHIO, , S#, F, , DLZ OHIO, INC, , GENERAL NOTES
Page 36 :
A., , CONTRACTOR SHALL COORDINATE ALL DEVICE HEIGHTS AND EXACT, LOCATIONS WITH CASEWORK SHOP DRAWINGS AND ARCHITECTURAL, ELEVATION DETAILS., , B., , REFER TO ARCHITECTURAL SHEETS FOR FIRE RATED WALLS AND, CEILINGS. INSTALL FIRESTOP AT PENETRATIONS. INSTALL FIRE RATED, PUTTY AROUND BOXES INSTALLED IN FIRE RATED WALLS AND OFFSET, BACK TO BACK BOXES., , C., , REFER TO DRAWING E5.3, DETAIL #1 FOR FIRE ALARM DEVICES MOUNTING, REQUIREMENTS PER NFPA., , D., , ALL FIRE ALARM CONDUITS SHALL BE FACTORY PAINTED "RED". ALL, PULL/JUNCTION BOX COVERS SHALL BE FACTORY PAINTED RED., , E., , WIRING DEVICES AND RACEWAYS ON EXISTING WALLS TO BE SURFACE, MOUNTED, U.O.N. RACEWAYS AND RACEWAY ACCESSORES SHALL BE LOW, PROFILE, NON-METALLIC RACEWAY SUITABLE TO FINISHED OFFICE AREAS, (I.E. LEGRAND/WIREMOLD 400/800/2300 SERIES OR APPROVED EQUAL)., INSTALL IN NEAT AND WORKMANLIKE MANNER TO MINIMIZE BENDS,, ELBOWS, ETC. PAINT RACEWAYS TO MATCH WALL FINISH COLOR., , F., , REFER TO DRAWING A3.2, GENERAL NOTE E, FOR ACCESS CONTROL, REQUIREMENTS., , G., , NOT ALL KEYNOTES ARE USED ON EVERY SHEET., , DLZ OHIO, INC, , GENERAL NOTES, , S12, , F, S13, , S12, , S5, , S5, , APPRAISAL, X29, , P, , F, , S12, P, , S5, , DATA, COLLECT./, CAUV, X23, , S2, , S3, , S6, , 4 S12, , S4, , S5, , S6, , 1, E4.1, , SECOND FLOOR SYSTEMS PLAN, , S7, , SCALE: 1/8" = 1'-0", , NORTH, , S8, , S9, , S10, , S11, , S12, S13, , S14, , S15, S16, 135° F, , S17, 135° F, , S18, , F, , 135° F, RAID S, , 2, E4.1, , 135° F, , 135° F, , 135° F, , INTERFACE FIRE ALARM CONTROL PANEL WITH ELEVATOR, CONTROLLER SO THAT ACTIVATION OF ELEVATOR LOBBY OR, ELEVATOR SHAFT SMOKE DETECTORS RECALLS THE ELEVATOR TO, THE FIRST FLOOR., ACCESS CONTROL KEYPAD. PROVIDE 1-GANG RECESSED BOX WITH, (2)-1/2"C. STUBBED OUT ABOVE ACCESSIBLE CEILING FOR CONTROL, WIRING AND DATA. COORDINATE EXACT LOCATION WITH OWNER, BEFORE ROUGH-IN., TELEPHONE TERMINAL BOARD 'TTB-1'. BOARD SHALL BE PLYWOOD, AND 8'-0"H. X 4'-0"W X 3/4"D. REFER TO SPECIFICATION 271100 FOR, DETAILED REQUIREMENTS. PAINT (2) COATS MARINE GRADE FIRE, RETARDENT PAINT TO MATCH WALL FINISH. ALSO, REFER TO SHEET, A2.2, KEYED NOTE 0607 FOR MORE INFORMATION., , ATTIC SYSTEMS PLAN, SCALE: 1/8" = 1'-0", , DRAWING NUMBER, , LANCASTER, , NORTH, , 12/5/2018 12:46:16 PM, , C:\users\rwilley\Documents\7001.50_Fairfield_rwilley.rvt, , S14, , S19, , S12, , D, , EQUIPMENT RACK FOR DATA EQUIPMENT (SERVERS, SWITCHES,, PATCH PANEL(S) AND UPS, ETC) FURNISHED BY OWNER., GROUND BUS BAR NO.2. MOUNT AT +7'-0" AFF. REFER TO TELE-DATA, EQUIPMENT GROUND BUS DETAIL #4, DRAWING E5.3. BOND TO MAIN, GROUND BUS BAR NO.1 (IN LOWER LEVEL ELECTRICAL ROOM) USE, #1/0 AWG COPPER GREEN INSULATED CABLE., STUB 2-3"C OUT INTO 1ST FLOOR ACCESSIBLE CEILING SPACE FOR, DATA/TEL CABLES, WIRELESS ACCESS POINT (WAP) LOCATED ON CEILING. WAP, PROVIDED BY OWNER, INSTALLED BY CONTRACTOR. FURNISH AND, INSTALL (2) CAT6 DATA CABLES WITH 10' OF SLACK FOR FINAL, PLACEMENT OF DEVICE., NEW FURNITURE FEED POKE-THRU, REFER TO KEYNOTE #P1 ON, SHEET #E2.1 FOR MORE INFORMATION. FURNISH AND INSTALL FOUR, (4) CAT6 CABLES TO FURNITURE, COORDINATE EXACT LOCATION, BEFORE ROUGH-IN., NEW FURNITURE FEED POKE-THRU, REFER TO KEYNOTE #P1 ON, SHEET #E2.1 FOR MORE INFORMATION. FURNISH AND INSTALL EIGHT, (8) CAT6 CABLES TO FURNITURE, COORDINATE EXACT LOCATION, BEFORE ROUGH-IN., #1/0 AWG COPPER GREEN INSULATED GROUND CABLE. BOND TO, MAIN GROUND BUS #1 (IN MECHANICAL #1502). REFER TO DETAIL #5,, DRAWING E5.3., CARD ACCESS POINT. PROVIDE 1-GANG RECESSED BOX WITH, (2)-1/2"C. STUBBED OUT ABOVE ACCESSIBLE CEILING FOR CONTROL, WIRING AND DATA. COORDINATE EXACT LOCATION WITH OWNER, BEFORE ROUGH-IN., POWER OVER ETHERNET SECURITY CAMERA. CAMERA PROVIDED BY, OWNER, INSTALLED BY CONTRACTOR. FURNISH AND INSTALL (1) CAT6, DATA CABLE WITH 10' OF SLACK FOR FINAL PLACEMENT OF CAMERA., NEW 8" POKE-THRU DEVICE, REFER TO KEYNOTE #P10 ON SHEET, #E2.1 FOR MORE INFORMATION. FURNISH AND INSTALL (4) CAT 6, CABLES TO DEVICE. COORDINATE EXACT LOCATION BEFORE, ROUGH-IN., NEW CONCRETE FLOOR BOX, REFER TO KEYNOTE #P5 ON SHEET, #E2.1 FOR MORE INFORMATION. FURNISH AND INSTALL FOUR (4) CAT6, CABLES AND ASSOCIATED JACKS TO EACH BOX, COORDINATE EXACT, LOCATION BEFORE ROUGH-IN., NEW DEVICE(S) TO BE SURFACE MOUNTED ON EXISTING WALL., NEW FURNITURE FEED POKE-THRU, REFER TO KEYNOTE #P1 ON, SHEET #E2.0 FOR MORE INFORMATION. FURNISH AND INSTALL FOUR, (6) CAT6 CABLES TO FURNITURE, COORDINATE EXACT LOCATION, BEFORE ROUGH-IN., UNIT PROVIDED WITH DUCT SMOKE DETECTOR IN RETURN DUCT., PROVIDE ADDRESSABLE CONNECTION AS NEEDED TO FACP IN, LOWER LEVEL., PROVIDE (1) CAT6 CABLE FROM PANEL 'CP-O' TO COUNTY IT SERVER., VERIFY WITH OWNER EXACT LOCATION OF SERVER., NEW 4"C. WITH PULLSTRING UP TO IT/DATA #X21 FOR UTILITY, COMMUNICATIONS FEED. STUB OUT ABOVE ACCESSIBLE CEILING IN, IT/DATA #X21. REFER TO SITE/CIVIL UTILITY PLAN, DRAWING C07.0, FOR CONTINUATION. COORDINATE EXACT LOCATION WITH OTHER, TRADES BEFORE ROUGH-IN. PROVIDE SEAL FOR PENETRATION THRU, EXISTING WALL. REFER TO LINK SEAL DETAIL - OUTDOOR, PENETRATIONS THROUGH WALL DETAIL #4 ON DRAWING E5.3., , ELECTRICAL, , P, , S1, , 1821-7001-50, , MECH/ ELEC, 207, , S13, , S5, , SECOND FLOOR AND ATTIC SYSTEMS PLANS, , S13, , SYSTEMS KEYNOTES, , PROJECT NUMBER, , P, , WAP, , 4, +60", S12, P, TV, +60" GIS OFFICE, X22, , S#, , E4.1, , S13, P, , CP-O, S12, , DECEMBER 06, 2018, , CONFERENCE, 203, , S5, , S4, , S15, , DATE:, , P, , P, , TKF, , S5, , CORRIDOR, X25, , TV, +84", 2, , S, , S12, , 3P, , CA, , APPRV'D:, , WAP, , S, , S, , POTS 4, S12, , S 2, CA, , F, , P, S12, , P, , IT/DATA, X21, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , F, , CA, , CA, , S1, , S8, , S12, S8, , S8, , P, , 2, , S7, , DATE, , S, , CA, , S2, , S12, , F, , s, , S4, , S, , 2P, , CORRIDOR, X24, , REVISION, , S, , s, , 1,SCREEN, +84", , 2, , S12, , WAP, , P CA, , S12, , NO., , S8, , S19, , DESIGNED: RDW, , CORRIDOR, 204, S8, , CA F, , F, F, , S, , P, , 1,TC, +48", , S4, , 2, , CLOSET, X26, , S12, 2, , F, F, , R ELEVATOR, LOBBY, P, 201, , S8 CA, , S3, , CHK'D: MLH, , F, , F, , S12, , s, , S12, , F, , P, , P, , s, , P, WAP, , s, , s, S17, , S4, , 6, , 4, , s, , P, , MEN'S RR, 206, , 6, , F, , R, , WOMEN'S, RR, 205, , S12, , DRAWN: RDW, , S12, MECH/, STORAGE, 202, , 2, , S10, , OHIO, , TV, +84", , F, , 2, , RE, CONTRACT, X27, , s, , BREAK, ROOM, X28, , F, , ELEV, 106
Page 37 : MECHANICAL EQUIPMENT - ELECTRICAL CONNECTION SCHEDULE, , ---, , 11.3MCA, , FURNACE - F-3, , 120, , 1, , ---, , FURNACE - F-4, , 120, , 1, , FURNACE - F-5A, , 120, , FURNACE - F-5B, , 2#12 + #12G., , 3/4"C., , M.C., , ---, , MECH #202, DRAWING E2.1, , 1, *, , .75, , MDP-24, , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , ---, , BASEMENT, DRAWING E2.0, , 1, *, , 14.4MCA, , 1, , 2P-37, , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , ---, , ATTIC, DRAWING E2.1, , 1, *, , ---, , 11.3MCA, , .75, , 3P-12, , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , ---, , MECH/ELEC #207, DRAWING E2.1, , 1, *, , 1, , ---, , 11.3MCA, , .75, , 2P-41, , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , ---, , ATTIC, DRAWING E2.1, , 1, *, , 120, , 1, , ---, , 11.3MCA, , .75, , 2P-35, , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , ---, , ATTIC, DRAWING E2.1, , 1, *, , FURNACE - F-6, , 120, , 1, , ---, , 11.3MCA, , .75, , 2P-39, , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , ---, , ATTIC, DRAWING E2.1, , 1, *, , CONDENSING UNIT - ACCU-1, , 208, , 1, , ---, , 24MCA, , ---, , MDP(7,9), , 40, , 2, , 2#8 + #10G., , 3/4"C., , M.C., , ---, , EXTERIOR, DRAWING E2.0, , 1, *, , CONDENSING UNIT - ACCU-2, , 208, , 1, , ---, , 24MCA, , ---, , MDP(11,13), , 40, , 2, , 2#8 + #10G., , 3/4"C., , M.C., , ---, , EXTERIOR, DRAWING E2.0, , 1, *, , CONDENSING UNIT - ACCU-3, , 208, , 1, , ---, , 24MCA, , ---, , MDP(15,17), , 40, , 2, , 2#8 + #10G., , 3/4"C., , M.C., , ---, , EXTERIOR, DRAWING E2.0, , 1, *, , CONDENSING UNIT - ACCU-4, , 208, , 1, , ---, , 22MCA, , ---, , MDP(8,10), , 35, , 2, , 2#8 + #10G., , 3/4"C., , M.C., , ---, , EXTERIOR, DRAWING E2.0, , 1, *, , CONDENSING UNIT - ACCU-5A, , 208, , 1, , ---, , 22MCA, , ---, , MDP(12,14), , 35, , 2, , 2#8 + #10G., , 3/4"C., , M.C., , ---, , EXTERIOR, DRAWING E2.0, , 1, *, , CONDENSING UNIT - ACCU-5B, , 208, , 1, , ---, , 22MCA, , ---, , MDP(16,18), , 35, , 2, , 2#8 + #10G., , 3/4"C., , M.C., , ---, , EXTERIOR, DRAWING E2.0, , 1, *, , CONDENSING UNIT - ACCU-6, , 208, , 1, , ---, , 22MCA, , ---, , MDP(19,21), , 35, , 2, , 2#8 + #10G., , 3/4"C., , M.C., , ---, , EXTERIOR, DRAWING E2.0, , 1, *, , EXTERIOR, DRAWING E2.0, , 1, *, , CONDENSING UNIT - ACCU-7, , 208, , 1, , ---, , 13MCA, , ---, , MDP(23,25), , 15, , 2, , 2#8 + #10G., , 3/4"C., , M.C., , ---, , DUCTLESS SPLIT - DSS-1, , 208, , 1, , ---, , .33, , ---, , 2P(10,12), , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , ---, , IT/DATA #X21, DRAWING E2.1, , 1, *, , EXHAUST FAN - EF-1, , 120, , 1, , .028, , ---, , ---, , 1P-11, , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , M.C., , WOMEN #107, DRAWING E2.0, , 1 3, * *, , EXHAUST FAN - EF-2, , 120, , 1, , .028, , ---, , ---, , 1P-11, , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , M.C., , MEN #108, DRAWING E2.0, , 1 3, * *, , EXHAUST FAN - EF-3, , 120, , 1, , .028, , ---, , ---, , 3P-9, , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , M.C., , WOMEN #205, DRAWING E2.1, , 1 3, * *, , EXHAUST FAN - EF-4, , 120, , 1, , .028, , ---, , ---, , 3P-9, , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , M.C., , MEN #206, DRAWING E2.1, , 1 3, * *, 1 3, * *, , 120, , 1, , .028, , ---, , ---, , 1P-11, , 20, , 1, , 2#12 + #12G., , 3/4"C., , M.C., , M.C., , JAN #105, DRAWING E2.0, , ELEC. UNIT HEATER - EUH-1, , 208, , 1, , 5, , ---, , ---, , MDP(27,29), , 40, , 2, , 2#8 + #10G., , 3/4"C., , MFGR, , ---, , BASEMENT, DRAWING E2.0, , ELEC. BASEBOARD HEATER - EBH-1, , 208, , 1, , 1.5, , ---, , ---, , 6, *, , 20, , 2, , 2#12 + #12G., , 3/4"C., , MFGR, , ---, , VESTIBULE #101, DRAWING E2.0, , ELEC. WALL HEATER - EWH-1, , 120, , 1, , 1.5, , ---, , ---, , 4, *, , 20, , 1, , 2#12 + #12G., , 3/4"C., , MFGR, , ---, , 5, *, , PUMP - CP-1, , 120, , 1, , ---, , ---, , 1/6, , MDP-22, , 20, , 1, , 2#12 + #12G., , 3/4"C., , E.C., , E.C., , BASEMENT, DRAWING E2.0, , 2, *, , RECIRC PUMP - RP-1, , 120, , 1, , ---, , ---, , 1/12, , 3P-15, , 20, , 1, , 2#12 + #12G., , 3/4"C., , E.C., , E.C., , MECH #202, DRAWING E2.1, , 2, *, , SUMP PUMP - SP-1, , 120, , 1, , ---, , ---, , 4/10, , MDP-20, , 20, , 1, , 2#12 + #12G., , 3/4"C., , E.C., , E.C., , BASEMENT, DRAWING E2.0, , 7, *, , TANKLESS GAS WATER HEATER - WH-1, , 120, , 1, , ---, , 9, , ---, , 3P-13, , 20, , 1, , 2#12 + #12G., , 3/4"C., , E.C., , ---, , MECH #202, DRAWING E2.1, , 2, *, , CONDUIT AND CABLE SCHEDULE, SOURCE, , RACEWAY, , DESTINATION, , VOLTAGE, , PHASE, , Wire, , OCPD, AMPS, , POWER CONDUCTORS, , CONDUIT, QUANTITY AND, SIZE, , 208, , 3, , 4, , 300A, , 4#350 KCMIL, #3G., , 4"C., , 10, , EXISTING ELECTRIC UTILITY POLE, NEW UTILITY METER 'M-1', MOUNTED TRANSFORMER(S) 'UT-1', , 100, , NEW UTILITY METER 'M-1', , MAIN DIST. PANEL 'MDP', , 208/120, , 3, , 4, , 300A, , 4#350 KCMIL, #3G., , 3-1/2"C., , 100A, , MAIN DIST. PANEL 'MDP', , SURGE PROTECTIVE, DEVICE 'SPD-MDP', , 208/120, , 3, , 4, , 60A, , 4#6, #6G., , 1"C., , 120, , MAIN DIST. PANEL 'MDP', , PANELBOARD '1P', , 208/120, , 3, , 4, , 200A, , 4#3/0, #6G., , 2"C., , 130, , MAIN DIST. PANEL 'MDP', , PANELBOARD '2P', , 208/120, , 3, , 4, , 200A, , 4#3/0, #6G., , 2"C., , 135, , PANELBOARD '2P', , PANELBOARD '3P', , 208/120, , 3, , 4, , 100A, , 4#3, #6G., , 1-1/4"C., , COMMENTS, REFER TO DRAWING C07.0 FOR EXISTING UTILITY, POLE LOCATION. STUB UP CONDUIT AT POLE BASE, AND LEAVE 35 L.F. OF CONDUCTORS COILED UP, AT BASE FOR UTILITY TO MAKE FINAL CONNECTION, , USE SCHEDULE 40 PVC WITH LONG RADIUS, ELBOWS, CABLING LENGTH SHALL NOT, EXCEED 6'-0"., , SCHEDULE NOTES:, 1., , ELECTRIC UTILITY = AMERICAN ELECTRIC POWER (AEP), CONTACT = BOB HARDMAN, 740-689-4723,
[email protected], , DATE, , EXHAUST FAN - EF-5, , DLZ OHIO, INC, , 1, , 1, , E.C. - CONTRACTOR SHALL FURNISH AND INSTALL, SIZE AS SHOWN. SEE REMARKS FOR SIZE, M.C. - STARTER/DISCONNECT TO BE PROVIDED BY EQUIPMENT SUPPLIER, REFER TO MECHANICAL/PLUMBING SCHEDULES., MFGR - INDICATES DISCONNECT INTEGRAL TO UNIT BY MANUFACTURER, 4, (* ) - THERE ARE (4) TOTAL HEATERS, EACH CONNECTED TO AN INDIVIDUAL CIRCUIT., TWO ARE CONNECTED TO PANEL '1P' AND TWO ARE CONNECTED TO PANEL '3P', , 2, (* ) - FURNISH AND INSTALL 125VAC, 20A, 1-POLE MANUAL MOTOR, STARTER WITH TOGGLE DISCONNECT IN NEMA 1 ENCLOSURE., FURNISH WITH RED (RUN) PILOT LIGHT., , 5, (* ) - WALL HEATERS ARE LOCATED IN THE FOLLOWING ROOMS:, WOMEN'S RR #107, MEN'S RR #108 - SHEET E2.0, WOMEN'S RR #205, MEN'S RR #206 - SHEET E2.1, , 3, (* ) - FAN TO BE CONNECTED TO SAME CIRCUIT AS ROOM SERVED, LIGHTING AND BE CONTROLLED ON/OFF VIA OCCUPANCY, SENSOR IN ROOM., , 6, (* ) - THERE ARE (2) TOTAL HEATERS, EACH CONNECTED TO AN INDIVIDUAL CIRCUIT, ON PANEL '1P', CIRCUITS (21,23) AND (25,27)., , (TYP) CABLE/CONDUIT NUMBER,, REFER TO CONDUIT AND CABLE, SCHEDULE, THIS SHEET, , 7, (* ) - UNIT IS CORD AND PLUG, REFER TO PLAN FOR LOCATION., , DRAWN: RDW, , 1, (* ) - UNIT PROVIDED WITH STARTER/DISCONNECT., STARTER/DISCONNECT TO BE MOUNTED/WIRED BY CONTRACTOR., , 135, , FOR SERVICE GROUNDING, ELECTRODE SCHEMATIC, SEE, DETAIL #2 ON DRAWING E5.1., , (N), 3P, 208/120V, 3P,4W, 100A, MLO, 10KAIC, , (N), 2P, 208/120V, 3P,4W, 200A, MLO, 10KAIC, , (IN MECH/ELEC, RM #207), , SECOND FLOOR, , 320A, 120/208V, 3-PHASE METER, CABINET FURNISHED AND, INSTALLED BY CONTRACTOR. FIELD, COORDINATE CABINET, REQUIREMENT WITH AMERICAN, ELECTRIC POWER (AEP). METER, FURNISHED AND INSTALLED BY AEP., , 130, , (N), 1P, 208/120V, 3P,4W, 200A, MLO, 10KAIC, , M, , (IN MAP STORAGE, RM #X19), , 120, , FIRST FLOOR, , 100, , 100A, , REMOTE SURGE PROTECTIVE DEIVCE, (SPD). REFER TO SPECIFICATION 264313, FOR DETAILED INFORMATION, , SPD, (N) SPDMDP, , LOWER LEVEL, , 1, E5.0, , ONE-LINE DIAGRAM, SCALE: N.T.S., , (N), MDP, 208/120V, 3P,4W, 300A, MCB, 42KAIC, , SE RATED, (IN LOWER LEVEL, ELECTRICAL RM), , LANCASTER, , 10, , DRAWING NUMBER, , TO UTILITY POLE WITH POLE, MOUNTED TRANSFORMER(S), REFER, TO SITE/CIVIL UTILITY PLAN, DRAWING C07.0 FOR POLE, LOCATION., , 12/5/2018 12:46:17 PM, , C:\users\rwilley\Documents\7001.50_Fairfield_rwilley.rvt, , METER TO BE SURFACE MOUNTED, ON EXTERIOR WALL. REFER TO, DRAWING E2.0 FOR LOCATION, , (IN CLOSET, RM #X26), , ELECTRICAL, , 120, , 20, , 1821-7001-50, , FURNACE - F-2, , 3P-14, , ELECTRICAL ONE-LINE DIAGRAM AND SCHEDULES, , .75, , PROJECT NUMBER, , 11.3MCA, , E5.0, , ---, , POLE, , DECEMBER 06, 2018, , 1, , REMARK / DISC OR STARTER TYPE, , AMPS, , DATE:, , 120, , DRAWING, LOCATION, , TKF, , FURNACE - F-1, , STARTER, BY, , APPRV'D:, , HP, , DISCONNECT, BY, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , FLA, , CONDUIT, , REVISION, , KW, , CONDUCTORS, , NO., , o, , O.C.P., , DESIGNED: RDW, , VOLTS, , CIRCUIT (*), DESIGNATION, , CHK'D: MLH, , ELECTRICAL DATA, , OHIO, , DESCRIPTION
Page 38 :
Lighting Fixture Schedule, LAMP, , BASIS OF DESIGN, , EQUAL MANUFACTURER, , A1, , LED, , 26 W, , 120V, , A2, , LED, , 33 W, , 120V, , A3, , LED, , 39 W, , 120V, , B1, , LED, , 23 W, , 120V, , B1E, , LED, , 23 W, , 120V, , B1F, , LED, , 23 W, , 120V, , C1, , LED, , 16 W, , 120V, , D1, , LED, , 25 W, , 120V, , 2X4 LED GRID LAY-IN VOLUMETRIC STYLE TROFFER, 3000 LUMENS, 3500K COLOR, 1 DRIVER, UNIVERSAL VOLTAGE WITH ACRYLIC LINEAR PRISMATIC DIFFUSER WITH DIFFUSER TRIM, RINGS., 2X4 LED GRID LAY-IN VOLUMETRIC STYLE TROFFER, 4000 LUMENS, 3500K COLOR, 1 DRIVER, UNIVERSAL VOLTAGE WITH ACRYLIC LINEAR PRISMATIC DIFFUSER WITH DIFFUSER TRIM, RINGS., 2X4 LED GRID LAY-IN VOLUMETRIC STYLE TROFFER, 4800 LUMENS, 3500K COLOR, 1 DRIVER, UNIVERSAL VOLTAGE WITH ACRYLIC LINEAR PRISMATIC DIFFUSER WITH DIFFUSER TRIM, RINGS., 2' X 4', LAY-IN GRID TROFFER WITH 0.125" #12 PATTERN ACRYLIC LENS, 3000 LUMENS, 3500K COLOR, COLD ROLLED STEEL HOUSING, FRAME AND HOUSING WITH WHITE POWDER, COAT FINISH. PAINTED AFTER FABRICATION.., 2' X 4', LAY-IN GRID TROFFER WITH 0.125" #12 PATTERN ACRYLIC LENS, 3000 LUMENS, 3500K COLOR, COLD ROLLED STEEL HOUSING, FRAME AND HOUSING WITH WHITE POWDER, COAT FINISH. PAINTED AFTER FABRICATION WITH 14-WATT EMERGENCY BATTERY PACK., 2' X 4', FLANGED TROFFER WITH 0.125" #12 PATTERN ACRYLIC LENS, 3000 LUMENS, 3500K COLOR, COLD ROLLED STEEL HOUSING, FRAME AND HOUSING WITH WHITE POWDER COAT, FINISH. PAINTED AFTER FABRICATION WITH DRYWALL FRAME KIT., 2' X 2', LAY-IN GRID TROFFER WITH 0.125" #12 PATTERN ACRYLIC LENS, 2000 LUMENS, 3500K COLOR, COLD ROLLED STEEL HOUSING, FRAME AND HOUSING WITH WHITE POWDER, COAT FINISH. PAINTED AFTER FABRICATION., 4' LED SURFACE STRIPLIGHT WITH DIFFUSE LENS, 3000 LUMENS, 80CRI, 3500K COLOR, WHITE FINISH, , D1E, , LED, , 25 W, , 120V, , 4' LED SURFACE STRIPLIGHT WITH DIFFUSE LENS, 3000 LUMENS, 80CRI, 3500K COLOR, WHITE FINISH WITH 10-WATT EMERGENCY BATTERY PACK., , EM, , LED, , 3W, , 120V, , THERMOPLASTIC EMERGENCY LIGHT WITH (2) LED LAMPS, Ni-CAD BATTERY AND SELF-DIAGNOSTICS. FINISH TO BE SELECTED BY ARCHITECT., , F1, , LED, , 44 W, , 120V, , SA, , LED, , 0W, , 120V, , 8" X 54", ROUGH SERVICE FIXTURE, SURFACE MOUNT, 4000 LUMENS, 4000K, CLEAR POLYCARBONATE LENS, MEDIUM DISTRIBUTION, UL LISTED FOR WET LOCATION, STAINLESS, STEEL TAMPER RESISTANT LATCHES., DECORATIVE PENDANT (CHAIN) MOUNTED LANTERN, BLACKENED COPPER FINISH, 120V. FURNISH WITH (3) 4.5W, 300 LUMEN LED NON-DIMMABLE CADLEABRA E12 BASE LAMPS., , SB, , LED, , 9W, , 120V, , DECORATIVE WALL MOUNTED LANTERN, BLACKENED COPPER FINISH, 120V. FURNISH WITH (2) 4.5W, 300 LUMEN LED NON-DIMMABLE CADLEABRA E12 BASE LAMPS., , SC, , LED, , 6W, , 120V, , SD, , LED, , 46 W, , 120V, , LED RECESSED WALL STEP LIGHT, 120V, 5.9W, 62 LUMENS, WET LOCATION LISTED, 3000K COLOR, IP65 RATED, BRONZE FINISH WITH DIE-CAST ALUMINUM HOUSING/FACEPLATE WITH BEGA-US 33-050-K3, LOUVERS, ARCHITECTURAL FLOOD LIGHT, DIE-CAST ALUMINUM HOUSING, 3000K COLOR, 80CRI, 3877 LUMENS, 46 WATTS, ELECTRONIC BALLAST, TIGHT SPOT DISTRIBUTION, VANDAL, EATON INVUE, RESISTANT VISOR, 18" STANCHION MOUNT, 5-YEAR WARRANTY WITH FINISH AS SELECTED BY ARCHITECT., VFS-K-B40-7-LED-E1-TS-XX-SM-18-VFS-4S-8030, , SE, , LED, , 46 W, , 120V, , ARCHITECTURAL FLOOD LIGHT, DIE-CAST ALUMINUM HOUSING, 3000K COLOR, 80CRI, 3877 LUMENS, 46 WATTS, ELECTRONIC BALLAST, MEDIUM SYMMETRICAL RECTANGULAR, DISTRIBUTION, VANDAL RESISTANT VISOR, 18" STANCHION MOUNT, 5-YEAR WARRANTY WITH FINISH BY ARCHITECT., , EATON INVUE, VFS-K-B40-7-LED-E1-MST-XX-SM-18-VFS-4S-8030, , SF, , LED, , 15 W, , 120V, , LUMINAIRE LED, SPC4-22-NB-14WHP-4000K-120-CP-XX-WET-GLR-TXSD, , SG, , LED, , 30 W, , 120V, , 26"L X 4.3"W X 2.7"D VANDAL RESISTANT WALL MOUNTED FIXTURE. MARINE GRADE DIE-CAST ALUMINUM HOUSING, PRISMATIC POLYCARBONATE LESN, CONSTANT CURRENT DRIVER,, 4000K COLOR, 120V, 82 CRI WITH FINISH AS SELECTED BY ARCHITECT AND UL WET LOCATION LABEL. FIXTURE TO HAVE LIFETIME WARRANTY AGAINST VANDALISM. PROVIDE WITH, FUSE AND FUSE HOLDER AND TORX HEAD SCREWS., ARCHITECTURAL FLOOD LIGHT WITH COLOR CHANGING LIGHT ENGINE, 1846 LUMEN OUTPUT, 3000K COLOR, 60 DEGREE FLOOD, 120-277V, POWERSYNC CONTROLLER WITH DATA, INJECTOR AND SURFACE MOUNTED KIT. ALL WITH FINISH TO BE SELECTED BY ARCHITECT., , LUMASCAPE LS9120-30-D-4CW-84-WF-09-PS-XX-006 /, LS6301-XX / LS6540, , LUMENPULSE AS, APPROVED EQUAL, , AS APPROVED EQUAL, , X1, , LED, , 4W, , 120V, , THERMOPLASTIC COMBO EXIT SIGN WITH SINGLE BATTERY, 120V, 4.3W, SEALED Ni-CAD BATTERY, DOUBLE LED HEADS AND SELF DIAGNOSTICS AND RED LETTERS., , LITHONIA LHQM-LED-R-SD, , X2, , LED, , 3W, , 120V, , THERMOPLASTIC EXIT SIGN WITH SEALED LEAD-ACID BATTERY, 120V, 3.3W, WHITE HOUSING AND RED LETTERS., , LITHONIA LHQM-S-W-3-R, , EATON SURE-LITES AS, APPROVED EQUAL, EATON SURE-LITES AS, APPROVED EQUAL, , DUAL-LITE AS, APPROVED EQUAL, DUAL-LITE AS, APPROVED EQUAL, , LITHONIA 2VTL-30L-ADPT-MVOLT-EZ1-L835, , EATON METALUX AS, APPROVED EQUAL, LITHONIA 2VTL-40L-ADPT-MVOLT-EZ1-L835, EATON METALUX AS, APPROVED EQUAL, LITHONIA 2VTL-48L-ADPT-MVOLT-EZ1-L835, EATON METALUX AS, APPROVED EQUAL, EATON METALUX 24GR-LD5-30-A125-UNV-L835-CD1-PAF LITHONIA LIGHTING AS, APPROVED EQUAL, EATON METALUX, LITHONIA LIGHTING AS, 24GR-LD5-30-A125-UNV-EL14W-L835-CD1-PAF, APPROVED EQUAL, EATON METALUX, LITHONIA LIGHTING AS, 24GR-LD5-30-A125-UNV-L835-CD1-PAF-DF-24-W, APPROVED EQUAL, EATON METALUX 22GR-LD5-20-A125-UNV-L835-CD1-PAF LITHONIA LIGHTING AS, APPROVED EQUAL, LITHONIA ZL1N-L48-3000LM-FST-MVOLT-35K-80CRI-WH EATON METALUX AS, APPROVED EQUAL, LITHONIA, EATON METALUX AS, ZL1N-L48-3000LM-FST-MVOLT-35K-80CRI-WH-E10WLCP APPROVED EQUAL, LITHONIA ELM2-LED-X-SD, EATON SURE-LITES AS, APPROVED EQUAL, LITHONIA VAP-4000LM-PCL-MVOLT-GZ10-35K-80CRI, EATON METALUX AS, APPROVED EQUAL, SHADES OF LIGHT - FEDERAL OUTDOOR HANGING, LANTERN - 3 LIGHT SKU OL9905H, SHADES OF LIGHT - FEDERAL OUTDOOR LIGHT MEDIUM SKU OL9905, , EQUAL MANUFACTURER, , HUBBELL COLUMBIA AS, APPROVED EQUAL, HUBBELL COLUMBIA AS, APPROVED EQUAL, HUBBELL COLUMBIA AS, APPROVED EQUAL, HUBBELL COLUMBIA AS, APPROVED EQUAL, HUBBELL COLUMBIA AS, APPROVED EQUAL, HUBBELL COLUMBIA AS, APPROVED EQUAL, HUBBELL COLUMBIA AS, APPROVED EQUAL, HUBBELL COLUMBIA AS, APPROVED EQUAL, HUBBELL COLUMBIA AS, APPROVED EQUAL, DUAL-LITE AS, APPROVED EQUAL, HUBBELL COLUMBIA AS, APPROVED EQUAL, , COMMENTS, , LAY IN, LAY IN, LAY IN, , FIXTURES TO BE SURFACE MOUNTED ON BOTTOM OF JOIST, , MOUNT WITH BOTTOM AT +8'-0" AFF U.O.N., , PROVIDE AN ALLOWANCE OF $500 PER FIXTURE. CHAIN, MOUNT WITH BOTTOM AT +8'-0" AFG., PROVIDE AN ALLOWANCE OF $500 PER FIXTURE. MOUNT AT, HEIGHT AS INDICATED ON EXTERIOR ARCHITECTURAL, ELEVATIONS ON SHEETS A5.1 AND A5.2., WE-EF AS APPROVED INTRIGUE LIGHTING AS MOUNT RECESSED IN WALL WITH BOTTOM AT +12" ABOVE, EQUAL, APPROVED EQUAL, RAMP/WALK., LITHONIA LIGHTING AS HUBBELL OUTDOOR, FIXTURE TO BE MOUNTED ON CONCRETE BASE, REFER TO, APPROVED EQUAL, LIGHTING AS APPROVED DETAIL #3 ON SHEET E5.3., EQUAL, LITHONIA LIGHTING AS HUBBELL OUTDOOR, FIXTURE TO BE MOUNTED ON CONCRETE BASE, REFER TO, APPROVED EQUAL, LIGHTING AS APPROVED DETAIL #3 ON SHEET E5.3., EQUAL, SURFACE MOUNT ON WALL WITH BOTTOM AT +7'-6" AFF., , FIXTURE TO BE MOUNTED ON CONCRETE BASE, REFER TO, DETAIL #3 ON SHEET E5.3. PROVIDE ALL TERMINATIONS AND, CABLING NEEDED FOR A COMPLETE AND OPERABLE SYSTEM., REFER TO LIGHT FIXTURE SCHEUDLE NOTE C BELOW., , DATE, , DESCRIPTION, , REVISION, , WATTAGE VOLTAGE, , DLZ OHIO, INC, , TYPE, , EXOTHERMIC WELD,, TYPICAL, OR CLAMP ONLY,, IF COPPER PIPE, , Adjustable Skylights, , Black, Green, , Receptacle, BMS/Out, Sensors, Sensors, Slider, Station, , (120/277VAC), Alert, Mode, Time, Clock, , Integration Controls, , +, , Integration Controls, , 3, , EXOTHERMIC, WELD, , 2, Blue, Red, , 1, , Black, Brown, , Occupancy, 2, , Not Used, 3, , 4, , 0-10V Dimming Outputs, + + +, Dimmer 3, , Dimmer 2, , OCC-RJ45, (OCCUPANCY COUPLER), , Reset, , Occ, Vac (default), , To additional occupancy, sensors as shown on, , NOTES:, , Status, , drawings, , -, , 1., , ALL WIRE SIZES SHOWN ARE MINIMUM SIZE TO BE INSTALLED. ALL, GROUNDING ELECTRODE CONDUCTOR SIZES SHALL CONFORM TO NEC, ARTICLE 250-94., , 2., , FURNISH AND INSTALL BRAIDED BONDING JUMPERS AT ALL JOINTS AND, TO BUILDING STEEL., , 3., , WHERE MORE THAN ONE METAL UNDERGROUND WATER PIPE ENTERS, THE BUILDING, BOND TO ALL ENTRIES., , 4., , ALL UNDERGROUND/BURIED GROUND RODS AND GROUNDING, ELECTRODE CONDUCTORS SHALL BE AT LEAST 18" BELOW GRADE., , 5., , GROUND RODS SHALL BE INSTALLED PER NEC ARTICLE 250.53G. THE FULL, LENGTH OF THE ELECTRODE SHALL BE IN CONTACT WITH SOIL. THE, ELECTRODE SHALL BE BURIED IN TRENCH A MINIMUM OF 30" DEEP WITH, THE UPPER END OF THE ELECTRODE FLUSH WITH OR BELOW GROUND, LEVEL UNLESS PROTECTED., , Dimmer 1, , Dimmer 3, , +, , -, , Dimmer 2, , +, , -, , Dimmer 1, , +, , 3/4" X 10' COPPER-CLAD, GROUND RODS, SEE NOTE #5, , METAL FRAME OF, BUILDING, , 0-10V Gain, Adjustment, , 1, Default 10%, 20%, 30%, 40%, , High End, , Demand Response, , Energy, Options, , Energy Options DIP Switch, , Low End, , Blue - Load In, Yellow - Load 1 Out, , CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation., , Black - Line In, White/Black - 120V N, White/Orange - 277V N, Blue - EM Line In, Blue - EM Loads Out, , +, , Demand, Response, , MINIMUM #1/0 GREEN INSULATED, COPPER GROUNDING ELECTRODE, , WATER, METER, , BRAIDED BONDING JUMPER, AT METER AND ALL, INSULATED PIPE JOINTS, , Model: OCC-RJ45, Occupancy Sensor Coupler, , -, , GRAY - DIMMER 1, , To additional button stations as shown, on drawings., , RC-6TSB-P4-*, WALL STATION, , 1, E5.1, , TYPICAL DAYLIGHTING-OCCUPANY SENSOR WITH, MANUAL CONTROL WIRING DIAGRAM, SCALE: N.T.S., , 2, E5.1, , SERVICE ENTRANCE GROUNDING ELECTRODE, SYSTEM SCHEMATIC, SCALE: N.T.S., , DRAWING NUMBER, , VIOLET - DIMMER 1, , Scene 1, Scene 2, Scene 3, Raise, Lower, All Off, , 1821-7001-50, , PROJECT NUMBER, , LANCASTER, , 0-10V Dimming, , 12/5/2018 12:46:18 PM, , C:\users\rwilley\Documents\7001.50_Fairfield_rwilley.rvt, , (120/277VAC), , +, +, , A/V, Mode, , 4, , #6 CU, , #1/0 BARE CU GROUND, COPPERWELD TO RODS, , DAYLIGHT SENSOR, (DSRC-FMOIR), *IMMEDIATELY PROVIDES MULTI-ZONE DAYLIGHT, DIMMING UPON POWERUP, , 5, , Wallstations, , BLUE - RELAY IN, , 6, , QuickConnect Cables, , Red - Load 2 Out, Purple - Load 3 Out, , Red, , BLACK - HOT, , Adjustable Skylights, , Switchpack, , White, , METAL, UNDERGROUND, WATER PIPE, , EQUIPMENT AND BRANCH, CIRCUIT GROUNDS REQUIRED, BUT NOT SHOWN, , ELECTRICAL, , QUICK CONNECT COUPLER, (GGRC-COUPLER), , ADJUSTABLE DAYLIGHT SENSOR DOME, , WHT/ORG OR WHT/BLK, NEUTRAL, , BUILDING MAIN, GROUND BUS, BAR NO.1, (BASEMENT), , LIGHT FIXTURE SCHEDULE, , RECORD LOCATIONS OF REMOTE AND/OR CONCEALED FIELD, INSTALLED DEVICES (I.E. POWER PACKS, LIGHTING CONTROLLERS,, ETC. LOCATED ABOVE SUSPENDED CEILING) ON ELECTRICAL, RECORD DRAWINGS. REVISE LOCATIONS ON SUBMITTED SHOP, DRAWINGS AND INCLUDE WITH O&M MANUAL., , LIGHTING LOAD (1), , E5.1, , GENERAL NOTE:, , PANELBOARD 'MDP-2', NEUTRAL BUS, , OHIO, , INTERSYSTEM BONDING, TERMINATION EQUAL TO STORM, COPPER COMPONENTS, SCGB-1KT. MOUNT ADJACENT TO, SERVICE GEAR, , PANELBOARD, 'MPD-2', GROUND, BUS, , DECEMBER 06, 2018, , TYPICAL BOLTED, CONNECTION USING TWO, HOLE COPPER LUG, , TELECOMM GROUND, BUS BAR NO.2, (IT/DATA #X21), , EXOTHERMIC, WELD, , YELLOW, , GROUNDED, CONDUCTOR, , DATE:, , MAIN BONDING JUMPER PER, MANUFACTURER'S RECOMMENDATION, AND IN COMPLIANCE WITH NEC, , TKF, , FURNISH AND INSTALL TWO (2) TOUCH-BASED WALL MOUNTED DMX CONTROLLERS FOR CONTROL OF EXTERIOR RGBW LIGHTS., CONTROLLER TO BE LIKE ACCLAIM LIGHTING #ART-4 PRO OR APPROVED EQUAL. CONTROLLER WILL DRIVE 12-24VDC FIXTURES, WITH FOUR USER PRGRAMMABLE STATIC COLOR PRESETS WITH A MANUAL SPEED AND DIMMER FUNCTION. PROVIDE ONE, CONTOLLER FOR EACH PAIR OF FLOOD LIGHTS, COORDINATE EXACT MOUNTING LOCATION WITH OWNER BEFORE ROUGH-IN., ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE TO TRAIN THE OWNER / OWNER'S PERSONNEL TO ADJUST, OPERATE, AND MAINTAIN THE CONTROLLER. INCLUDE ALL WIRING AS NEEDED BETWEEN CONTROLLER AND LIGHTS AND/OR DATA INJECTOR., , APPRV'D:, , C., , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , ALL FIXTURES SHALL BE U.L. LISTED., , DESIGNED: RDW, , B., , CHK'D: MLH, , ALL LAY-IN FIXTURES TO HAVE EARTHQUAKE CLIPS AND BE SUPPORTED WITH SAFETY CHAIN, SEE SPECIFICATIONS., , DRAWN: RDW, , A., , NO., , LIGHT FIXTURE SCHEDULE NOTES
Page 39 :
Branch Panel: 2P, , Location:, Supply From: MDP, Mounting: Flush, Enclosure: 1, , Volts: 120/208 Wye, Phases: 3, Wires: 4, , A.I.C. Rating: 10kA, Mains Type: MLO, Mains Rating: 200 A, , Location:, Supply From: MDP, Mounting: Surface, Enclosure: 1, , Notes:, NEW FLUSH MOUNTED PANEL, PROVIDE WITH THREE (3) EMPTY 1"C. STUBBED OUT ABOVE CEILING FOR FUTURE USE., , CKT, 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31, 33, 35, 37, 39, 41, , Circuit Description, SPARE, SPARE, SPARE, Lighting - Rooms #X11 to #X15, Lighting - Rooms #X16 to #X19, Lighting - Rooms #101 to #110 & EF-1,2,5, Recepts - Rms #X19, X20 & 103, Wall Heater - EWH-1 - Rm #108, Wall Heater - EWH-1 - Rm #107, Recepts - Rms #103, 107 & 108 and Elec Valves, Baseboard Heater - EBH-1 - Rm #101, -Baseboard Heater - EBH-1 - Rm #101, -Recepts - Rms #101 & 105, Recepts - Rm #104, Recepts - Rm #104, Copier - Rm #104, Recepts - Rm #104, , Trip, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, -20 A, -20 A, 20 A, 20 A, 20 A, 20 A, , Recepts - Rm #104, , 20 A, , Poles, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, 2, -2, -1, 1, 1, 1, 1, 1, , Total Load:, Total Amps:, , B (VA), , C (VA), , 0, 0, , 0, 0, , 549, , 0, , 720, 577, , 720, 579, , 720, , 720, , 720, 1500, , 720, 1500, , 1120, , 1080, , 1260, 750, , 1080, 750, , 750, , 360, , 1000, 750, , 720, 720, , 900, , 1000, , 1000, 900, , 540, 1000, , 720, , 540, , 0, 720, , 9435 VA, 80 A, , A.I.C. Rating:, Mains Type:, Mains Rating:, MCB Rating:, , 10kA, MLO, 200 A, 200 A, , Notes:, NEW SURFACE MOUNTED PANEL, , A (VA), 0, , Volts: 120/208 Wye, Phases: 3, Wires: 4, , DLZ OHIO, INC, , Branch Panel: 1P, , 0, , 8950 VA, 76 A, , 0, 8230 VA, 69 A, , Poles, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, ----, , Trip, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, ----, , Circuit Description, SPARE, SPARE, SPARE, Recepts - Rm #X18, Recepts - Rm #X18, Recepts - Rms #X11, X14 & X15, Recepts - Rm #X12, Recepts - Rm #X12, Recepts - Rm #X13, Recepts - Rms #X13 & X15, Recepts - Rms #X17, Quad Recept - Rm #X13 (Coffee), Printer - Rm #X17, Recepts - Rm #X17, Copier - Rm #X17, Auto Doors - Doors #101A & 101B - Rm #101, Recepts - Rm #X17, Recepts - Exterior, SPACE, SPACE, SPACE, , CKT, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, , CKT, 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31, 33, 35, 37, 39, 41, 43, 45, 47, 49, 51, 53, , Circuit Description, SPARE, SPARE, SPARE, Lighting - Rooms #X21 to #X25, Lighting - Rooms #X26 to #X30, Recepts - Rms #X26 & X27, Quad Recepts - Rm #X27, Floor Box - Rm #X27, Floor Box - Rm #X27, Quad Recepts - Rm #X27, Recepts - Rm #X28, *,Refrig - Rm #X28, Disposal - Rm #X28, Coffee - Rm #X28, Micro - Rm #X28, Recepts - Attic, SPACE, Furnace - F-5B - Attic, Furnace - F-3 - Attic, Furnace - F-6 - Attic, Furnace - F-5A - Attic, SPACE, SPACE, SPACE, SPACE, SPACE, SPACE, , Legend:, , Trip Poles, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, --20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, ------------Total Load:, Total Amps:, , A (VA), 0, , B (VA), , C (VA), , 0, 0, , 446, , 0, , 582, 720, , 34, , 720, , 250, , 1000, , 900, , 1200, , 720, , 1085, , 1000, , 1085, , 0, , 0, , 0, , 1500, , 1080, , 900, 1000, , 360, , 720, , 34, , 360, 900, , 696, , 0, , 1500, 720, , 720, , 0, 360, , 900, , 900, 0, , 1382, , 900, , 0, 1085, , 0, , 0, , 0, 0, , 0, , 0, , 3825, 0, , 12148 VA, 101 A, , 3380, , 12056 VA, 100 A, , 0, 4023, 12736 VA, 106 A, , Poles, 1, 1, 1, 1, 2, -2, -1, 1, 1, 1, 1, 1, 1, 1, 1, 1, ------3, ---, , Trip, 20 A, 20 A, 20 A, 20 A, 20 A, -30 A, -20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, ------100 A, ---, , Circuit Description, SPARE, SPARE, SPARE, Quad Recept - IT/Data #X21, Ductless Split - 'DSS-1' - Rm #X21, -Spec. Recept - IT/Data #X21, -Control Panel 'CP-O' - Rm #X21, Quad Recept - IT/Data #X21, Recepts - Rms #X21, X22 & X24, Recepts - Rm #X23, Recepts - Rm #X22, Recepts - Rms #X23 & X25, Recepts- Rm #X29, Recepts- Rm #X29 & Corridor, Recepts- Rm #X29, Copier - Rm #X29, SPACE, SPACE, SPACE, SPACE, SPACE, SPACE, Panel '3P' - Second Floor Rm #207, ---, , CKT, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44, 46, 48, 50, 52, 54, , Legend:, Demand Factor, 100.00%, 125.00%, 112.50%, 0.00%, 100.00%, 100.00%, 100.00%, 0.01%, , Estimated Demand, 84 VA, 2030 VA, 1125 VA, 0 VA, 14580 VA, 6000 VA, 400 VA, 0 VA, , Panel Totals, Total Conn. Load:, Total Est. Demand:, Total Conn. Current:, Total Est. Demand Current:, , Load Classification, Connected Load, HVAC, 1136 VA, Lighting, 1698 VA, Motor, 960 VA, Other, 0 VA, Receptacle, 16480 VA, Cooling, 68 VA, Heating, 9806 VA, Misc., 4400 VA, Misc. Non-Continuous, 2200 VA, Notes:, * = PROVIDE GROUND FAULT CIRCUIT INTERRUPTING (GFCI) BREAKER, , 26616 VA, 24131 VA, 74 A, 67 A, , Demand Factor, 100.00%, 125.00%, 118.13%, 0.00%, 100.00%, 100.00%, 100.00%, 100.00%, 0.01%, , Estimated Demand, 1136 VA, 2123 VA, 1134 VA, 0 VA, 16480 VA, 68 VA, 9806 VA, 4400 VA, 0 VA, , Panel Totals, Total Conn. Load:, Total Est. Demand:, Total Conn. Current:, Total Est. Demand Current:, , 36688 VA, 35073 VA, 102 A, 97 A, , DATE, , Connected Load, 84 VA, 1624 VA, 1000 VA, 0 VA, 14580 VA, 6000 VA, 400 VA, 3000 VA, , REVISION, , Load Classification, HVAC, Lighting, Motor, Other, Receptacle, Heating, Misc., Misc. Non-Continuous, Notes:, , Branch Panel: MDP, 22kA, MCB, 300 A, 300 A, , 1831, , 528, 1082, , 1085, , 2500, , 100, , 0, , 86, 166, 92, , *,Elevator - Basement, --Panelboard '1P' - First Floor Rm #X19, --Panelboards '2P' & '3P' - Second Floor, ---, , 150 A, 3, 7812, 125, ----200 A, 3, 9435, 0, ----200 A, 3, 12148, 0, ----41747 VA, Total Load:, Total Amps:, 348 A, , 7812, , 180, 7812, , 8950, , 0, 8230, , 12056, , 1000, , 0, , 0, , 41675 VA, 347 A, , 12736, 0, 42291 VA, 353 A, , Circuit Description, SPARE, SPARE, SPARE, Condensing Unit - ACCU-4 - Exterior, -Condensing Unit - ACCU-5A - Exterior, -Condensing Unit - ACCU-5B - Exterior, -Sump Pump - 'SP-1' - Basement, Circ Pump - 'CP-1' - Basement, Furnace 'F-2' - Basement, Lighting - Basement, Lighting Contactors #LC1 & LC2 coils, Time Clock - Basement, Lighting - Exterior Egress (via central inverter unit), Lighting - Exterior Sign, Lighting - Exterior Flag Pole, Central Inverter Unit - Basement, Elevator Pit Recept. - Basement, Elev Cab Lights - Basement, SPACE, SPACE, SPACE, Surge Protective Device 'SPD-MDP', ---, , CKT, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44, 46, 48, 50, 52, 54, , Notes:, NEW SURFACE MOUNTED PANEL, , CKT, 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, , Circuit Description, SPARE, SPARE, SPARE, Recepts - Rms #201, 202, 205 & 206, Lighting - Rooms #201 to #207, EF-3 & EF-4, Recepts - Rms #204 & 207, Water Heater - WH-1 - Rm #202, Recirc Pump - RP-1 - Rm #202, Lighting - Attic, SPACE, SPACE, SPACE, SPACE, SPACE, SPACE, , Trip Poles, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, 20 A, 1, ------------Total Load:, Total Amps:, , A (VA), 0, , B (VA), 0, , 760, , 0, , 1260, , 1085, , 178, , 1500, , 0, , 0, , 1080, , 1500, , 0, 0, , 0, , 0, , 1085, 264, , 0, , 0, , 900, 554, , 1080, , C (VA), , 0, , 0, , 0, 0, , 3825 VA, 32 A, , 0, , 3380 VA, 28 A, , 0, 0, 4023 VA, 34 A, , Poles, 1, 1, 1, 1, 1, 1, 1, 1, 1, ---1, 1, 1, , Trip, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, ---20 A, 20 A, 20 A, , Circuit Description, SPARE, SPARE, SPARE, Recepts - Rm #203, Recepts - Rm #203, Furnace - F-4 - Rm #207, Furnace - F-1 - Rm #202, Elec. Wall Heater - EWH-1 - Rm #206, Elec. Wall Heater - EWH-1 - Rm #205, SPACE, SPACE, SPACE, SPARE, SPARE, SPARE, , CKT, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, , Legend:, , Total Conn. Load:, Total Est. Demand:, Total Conn. Current:, Total Est. Demand Current:, , 101777 VA, 97723 VA, 283 A, 271 A, , Load Classification, HVAC, Lighting, Motor, Other, Receptacle, Heating, Misc., Notes:, , Connected Load, 1136 VA, 672 VA, 264 VA, 0 VA, 3600 VA, 5170 VA, 400 VA, , Demand Factor, 100.00%, 125.00%, 125.00%, 0.00%, 100.00%, 100.00%, 100.00%, , Estimated Demand, 1136 VA, 839 VA, 330 VA, 0 VA, 3600 VA, 5170 VA, 400 VA, , Panel Totals, Total Conn. Load:, Total Est. Demand:, Total Conn. Current:, Total Est. Demand Current:, , 11225 VA, 11455 VA, 31 A, 32 A, , TKF, , LANCASTER, , Panel Totals, , DRAWING NUMBER, , Load Classification, Connected Load, Demand Factor, Estimated Demand, HVAC, 1749 VA, 100.00%, 1749 VA, Lighting, 3991 VA, 125.00%, 4989 VA, Motor, 1960 VA, 108.88%, 2134 VA, Other, 1000 VA, 100.00%, 1000 VA, Receptacle, 31240 VA, 100.00%, 31240 VA, Cooling, 28857 VA, 100.00%, 28857 VA, Heating, 21891 VA, 100.00%, 21891 VA, Misc., 6000 VA, 100.00%, 6000 VA, Misc. Non-Continuous, 5200 VA, 0.01%, 1 VA, Notes:, * = PROVIDE WITH RED BREAKER LOCK KIT TO HOLD THE BRANCH BREAKER HANDLE IN THE OPEN OR CLOSED POSITION., , ELECTRICAL, , 1997, , 1831, , Trip, 20 A, 20 A, 20 A, 35 A, -35 A, -35 A, -20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, 20 A, ---60 A, ---, , 1821-7001-50, , 1831, , 125, 2500, , 250, , 1997, , 1831, , 1200, 1831, , 1082, , 0, , 1831, 1997, , 1831, , 0, 1831, 1997, 1997, , 0, , Poles, 1, 1, 1, 2, -2, -2, -1, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, 1, ---3, ---, , PANELBOARD SCHEDULES, , 0, 1997, , C (VA), , PROJECT NUMBER, , B (VA), 0, , E5.2, , A (VA), 0, , DATE:, , Poles, 1, 1, 1, 2, -2, -2, -2, -2, -2, -1, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , Trip, 20 A, 20 A, 20 A, 40 A, -40 A, -40 A, -35 A, -15 A, -40 A, -20 A, , A.I.C. Rating: 10kA, Mains Type: MLO, Mains Rating: 100 A, , DRAWN: RDW, , Circuit Description, SPARE, SPARE, SPARE, Condensing Unit - ACCU-1 - Exterior, -Condensing Unit - ACCU-2 - Exterior, -Condensing Unit - ACCU-3 - Exterior, -Condensing Unit - ACCU-6 - Exterior, -Condensing Unit - ACCU-7 - Exterior, -Elec. Unit Heater - 'EUH-1' - Basement, -*,Fire Alarm Control Panel - FACP - Basement, , Volts: 120/208 Wye, Phases: 3, Wires: 4, , Legend:, , 12/5/2018 12:46:19 PM, , C:\users\rwilley\Documents\7001.50_Fairfield_rwilley.rvt, , CKT, 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, 25, 27, 29, 31, 33, 35, 37, 39, 41, 43, 45, 47, 49, 51, 53, , Location:, Supply From: 2P, Mounting: Surface, Enclosure: 1, , APPRV'D:, , Branch Panel: 3P, , Notes:, NEW SURFACE MOUNTED PANEL. PANEL TO SERVICE ENTRANCE (SE) RATED., , DECEMBER 06, 2018, , NO., , A.I.C. Rating:, Mains Type:, Mains Rating:, MCB Rating:, , DESIGNED: RDW, , Volts: 120/208 Wye, Phases: 3, Wires: 4, , CHK'D: MLH, , Room, , OHIO, , Location: Basement Electrical, Supply From: See One-Line, Mounting: Surface, Enclosure: 1
Page 40 :
A/C SUPPLY, OR RETURN, DIFFUSER, , DEVICE MOUNTING HEIGHTS, (PER NFPA 72, 2010 EDITION), , HOT, , (MIN), CEILING, , FOR CEILING HEIGHTS LESS THAN 86",, THE VISUAL LENS MOUNTING HEIGHT SHALL, BE WITHIN 6" OF THE CEILING, AUDIBLE ONLY, , BLACK, WHITE, , CEILING MOUNTED, HEAT DETECTOR, , RED (+20 - 24V), , 4", , BLACK (COMMON), , TO EXIT DOOR, 5' (MAX), , 96" MAX (NFPA), ABOVE FINISHED, FLOOR, , 2, , 2, , 2, , 4, , Priori ty 2, Ack, , Fire Al arm, Ack, , SYSTEM WARN INGS, Supe rvis ory, Tro ub le, , Supv, Ack, , Event, Time, , Tro ub le, Ack, , Alar m Si len ced, , System, Reset, , Previ ous, Men u, On, Arm, Off, Disa rm, , Next, , Auto, , Lamp, Test, , R, , REMOTE, ANNUNCIATOR, , 2, , MANUAL PULL, STATION, , 2., , FURNISH AND INSTALL CEILING MOUNT DUAL SENSOR (INFRARED, ULTRASOUND) OCCUPANCY, SENSOR. SEE LIGHTING PLAN FOR LOCATIONS. FIELD ADJUST 0-30 MINUTE TIME DELAY ON, SENSOR PER OWNER'S WRITTEN INSTRUCTION., , 3., , POWER PACK WITH HEAVY DUTY CONTACT AND RELAY CONTROL., , 4., , ALL CONTROL WIRING SHALL BE NOT LESS THAN 2#14, #14G., 1/2"C., U.O.N., , 5., , TRANSFORMER, POWER PACK AND ALL ASSOCIATED COMPONENTS SHALL BE INSTALLED IN, NEMA APPROVED BOX., , OCCUPANCY SENSOR WIRING DETAIL, SCALE: N.T.S., , ELASTOMERIC SEAL ELEMENT LS MODEL, (C, L, S-316, O, OS-316, T), 4100U, , Fire Control, , 2", FINISH GRADE, , WALL, , STUB OUT EMPTY 3/4"C., WHERE SHOWN ON PLANS, , WIRE HANGER AT EACH, CORNER OF FIXTURE, INDEPENDENT OF, CEILING SUPPORT SYSTEM, , GAW910 - TEST WELL, , E5.3, , 4, , FLOOD/SPOT LIGHT CONCRETE BASE DETAIL, , E5.3, , SCALE: N.T.S., , SCALE: N.T.S., , CHK'D: MLH, , 3, RECESSED TROFFER, , LINK SEAL DETAIL - OUTDOOR PENETRATIONS, THROUGH WALL, , MDP-30, , ON PULSE, 'L', FURNISH AND INSTALL 120V, CONDUIT AND WIRE TO, TRANSFORMER, , FIXTURE CLAMP, PROVIDE 2 PER SIDE, , DRAWN: RDW, , COPPER LIGHTNING PROTECTION, OR GROUNDING CONDUCTOR, , TIME CLOCK TC1, TORK #DZS200BP, OFF PULSE, 'UL', , LIGHTING CONTACTOR LC1, SQUARE D TYPE, CLASS 8903, (#LXG30V02CF4R6P1), MECHANICALLY, HELD, 120VAC COIL, RED PILOT LIGHT, CONNECT COIL TO CKT #MDP-28, , NO C NC NO C NC, TIMER, SUPPLY, , CHANNEL 1, COPPER, COPPER CLAD OR, STAINLESS STEEL GROUNDING ROD, , COMMON, , INSTALL SENSOR, SENSOR, PROVIDED OTHERS, , LATCH, L, UNLATCH, UL, , PULSE (ON), PULSE (OFF), , 6, , GROUND TEST WELL DETAIL, SECOND CHANNEL TO BE SPARE, , SCALE: N.T.S., , FURNISH AND INSTALL 2-GANG, DEEP BOX WITH COVER, LOCATE PER, MANUFACTURERS RECOMMENDATION, , TYPICAL RECESSED FIXTURE MOUNTING DETAIL, SCALE: N.T.S., (IT ROOM #X21), , 7/16" DIA, , 2", , TO OWNER, FURNISHED RACK, (IN IT ROOM #X21), , 2", , TO OTHER, METALLIC EQUIP., IN IT ROOM #X21, #2, , 4", , #6, , TORK #EPC1, , 10 POINT GROUNDING, BLOCK AT TELEPHONE, TERMINAL BOARD, , LEC, PROTECTION, , FURNISH AND INSTALL 15 WATT LOW, VOLTAGE TRANSFORMER. TRANSFORMER, PROVIDED BY MECHANICAL CONTRACTOR, , TO ELECTRICAL SERVICE, ENTRANCE MAIN GROUND, BUS BAR NO.1, (IN LOWER LEVEL ELEC. ROOM), , 1, , 2, , 3, , PHOTO, EYE, PC1, , 30A, , NOTE: EXTERIOR EGRESS LIGHTING, CKT #MDP-32, TIME CLOCK CKT #MDP-30, AND COIL CKT #MDP-28 TO BE, ROUTED THRU CENTRAL INVERTER, UNIT, , REMOTE INPUT, 24", , LIGHTING CONTACTOR LC2, SQUARE D TYPE, CLASS 8903, (#LG20V02CFP1), ELECTRICALLY HELD,, 120VAC COIL, HAND-OFF-AUTO SELECTOR, SWITCH, RED PILOT LIGHT, CONNECT, COIL TO CKT #MDP-28, , #6, 30A, PHOTOCELL ON/OFF, , #1/O, , NOTES:, , SCALE: N.T.S., , 7, E5.3, , TELECOMM MAIN GROUNDING BUS BAR 'TMBG', DETAIL, SCALE: N.T.S., , 9, E5.3, , AUTOMATIC ELECTRONIC FLUSH VALVE DETAIL, SCALE: N.T.S., , G, SP, AR, E, , LI, G, H, TI, N, LE, , *COORDINATE LOCATION OF ALL ITEMS, WITH ALL TRADES AND MANUFACTURERS, RECOMMENDATION, , 10, E5.3, , EXTERIOR LIGHTING WIRING DIAGRAM, SCALE: N.T.S., , DRAWING NUMBER, , 5, E5.3, , BUILDING GROUND BUS BAR #1 AND TELECOMM, MAIN GROUNDING BUS BAR 'TMGB' DETAIL, , NOTE:, 1. CONTRACTOR SHALL FIELD COORDINATE BEST LOCATION, OF BUS BAR WITHIN IT ROOM #X21, , PROVIDE LED "LIGHTS ON", PILOT LIGHT, , FL, AG, PO, , 1. PROVIDE 1/4"D x 4"H x 2'-0"L COPPER GROUND BUS BAR WITH, INSULATED WALL BRACKET ASSEMBLY. ERICO EGB-A-14-4-24-CC OR, APPROVED EQUAL AS SPECIFIED. PREDRILLED NEMA BOLT CONFIGURATION, AS INDICATED. PROVIDE BRASS METAL NAME TAGS ON EACH GROUNDING, CABLE INDICATING IDENTIFYING TAG OF EQUIPMENT BEING GROUNDED., TERMINATE GROUNDING CABLE WITH NEMA TWO-HOLE BOLTED LUG., 2. REFER TO EQUIPMENT PLANS FOR GROUNDING CABLE SIZES, QUANTITIES, AND EQUIPMENT DESCRIPTIONS., , ONE TWISTED PAIR, #18 AWG, 3/4"C, , GROUND, BUS BAR, , 30A, , LANCASTER, , INSTALL LOW VOLTAGE LEADS FROM, TRANSFORMER TO SOLENOID, , #1/O, , 12/5/2018 12:46:20 PM, , C:\users\rwilley\Documents\7001.50_Fairfield_rwilley.rvt, , E5.3, , 30A, , EX, T, FL ER, I, EX OO OR, C, D S, T, ER L IG, IR, C, IO IGH N &, UI, R, T, T, SP, EG IN, #, G, A R MD, LI R E, PG, E, S, 36, H S, TI, SP NG, AR, E, , 8, , LAY-IN, CEILING GRID, , E5.3, , C, IR, C, UI, T, C, #M, IR, C, D, UI, PT, 34, SP, #M, AR, D, PE, 32, , NEUTRAL, , 305 - GROUND ROD CLAMP, , LINE, , NO., , ELECTRICAL, , SCALE: N.T.S., , CAST/CORE DRILLED HOLE, , 1821-7001-50, , FIRE ALARM DEVICES - MOUNTING REQUIREMENTS, PER NFPA 72, , ELECTRICAL DETAILS, , DRILLED & TAPPED HOLES FOR, CONDUIT AS SIZED ON PLANS, , E5.3, , FINISHED, FLOOR, , PRESSURE PLATE, , PROJECT NUMBER, , CONCRETE BASE, 12" X 12" X 12", (PROVIDE SLOPE, TO DRAIN), , DECEMBER 06, 2018, , FIRE ALARM, CONTROL PANEL, , BOLT, , DATE:, , 4'-0", , TKF, , 48" MAX (ADA), 42" MIN/54" MAX (NFPA), NFPA 72 2010 EDITION, (SECTION 17.14.4), , W.P., GALV. C.I. J-BOX, W/NEOPRENE GASKET,, HOPE # H402 W/ # P70, COVER. TOP OF BOX, 1/2" ABOVE CONC., , 6'-0", , APPRV'D:, , 5'-0", , DATE, , PULL DOWN, , FAIRFIELD COUNTY AUDITOR'S OFFICE, REAL ESTATE DEPARTMENT, , FIXTURE TYPES 'SD', AND 'SE', , REVISION, , FIRE ALARM, , NO., , FIRE, PHONE, JACK, , E5.3, , FURNISH AND INSTALL MANUAL OFF OVERRIDE SWITCH(S) WHERE INDICATED ON PLANS., , DESIGNED: RDW, , 80" (ADA), 80" MIN (NFPA), NFPA 72 2010 EDITION, (SECTION 18.5.4.1), , 1., , (MAX 3 SENSORS, PER ZONE), , RECORD LOCATIONS OF REMOTE AND/OR CONCEALED FIELD, INSTALLED DEVICES (I.E. POWER PACKS, LIGHTING CONTROLLERS,, ETC. LOCATED ABOVE SUSPENDED CEILING) ON ELECTRICAL, RECORD DRAWINGS. REVISE LOCATIONS ON SUBMITTED SHOP, DRAWINGS AND INCLUDE WITH O&M MANUAL., , AC Po wer, , Alarm, Silence, , Mor e, Info, , Enable, , Disable, , CODED NOTES:, , #, , FINISHED WALL, , ALARMS, Fire Al arm Prior ity 2 Al arm, , E5.3, , RED, , 1, , NFPA 72 2010 EDITION, (SECTION 17.7.3.2.1 SMOKE DETECTOR), (SECTION 17.6.3.1.3.1 HEAT DETECTOR), , GENERAL NOTE:, , 1, , LIGHTING, LOAD, , HEAT DETECTORS, NEVER HERE, WALL MOUNTED, SMOKE/HEAT, DETECTOR, , NOTE:, REFER TO THE PROPER DEVICE, INSTALLATION INSTRUCTIONS, FOR BACKBOX MOUNTING HEIGHT, , RED, , 5, , FIRE, , FIRE, , REF. 80" MIN (IBC), REF. 96" MAX (IBC), ABOVE FINISHED FLOOR, , 3, , BLUE (SIGNAL), , 12", (MAX), , HEAT DETECTORS, ACCEPTED HERE, , AUDIBLE/VISUAL, & VISUAL ONLY, APPLIANCES, SYNCHRONIZE MORE THAN, TWO APPLIANCES IN ANY, FIELD OF VIEW., NFPA 72 2010 EDITION, (SECTION 18.5.4.3.2(4)), , NEUTRAL, , OHIO, , FIRE, , NFPA 72 AUDIBLE APPLIANCE 6" MIN BELOW, FINISHED CEILING 90" MIN ABOVE FINISHED, FLOOR (OTHER MOUNTING HEIGHTS SHALL BE, PERMITTED BY THE AHJ PROVIDING IT MEETS, THE SOUND LEVEL OUTPUT REQUIRED), , NFPA 2010 17.7.3, (SMOKE DETECTOR, SPACING), 17.6.3 (HEAT, DETECTOR SPACING), , NOTE:, MEASUREMENTS, SHOWN ARE TO THE, CLOSEST EDGE OF THE, DETECTOR, , DLZ OHIO, INC, , 4", , 3'